Overview
- Match the IM 153-2AA02 or IM 153-2AB01 redundancy arrangement.
- Do not combine this bus module with an IM 153-2BA10 successor.
- Provide the active-bus mounting rail and correctly sized I/O bus bases.
- Close vacant slots and the final bus module with the appropriate covers.
6ES7195-7HD00-0XA0 SIMATIC ET 200M BM IM/IM Legacy Interface Bus Module
The BM IM/IM base assigned to legacy IM 153-2AA02 and IM 153-2AB01 redundancy arrangements.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7195-7HD00-0XA0 |
| Product Type | Active backplane base |
| Core Function | Preserving station backplane continuity |
| Application | Legacy redundant ET 200M interface arrangements |
Legacy interface pairing
The order assignment covers the IM 153-2AA02 and IM 153-2AB01 arrangements.
Active backplane
Other station modules remain reachable when one module is absent.
Version-specific replacement
The IM 153-2BA10 successor cannot operate on this bus base.
Product Overview
6ES7195-7HD00-0XA0 forms the interface-side active backplane for the legacy ET 200M BM IM/IM arrangement. The order assignment pairs it with the redundant IM 153-2AA02 or IM 153-2AB01 interface configuration.
Interface generation is a decisive replacement constraint: the IM 153-2BA10 successor cannot be operated on this bus module. The station also requires the active-bus mounting rail and the appropriate downstream I/O bus bases and covers.
Key Functions
Carry the interface pair
The BM IM/IM arrangement provides two positions for the redundant interface modules.
Maintain the station bus
Active bus modules keep other station modules reachable when a module is removed.
Support the legacy redundancy layout
The base belongs to the interface-generation-specific ET 200M redundancy arrangement.
Official Specifications
| Interface mounting positions | 2 for the BM IM/IM arrangement |
|---|---|
| Approximate module weight | 133 g |
| Permitted I/O module replacement state | RUN operation |
| ET 200M operating temperature | 0–60 °C horizontally mounted; 0–40 °C vertically mounted |
| ET 200M operating humidity | 10–95% RH, without condensation |
| ET 200M storage and transport temperature | −40 to +70 °C in original packaging |
| ET 200M degree of protection | IP20 in accordance with IEC 60529 |
| ET 200M shock-test severity | Half-sine pulse, 15 g peak for 11 ms; 3 shocks in each direction on each of 3 axes |
Frequently Asked Questions
Is 6ES7195-7HD00-0XA0 the base assigned to the legacy IM 153-2AA02 and IM 153-2AB01 arrangements?
The ET 200M order assignment specifies this bus module for redundancy with those interface versions.
Can I install an IM 153-2BA10 successor on 6ES7195-7HD00-0XA0?
The IM 153-2BA10 successor cannot be operated on this bus module.
What type of rack support is required for an active-bus installation using 6ES7195-7HD00-0XA0?
Use the ET 200M mounting rail designed to accommodate active bus modules.
Can I extend a station containing 6ES7195-7HD00-0XA0 onto a second rail through interface modules?
An ET 200M station is limited to one mounting rack and cannot couple additional racks through interface modules.
How should I protect vacant backplane positions in the station with 6ES7195-7HD00-0XA0?
Close unused positions with backplane bus covers and close the final bus module with the bus-module cover.
Will the station bus using 6ES7195-7HD00-0XA0 remain accessible if an I/O module is absent?
The active backplane allows the other modules to remain reachable when a module is missing.
Which bus-base sizes follow 6ES7195-7HD00-0XA0 for the S7-300 I/O modules?
Use BM 2 × 40 for one or two 40 mm modules and BM 1 × 80 for an 80 mm module.