- Use an I/O module requiring BaseUnit type D0.
- Follow the installed I/O module’s assignments for all twelve process terminals.
- Apply the separate bus and process-terminal current limits.
- Keep the correct N and FE connections for the integrated filter.
- Do not install the system shield support or shield terminal on this BaseUnit.
- Do not treat the dark base as a new-group infeed or an external P1/P2/AUX tapping point.
6ES7193-6BP00-0BD0 SIMATIC ET 200SP BU20-P12+A0+0B D0 BaseUnit
A D0 push-in BaseUnit with twelve process terminals, an integrated N-to-FE filter and no external P1, P2 or AUX terminal access.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7193-6BP00-0BD0 |
| Product Type | Dark-colored D0 BaseUnit |
| Core Function | Providing the module wiring base while continuing the potential group |
| Application | ET 200SP I/O modules requiring BaseUnit type D0 |
D0 module interface
Use the I/O module’s specified D0 BaseUnit requirement.
Integrated filter
The mains filter is connected between N and functional earth.
No shield support
The system shield support and shield terminal must not be installed on this base.
Product Overview
6ES7193-6BP00-0BD0 is the BU20-P12+A0+0B BaseUnit for ET 200SP I/O modules requiring type D0, using twelve push-in process terminals in a 20 mm-wide base.
The dark-colored base continues the existing P1, P2 and AUX buses, with module-specific process wiring and a filter between N and functional earth.
Key Functions
Provide the D0 process interface
The installed I/O module defines the twelve process-terminal assignments within the D0 base.
Continue the station buses without external taps
P1, P2 and AUX connect to the BaseUnit on the left, while their busbars have no external terminal access on this variant.
Provide filtering between neutral and functional earth
The integrated mains filter is located between N and FE as part of the D0 wiring arrangement.
Official Specifications
| P1/P2 and AUX DC Rating | 120 V DC; AUX at the same potential group as P1/P2 or PE |
|---|---|
| P1/P2 and AUX AC Rating | 277 V AC; AUX at the same potential group as P1/P2 or PE |
| Process-Terminal AC Rating | 277 V phase-to-neutral; 480 V between L1, L2 and L3 |
| Maximum Process-Terminal Current | 5 A |
| P1/P2 and AUX Bus Capacity | 10 A |
| Current-Carrying Capacity at 60 °C | Maximum 5 A |
| Process-Terminal Construction and Count | 12 push-in terminals per slot |
| External Busbar Access | No external P1/P2 or AUX bus terminals; no add-on terminals |
| Integrated Filter Connection | Between N and FE |
| Insulation Test Voltage | 3100 V DC |
| Mechanical Coding | Automatic coding |
| Conductor Cross-Section | 0.14–2.5 mm²; AWG 26–14 |
| Horizontal Operating Temperature | −30 to +60 °C |
| Vertical Operating Temperature | −30 to +50 °C |
| Standard Maximum Installation Altitude | 2000 m above sea level |
| Dimensions and Approximate Weight | 20 × 117 × 35 mm; 47 g |
Frequently Asked Questions
Can I attach a shield support and shield terminal to 6ES7193-6BP00-0BD0?
The system shield connection is not intended for this BaseUnit and must not be installed.
Where is the integrated mains filter connected in 6ES7193-6BP00-0BD0?
The filter is connected between neutral N and functional earth FE.
Does 6ES7193-6BP00-0BD0 provide an accessible terminal for the AUX bus?
The AUX bus is continued internally without external terminal access.
Can I use 6ES7193-6BP00-0BD0 as a new potential-group infeed?
This dark-colored base continues the group from the left rather than starting a new group.
Which I/O module requirement should I match before selecting 6ES7193-6BP00-0BD0?
The module must require BaseUnit type D0.
How much field current can one process terminal on 6ES7193-6BP00-0BD0 carry?
The maximum process-terminal current is 5 A.
How should I determine the signal wiring for terminals 1–12 on 6ES7193-6BP00-0BD0?
The installed D0 I/O module determines the process-terminal assignments.