Siemens 6ES7141-5AF00-0BA0 SIMATIC ET 200AL DI 8x24VDC M12 Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use five-pole M12 sensor connectors and the specified four-pole M8 supply connection.
- Allocate sensor loads within the shared 0.7 A limit.
- Select a supported STEP 7 or TIA Portal release and the matching station device description.
- Preserve field-connection sealing and keep the input cable length within its limit.
6ES7141-5AF00-0BA0 SIMATIC ET 200AL DI 8x24VDC M12 Module
Eight 24 V DC inputs through four M12 sockets, with a shared 0.7 A sensor supply and IP65/67 field protection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7141-5AF00-0BA0 |
| Product Type | Digital input field block |
| Core Function | Acquisition of distributed sensor states |
| Application | ET 200AL machine I/O stations |
Four M12 sensor sockets
Eight digital inputs are brought into the field block through four five-pole M12 connections.
Module-level supply protection
The sensor supply has electronic short-circuit protection and can generate a configured diagnostic alarm.
ET-Connection station link
Shielded four-pin M8 ET-Connection integrates the block into the distributed station.
Product Overview
6ES7141-5AF00-0BA0 collects eight digital input signals in an ET 200AL station through four five-pole M12 sensor connections.
The 30 mm wide field block uses Type 3 inputs, electronic sensor-supply protection and configurable diagnostics while connecting to the station through M8 ET-Connection cabling.
Key Functions
Four M12 sensor sockets
Eight digital inputs are brought into the field block through four five-pole M12 connections.
Module-level supply protection
The sensor supply has electronic short-circuit protection and can generate a configured diagnostic alarm.
ET-Connection station link
Shielded four-pin M8 ET-Connection integrates the block into the distributed station.
Official Specifications
| Digital input bank | 8 P-reading inputs; IEC 61131 Type 3 |
|---|---|
| Sensor connector arrangement | 4 five-pole M12 sockets |
| Nominal load supply | 24 V DC; operating range 20.4–28.8 V |
| No-load current | 25 mA rated |
| Supply through-current limits | 4 A maximum on 1L+ and 4 A maximum on 2L+ |
| Sensor supply outputs | 4 outputs with 0.7 A combined maximum current |
| Typical power loss | 1.9 W |
| Input switching levels | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Typical high-state input current | 3.2 mA |
| Input delay | 1.2–4.8 ms on rising and falling transitions |
| Maximum unshielded sensor cable | 30 m |
| Two-wire sensor quiescent current | 1.5 mA maximum |
| Fault indication | Green channel LEDs and green/red module diagnostic LED |
| Electrical isolation | Inputs isolated from backplane; no isolation between channels |
| Isolation type test | 707 V DC |
| Enclosure protection | IP65/67 |
| Operating ambient | −30 to +55°C |
| Maximum operating altitude | 5000 m with additional restrictions above 2000 m |
| Supply and ET-Connection | 4-pole M8 supply; shielded 4-pin M8 ET-Connection |
| Dimensions and mass | 30 × 159 × 40 mm (W × H × D); approximately 145 g |
Frequently Asked Questions
How many M12 sockets are used for the eight inputs of 6ES7141-5AF00-0BA0?
The block has four five-pole M12 sensor connections serving eight digital inputs.
What total current is available to sensors powered by 6ES7141-5AF00-0BA0?
The four sensor supply outputs share a maximum combined current of 0.7 A.
Which device description is needed to configure 6ES7141-5AF00-0BA0?
Use GSD revision 5 or later for PROFIBUS integration or GSDML V2.3.1 for the stated PROFINET integration.
Can I configure 6ES7141-5AF00-0BA0 with classic STEP 7?
Classic STEP 7 support starts at V5.5 SP4 Hotfix 7.
Can all inputs on 6ES7141-5AF00-0BA0 remain active at the maximum ambient temperature?
All eight inputs may be active up to +55°C.
Does 6ES7141-5AF00-0BA0 provide galvanic isolation between adjacent input channels?
The channels are not isolated from each other but are isolated from the backplane bus.
How far from 6ES7141-5AF00-0BA0 can an unshielded sensor connection run?
Keep an unshielded sensor cable within 30 m.