- Use NEC Class 2 power and wire the 1L+ and 2L+ potential groups to suit the selected sensor and actuator circuits.
- Parameterize all eight channels and the CPU-stop output response before energizing the loads.
- Limit output loading to 1.3 A per channel and 3.9 A per group, without paralleling outputs for increased current.
- Use correctly assembled M12 connections and keep unshielded field wiring within 30 m.
6ES7147-6BG00-0AB0 SIMATIC ET 200eco PN 8DIO Field I/O Block
IP65/67 field block with eight individually configurable digital input/output channels, M12 connections and a two-port PROFINET switch.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7147-6BG00-0AB0 |
| Product Type | Configurable digital field I/O block |
| Core Function | Distributed sensor and actuator connection |
| Application | Cabinet-free PROFINET IO installations |
Channel-by-channel I/O selection
Each of the eight DIO channels can be parameterized as a digital input or output, with input operation as the default.
Protected field connections
IP65/67 construction and 4/5-pin M12 connectors support installation close to sensors and actuators.
Network and load diagnostics
PROFINET monitoring covers supply voltage, sensor and actuator wire breaks, short circuits and group errors.
Product Overview
6ES7147-6BG00-0AB0 connects sensors and actuators directly in the field through eight configurable digital I/O channels and sealed M12 connectors.
Each channel can be assigned as an input or output, allowing the station configuration to match the machine wiring while PROFINET diagnostics report supply, wire-break and short-circuit faults.
Key Functions
Channel-by-channel I/O selection
Each of the eight DIO channels can be parameterized as a digital input or output, with input operation as the default.
Protected field connections
IP65/67 construction and 4/5-pin M12 connectors support installation close to sensors and actuators.
Network and load diagnostics
PROFINET monitoring covers supply voltage, sensor and actuator wire breaks, short circuits and group errors.
Official Specifications
| Configurable channels | 8 DIO channels, each selectable as input or output |
|---|---|
| Rated supply and load voltage | 24 V DC; 2L+ range 20.4–28.8 V |
| Supply current limits | 4 A maximum from 1L+ and 4 A maximum from 2L+ |
| Typical electronics current and loss | 100 mA; 6.5 W |
| Sensor supply output | 100 mA maximum per output; electronic short-circuit protection |
| Input characteristic | IEC 61131 Type 3 |
| Input switching thresholds | Signal 0: −3 to +5 V; signal 1: +11 to +30 V |
| Typical input current and delay | 7 mA; 3 ms for each transition |
| Maximum output channel current | 1.3 A |
| Output-group current | 3.9 A maximum per group up to 60°C |
| Electronic short-circuit threshold | 1.8 A typical |
| Output leakage current | 1.5 mA maximum in the off state |
| Load switching limits | 100 Hz resistive; 0.5 Hz inductive; 1 Hz lamp load |
| Lamp-load rating | 5 W maximum |
| Unshielded field cable length | 30 m maximum for inputs and outputs |
| Ethernet interface | 100BASE-TX through M12 ports with integrated switch; 100 Mbit/s maximum |
| Network functions | MRP media redundancy, IRT high flexibility and prioritized startup |
| Electrical separation | Ethernet isolated from electronics; no channel-to-channel isolation |
| Protection and connectors | IP65/67; 4/5-pin M12 circular connections |
| Dimensions and weight | 60 × 175 × 49 mm (W × H × D); approximately 910 g |
Frequently Asked Questions
Does 6ES7147-6BG00-0AB0 have eight inputs plus eight independent outputs?
The block has eight shared DIO channels, each individually configured as an input or an output.
How are the channels on 6ES7147-6BG00-0AB0 configured before commissioning?
Assign the required input or output function to each channel in the PROFINET configuration, with digital input as the default setting.
Can all four outputs in one group of 6ES7147-6BG00-0AB0 carry 1.3 A together?
The total current of an output group must remain within 3.9 A up to 60°C even though a single channel can carry 1.3 A.
What power-supply arrangement is required for 6ES7147-6BG00-0AB0?
Use a 24 V DC supply meeting NEC Class 2 and keep the 2L+ load voltage within 20.4–28.8 V.
How can outputs on 6ES7147-6BG00-0AB0 behave when the CPU stops?
The configured CPU-stop response can switch outputs off or retain their last value.
Can 6ES7147-6BG00-0AB0 participate in an MRP ring?
The integrated PROFINET switch supports MRP media redundancy.
Which wiring faults can 6ES7147-6BG00-0AB0 diagnose?
The block can report actuator and sensor wire breaks, short circuits, sensor-supply faults and group errors.