Siemens 6ES7138-4HA00-0AB0 SIMATIC ET 200S PROFIBUS DP Master Interface
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Choose a supported host CPU and the corresponding engineering configuration.
- Install the module in the designated CPU-side interface position.
- Respect the host CPU device-count and connection-resource limits.
- Use the specified shielded PROFIBUS wiring and a supported transmission rate.
6ES7138-4HA00-0AB0 SIMATIC ET 200S PROFIBUS DP Master Interface
An add-on DP master interface for supported ET 200S CPUs, with a D-sub fieldbus connection and a compact side-by-side mounting format.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7138-4HA00-0AB0 |
| Product Type | CPU fieldbus expansion interface |
| Core Function | Connecting a subordinate device network |
| Application | IM151-7 CPU or IM151-8 PN/DP stations |
Separate master network
The interface adds DP master operation to the supported station CPU.
Broad PROFIBUS rate selection
The supported baud-rate range extends from low-rate DP operation to 12 Mbit/s.
Compact CPU-side expansion
The narrow module occupies the designated position beside the station CPU.
Product Overview
6ES7138-4HA00-0AB0 adds a PROFIBUS DP master connection to a supported ET 200S CPU.
The module supplies the fieldbus interface while the host CPU provides the program and communication resources; in an IM151-7 arrangement it mounts immediately to the CPU right.
Key Functions
Separate master network
The interface adds DP master operation to the supported station CPU.
Broad PROFIBUS rate selection
The supported baud-rate range extends from low-rate DP operation to 12 Mbit/s.
Compact CPU-side expansion
The narrow module occupies the designated position beside the station CPU.
Official Specifications
| Fieldbus connection | 9-pin D-sub socket, RS485 |
|---|---|
| Supported rates | 9.6, 19.2, 45.45, 93.75, 187.5 and 500 kbit/s; 1.5, 3, 6 and 12 Mbit/s |
| Maximum shielded cable length | 100 m |
| Dimensions | 35 × 119.5 × 75 mm |
| Approximate mass | 100 g |
Frequently Asked Questions
Which ET 200S CPU families support 6ES7138-4HA00-0AB0?
The interface is intended for IM151-7 CPU or IM151-8 PN/DP stations.
Where should I place 6ES7138-4HA00-0AB0 in an IM151-7 station?
Install it immediately to the right of the IM151-7 CPU at its X2 interface.
Does 6ES7138-4HA00-0AB0 add another Ethernet connection?
The added connection is a PROFIBUS DP master interface using RS485 and a nine-pin D-sub socket.
How many DP devices can 6ES7138-4HA00-0AB0 serve with the IM151-7 CPU?
That CPU and master-module arrangement supports up to 32 DP devices per station.
Does 6ES7138-4HA00-0AB0 give an IM151-7 CPU a second independent set of twelve connections?
The twelve-connection limit belongs to the IM151-7 CPU as a whole.
Which STEP 7 release is required for 6ES7138-4HA00-0AB0 with an IM151-7 CPU?
The paired configuration requires STEP 7 V5.2 SP1 or later.
How does adding 6ES7138-4HA00-0AB0 affect the maximum IM151-7 CPU supply current?
The specified CPU 1L+ current increases from 250 mA to 280 mA with the master module.