Siemens 6ES7221-1BF22-0XA0 S7-200 EM 221 Eight-Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the S7-200 CPU 22x expansion system.
- Keep the input reference arrangement consistent within each four-channel group.
- Limit two-wire sensor quiescent current to 1 mA.
- Use shielded wiring up to 500 m or unshielded wiring up to 300 m.
6ES7221-1BF22-0XA0 S7-200 EM 221 Eight-Input Module
Eight 24 V DC sinking or sourcing inputs in a 46 mm-wide S7-200 expansion module with removable I/O terminals.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7221-1BF22-0XA0 |
| Product Type | Digital input expansion module |
| Core Function | Acquisition of discrete field contacts |
| Application | CPU 22x input expansion |
Eight input points
The input circuit accepts sinking or sourcing field wiring.
Two isolated groups
Optocoupler isolation is arranged in groups of four channels.
Removable terminals
Plug-in I/O terminals support wiring service work.
Product Overview
6ES7221-1BF22-0XA0 expands a SIMATIC S7-200 CPU 22x with eight digital inputs. The 24 V DC inputs support sinking or sourcing connections, with optical isolation organized in four-channel groups.
The narrow module uses plug-in I/O terminals and draws no more than 30 mA from the 5 V backplane. Field-device selection should account for the input thresholds and the 1 mA maximum quiescent current of two-wire sensors.
Key Functions
Read eight external states
The inputs recognize logic 1 from +15 to +30 V and logic 0 from 0 to 5 V.
Separate field signal groups
Optocouplers provide electrical isolation, with four channels grouped together.
Support input wiring service
Plug-in I/O terminals allow the field-connection assembly to be disconnected during module servicing.
Official Specifications
| Digital inputs | 8 |
|---|---|
| Input voltage and polarity | 24 V DC; sinking or sourcing |
| Logic voltage thresholds | Signal 0: 0–5 V; signal 1: +15 to +30 V |
| Typical signal-1 current | 4 mA |
| Maximum 0-to-1 input delay | 4.5 ms |
| Two-wire sensor quiescent-current limit | 1 mA |
| Maximum input-cable length | 500 m shielded; 300 m unshielded |
| Isolation technology and grouping | Optocoupler; groups of 4 channels |
| Maximum backplane current | 30 mA from 5 V DC |
| Typical power loss | 2 W |
| I/O termination | Plug-in terminals |
| Dimensions and weight | 46 × 80 × 62 mm (W × H × D); approximately 150 g |
Frequently Asked Questions
Can I mix input reference potentials between every channel of 6ES7221-1BF22-0XA0?
Electrical isolation is arranged in groups of four channels rather than separately for every channel.
Will a sensor output of 12 V reliably turn on 6ES7221-1BF22-0XA0?
The specified signal-1 voltage range is +15 to +30 V.
Can a two-wire sensor with 1.5 mA off-state current be connected to 6ES7221-1BF22-0XA0?
The permissible two-wire sensor quiescent current is limited to 1 mA.
How much delay should I allow when an input on 6ES7221-1BF22-0XA0 turns on?
The maximum 0-to-1 input delay is 4.5 ms.
What length is permitted for an unshielded sensor run to 6ES7221-1BF22-0XA0?
The maximum unshielded input-cable length is 300 m.
Can the I/O terminal assembly be unplugged when servicing 6ES7221-1BF22-0XA0?
The module has plug-in I/O terminals.
How much CPU backplane capacity should I reserve for 6ES7221-1BF22-0XA0?
Reserve up to 30 mA from the 5 V DC backplane supply.