Siemens 6ES7193-0CA30-0XA0 ET 200B TB3/DC Spring-Terminal Block
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Compatible compact electronics include ET 200B 16DI, 16DO, 8DI/8DO, 8DI/8DO HWA and 8RO.
- Do not substitute the compact base for the wider 16DO/2A or 32-channel base arrangement.
- Use the wiring assignment for the actual electronics block.
- Set mechanical coding to the correct 24 V digital module class.
- Use 1–99 with IM 308-C or S7/M7 DP masters, or 3–99 with IM 308-B, and apply the STOP/RUN transition after changing the address.
- Use a TR5-T 1.6 A, 250 V fuse and follow the STOP/remove-electronics procedure for replacement.
- Keep supply voltage including ripple within 18.5–30 V DC and the ambient temperature within 0 to +60 °C.
6ES7193-0CA30-0XA0 ET 200B TB3/DC Spring-Terminal Block
The 160 mm wide TB3/DC spring-terminal base with a three-tier wiring field, a 24 V DC supply interface and a TR5-T 1.6 A protection fuse.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7193-0CA30-0XA0 |
| Product Type | Digital-station terminal block |
| Core Function | Holds the permanent field wiring beneath the electronics |
| Application | Compact SIMATIC ET 200B digital I/O stations |
Compact terminal field
The base occupies 160 mm of mounting width.
Spring-latch wiring
The three numbered terminal tiers carry the fixed field connections.
Plug-on electronics
Input, output, mixed or relay electronics determine the installed signal functions.
Product Overview
6ES7193-0CA30-0XA0 forms the compact spring-terminal wiring base for compatible ET 200B digital electronics blocks.
The 160 mm base retains the permanent wiring and station settings beneath the removable electronics, with three terminal tiers, a 24 V DC supply interface and a replaceable 1.6 A fuse for the sensor and internal-logic supplies.
Key Functions
Hold the compact station wiring
The three-tier spring-latch terminal field retains the field connections independently of the plug-on electronics block.
Match the correct electronics class
The coding slide is set to position 1 for 24 V digital modules to prevent the wrong electronics class from being inserted.
Provide the protected station supply
The fused supply protects the sensor circuit against short circuits and the internal logic against reversed polarity and supply spikes.
Official Specifications
| Rated DC supply and permissible range | 24 V DC nominal; 18.5–30 V DC including ripple |
|---|---|
| Electronics current consumption | 100 mA typical; 170 mA maximum |
| Galvanic isolation | Between the electronics block and PROFIBUS DP |
| Operating temperature | 0 to +60 °C |
| Dimensions (W × H × D) | 160 × 130 × 59 mm |
| Approximate terminal-block weight | 600 g |
| Conductor cross-section without ferrule | 0.08–2.5 mm² for supply and signal conductors |
| Conductor cross-section with ferrule | Up to 1.5 mm² for supply and signal conductors |
| Sensor-supply and logic-protection fuse | TR5-T 1.6 A, 250 V miniature fuse |
| Mechanical module-class coding | Six-position coding slide; position 1 for 24 V digital modules |
| Station-address selector setting range | Two decimal digits, 00–99 |
| Fieldbus connector | 9-pin PROFIBUS DP interface |
| Field-terminal layout | Three-tier spring-latch connections, numbered 1–16, 17–32 and 33–48 |
| Mounting options | Standard sectional rail or direct mounting on a flat surface |
Frequently Asked Questions
How are wires inserted into the spring terminals of 6ES7193-0CA30-0XA0?
Open the spring latch with a screwdriver, insert the conductor and release the latch to clamp the wire.
Can the 16DO/2A high-current electronics be fitted to 6ES7193-0CA30-0XA0?
The 16DO/2A electronics require the wider TB2/DC, TB2-4/DC, TB4/DC or TB4M/DC base instead.
How much horizontal mounting space is needed for 6ES7193-0CA30-0XA0?
The terminal base is 160 mm wide.
Which replacement fuse belongs in 6ES7193-0CA30-0XA0?
Use a TR5-T 1.6 A, 250 V miniature fuse, available under replacement order number 6ES7193-0DA00-0XA0.
Can the field wiring stay connected when the electronics block is removed from 6ES7193-0CA30-0XA0?
The permanent field wiring remains on the terminal base when the plug-on electronics block is removed.
How does 6ES7193-0CA30-0XA0 prevent fitting the wrong electronics module class?
The six-position mechanical coding slide is assigned to the electronics class, with position 1 used for 24 V digital modules.
Are the terminal functions on 6ES7193-0CA30-0XA0 identical for every compatible electronics block?
The terminal assignments follow the installed input, output, mixed-I/O or relay electronics block.