- Overview
- Hot Selling Models
- Recommended Products
Overview
- Assign the four DIQ channels according to the required input/output balance.
- Keep each output at or below 0.5 A and each four-output group at or below 2 A.
- Use the correct M8 I/O, power and shielded ET-Connection cables.
- Use STEP 7 V13 SP1 or later in TIA Portal, or STEP 7 V5.5 SP4 Hotfix 3 or later for the supported engineering arrangement.
6ES7143-5BF00-0BA0 ET 200AL DIQ 4 + DQ 4 Digital I/O Module
A compact field module with four configurable DIQ channels, four fixed digital outputs and eight M8 I/O connections.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7143-5BF00-0BA0 |
| Product Type | Distributed digital I/O module |
| Core Function | Configurable sensor inputs and load switching |
| Application | ET 200AL field I/O stations |
Four configurable channels
Each DIQ position can serve as a digital input or output, allowing up to four inputs alongside the four fixed outputs or up to eight outputs in total.
Two output load groups
Current-sourcing outputs deliver up to 0.5 A per channel with a maximum of 2 A in each four-output group.
Field diagnostics and protection
Electronic short-circuit protection, status LEDs and configurable diagnostic alarms support field commissioning and maintenance.
Product Overview
6ES7143-5BF00-0BA0 combines four channels configurable as digital input or output with four dedicated digital outputs.
The module uses 24 V DC load supplies and M8 wiring for field installation, with channel status indication, electronic output protection and configurable substitute values.
Key Functions
Four configurable channels
Each DIQ position can serve as a digital input or output, allowing up to four inputs alongside the four fixed outputs or up to eight outputs in total.
Two output load groups
Current-sourcing outputs deliver up to 0.5 A per channel with a maximum of 2 A in each four-output group.
Field diagnostics and protection
Electronic short-circuit protection, status LEDs and configurable diagnostic alarms support field commissioning and maintenance.
Official Specifications
| Channel arrangement | 4 configurable DIQ channels plus 4 fixed DQ channels |
|---|---|
| Load supplies | 1L+ and 2L+: 24 V DC; permitted 20.4–28.8 V DC |
| Input characteristic | P-reading; IEC 61131 type 3 |
| Input logic levels | Logic 0: −3 to +5 V; logic 1: +11 to +30 V |
| Input delay | 1.2–4.8 ms for either signal transition |
| Output channel rating | Current-sourcing, 0.5 A |
| Maximum output-group current | 2 A per group of four outputs |
| Output protection | Electronic short-circuit protection per channel; typical response threshold 0.7 A |
| Sensor supply | 4 outputs; maximum total sensor current 0.7 A |
| Maximum lamp load | 5 W |
| Switching frequencies | 100 Hz resistive; 0.5 Hz inductive; 1 Hz lamp load |
| Maximum unshielded I/O cable | 30 m |
| Two-wire sensor limit | Maximum quiescent current 1.5 mA |
| I/O connections | 8 × M8, 3-pole |
| Supply and ET-Connection | M8 4-pole power; M8 4-pin shielded ET-Connection |
| Typical power loss | 2.5 W |
| Protection rating | IP65/IP67 |
| Operating temperature | −30 to +55 °C |
| Dimensions | 30 × 159 × 40 mm |
| Approximate weight | 145 g |
Frequently Asked Questions
Can I configure all eight channels of 6ES7143-5BF00-0BA0 as outputs?
Four channels are fixed outputs and the other four can be parameterized as outputs, giving a maximum of eight outputs.
How many digital inputs remain when the DIQ channels of 6ES7143-5BF00-0BA0 are used as outputs?
A DIQ channel used as an output is unavailable as an input, so the input count depends on the four DIQ assignments.
Can one output on 6ES7143-5BF00-0BA0 supply a 0.8 A actuator?
The rated output current is 0.5 A per channel, so a 0.8 A actuator exceeds that channel rating.
What current limit applies to a four-output group on 6ES7143-5BF00-0BA0?
Each group of four outputs is limited to a total current of 2 A.
Can I use two-wire proximity sensors with 6ES7143-5BF00-0BA0?
Two-wire sensors are supported when their quiescent current does not exceed 1.5 mA.
How far can I run unshielded sensor or actuator cables from 6ES7143-5BF00-0BA0?
The maximum unshielded I/O cable length is 30 m.
Which TIA Portal release can configure 6ES7143-5BF00-0BA0?
The module is configurable from STEP 7 V13 SP1 in TIA Portal.