SIEMENS · SIMATIC ET 200iSP Power Supply Units
6ES7138-7EC00-0AA0 SIMATIC ET 200iSP PS AC120/230V Power Supply Module
This SIMATIC ET 200iSP power supply converts an AC 120/230 V line input into the electrically isolated, intrinsically safe operating voltages required by the station and is designed for approved hazardous-area installations.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7138-7EC00-0AA0 |
| Product Type | SIMATIC ET 200iSP power supply module |
| Core Function | Generates electrically isolated, intrinsically safe operating voltages for the distributed I/O station |
| Application or Compatible Series | SIMATIC ET 200iSP stations using TM-PS-A UC or TM-PS-B UC terminal submodules |
Exact Identification
Match 6ES7138-7EC00-0AA0 character by character and confirm the complete SIMATIC ET 200iSP PS AC120/230V Power Supply Module designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
This SIMATIC ET 200iSP power supply converts an AC 120/230 V line input into the electrically isolated, intrinsically safe operating voltages required by the station and is designed for approved hazardous-area installations.
The module supplies all output voltages required by an ET 200iSP station, with electrical isolation from the AC line supply and intrinsically safe output circuits. The device is approved for Zone 1 use when installed in an Ex e enclosure and for Zone 2 use in a suitable enclosure providing at least IP54 protection. The module plugs into a TM-PS-A UC or TM-PS-B UC terminal submodule and can be used in supported redundant power-supply arrangements.
Key Functions
Intrinsically Safe Station Supply
The module supplies all output voltages required by an ET 200iSP station, with electrical isolation from the AC line supply and intrinsically safe output circuits.
Hazardous-Area Installation
The device is approved for Zone 1 use when installed in an Ex e enclosure and for Zone 2 use in a suitable enclosure providing at least IP54 protection.
ET 200iSP Terminal Integration
The module plugs into a TM-PS-A UC or TM-PS-B UC terminal submodule and can be used in supported redundant power-supply arrangements.
Official Specifications
| Nominal AC Supply | 120/230 V AC |
|---|---|
| Module Protection Rating | IP30 |
| CE Identification | CE 0344 |
| UKCA Explosion Certificate | DEKRA 21UKEX0033 |
| cULus Listing | E334384 |
| FM Approval | CLASSIFIED 3025852 |
| BIS Approval | Yes |
| Suitability for Safety Functions | Yes |
| INMETRO Certificate | UL-BR 12.0066 |
| IEC 81346-2 Reference Designation | K |
| ATEX Certificate | KEMA 09 ATEX 0156 |
| IECEx Certificate | IECEx KEM 09.0070 |
| CCC Ex Certificate | 2020322303002989 |
| EAC Ex Marking | 1Ex d e [ib] IIC T4 Gb; PB Ex d e [ib Mb] I Mc |
| Gas Hazardous-Area Category | ATEX Zone 1 |
| Dust Hazardous-Area Category | ATEX Zone 21; install in the corresponding enclosure |
| Associated Equipment Protection | Ex ib supported; Ex ia not supported |
| Operating Ambient Temperature | -20 to +70 °C maximum range, subject to supply voltage and output-current derating |
| Enclosure Dimensions | 60 mm width × 190 mm height × 136.5 mm depth |
| Approximate Weight | 2,700 g |
Frequently Asked Questions
Which terminal submodules accept 6ES7138-7EC00-0AA0?
It plugs into a TM-PS-A UC or TM-PS-B UC terminal submodule.
Can 6ES7138-7EC00-0AA0 be installed in a Zone 1 area?
Yes, install it in an enclosure with Ex e protection and follow the applicable explosion-protection wiring rules.
What enclosure protection is required for 6ES7138-7EC00-0AA0 in Zone 2?
Use a suitable enclosure providing at least IP54 protection in accordance with IEC 60079-7.
Can 6ES7138-7EC00-0AA0 be used in a redundant power arrangement?
Yes, supported TM-PS-A and TM-PS-B combinations allow two modules to operate from separate supplies.
How should field wiring be separated around 6ES7138-7EC00-0AA0?
Route intrinsically safe and non-intrinsically safe circuits separately and never place them together in one cable duct.
Does 6ES7138-7EC00-0AA0 require routine maintenance?
No, the module is maintenance-free and any repair must be performed at the manufacturing site.
How does ambient temperature affect the output current of 6ES7138-7EC00-0AA0?
At 120 V AC the documented limits are 3 A at 70 °C, 4 A at 60 °C and 5 A at 50 °C, while at 230 V AC they are 4 A at 70 °C and 5 A at 60 °C.
Compatibility & Ordering Notes
Compatibility Checklist
- Use a compatible TM-PS-A UC or TM-PS-B UC terminal submodule in the ET 200iSP station.
- Maintain the required hazardous-area enclosure, potential equalization and separation between intrinsically safe and non-intrinsically safe wiring.
- Check the station load against the permitted output current for the selected AC supply voltage and maximum ambient temperature.