Siemens 6ES7141-5AH00-0BA0 SIMATIC ET 200AL DI 16x24VDC M12 Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use five-pole M12 sensor connections and the specified M8 supply and ET-Connection cables.
- Allocate sensor loads within the combined 1.4 A supply limit.
- Select the correct device description and engineering release, including Hotfix 7 for the stated STEP 7 V5.5 SP4 configuration.
- Keep unshielded sensor cables within 30 m and preserve the sealing required for IP65/67 field installation.
6ES7141-5AH00-0BA0 SIMATIC ET 200AL DI 16x24VDC M12 Input Module
Sixteen 24 V DC digital inputs through eight M12 connectors, with a 1.4 A combined sensor supply and IP65/67 field protection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7141-5AH00-0BA0 |
| Product Type | Digital sensor input block |
| Core Function | Collection of field-level switching signals |
| Application | ET 200AL distributed machine I/O |
Sixteen-input field acquisition
Eight M12 sensor connections bring sixteen 24 V DC input signals into the ET 200AL station.
Shared protected sensor supply
Eight sensor supply outputs share a 1.4 A total current budget and electronic short-circuit protection.
Identification and service diagnostics
I&M records, configurable diagnostic alarms and module indication assist commissioning and service.
Product Overview
6ES7141-5AH00-0BA0 collects sixteen digital input signals in an ET 200AL field station, using eight five-pole M12 sensor connections.
The 45 mm wide block combines Type 3 inputs, module-level sensor-supply diagnostics and I&M identification records with an operating ambient range extending from −30 to +55°C.
Key Functions
Sixteen-input field acquisition
Eight M12 sensor connections bring sixteen 24 V DC input signals into the ET 200AL station.
Shared protected sensor supply
Eight sensor supply outputs share a 1.4 A total current budget and electronic short-circuit protection.
Identification and service diagnostics
I&M records, configurable diagnostic alarms and module indication assist commissioning and service.
Official Specifications
| Digital input count and characteristic | 16 P-reading inputs; IEC 61131 Type 3 |
|---|---|
| Sensor sockets | 8 five-pole M12 connections |
| Rated load voltage | 24 V DC; permissible range 20.4–28.8 V |
| No-load electronics current | 30 mA rated |
| Supply path current limits | 4 A maximum on 1L+ and 4 A maximum on 2L+ |
| Sensor supply outputs | 8 outputs with a combined 1.4 A maximum |
| Typical power loss | 2.7 W |
| Input voltage levels | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Typical signal-high current | 3.2 mA |
| Input delay on each transition | 1.2–4.8 ms |
| Maximum unshielded input cable | 30 m |
| Maximum two-wire sensor quiescent current | 1.5 mA |
| Sensor-supply fault detection | Short circuit to M at module level |
| Status indications | Green channel LEDs and green/red module diagnostic LED |
| Potential separation | Inputs isolated from backplane; no isolation between channels |
| Type-test isolation voltage | 707 V DC |
| Degree of protection | IP65/67 |
| Operating ambient | −30 to +55°C |
| Power and station connectors | 4-pole M8 supply; shielded 4-pin M8 ET-Connection |
| Dimensions and mass | 45 × 159 × 40 mm (W × H × D); approximately 184 g |
Frequently Asked Questions
Can 6ES7141-5AH00-0BA0 handle sixteen active sensors at the top of its temperature range?
All sixteen inputs may be active at ambient temperatures up to +55°C.
Does 6ES7141-5AH00-0BA0 need a separate PROFINET RJ45 cable at the input block?
The module connects to the ET 200AL station through shielded four-pin M8 ET-Connection rather than an RJ45 network port.
How should I budget power for the sensors attached to 6ES7141-5AH00-0BA0?
Keep the combined current of the eight sensor supply outputs within 1.4 A.
Which older STEP 7 release can configure 6ES7141-5AH00-0BA0?
Use STEP 7 V5.5 SP4 Hotfix 7 or later, or STEP 7 TIA Portal V13 SP1 or later.
What device information is available for maintenance on 6ES7141-5AH00-0BA0?
The module provides identification and maintenance records I&M0 through I&M3.
Can 6ES7141-5AH00-0BA0 be installed on a machine operating at −30°C?
The specified operating ambient range starts at −30°C and extends to +55°C.
What happens to the sensor supply if a short to M is detected on 6ES7141-5AH00-0BA0?
Electronic sensor-supply short-circuit protection operates for the module and can generate a parameterized diagnostic alarm.