Siemens 6ES7138-4DE02-0AB0 SIMATIC ET 200S 1Count 5 V Counter Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the RS422 encoder interface rather than connecting a conventional 24 V pulse signal to the differential encoder pins.
- Maintain the shorter 30 m encoder-cable limit when the input frequency exceeds 500 kHz.
- Assign the control input to the required gate, synchronization or latch operation.
- Match output load type to the permitted switching frequency and retain the 30 mm station width.
6ES7138-4DE02-0AB0 SIMATIC ET 200S 1Count 5 V Counter Module
A single-channel 32-bit counter for RS422 incremental encoders, with frequency measurement up to 500 kHz, one control input and two digital outputs.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7138-4DE02-0AB0 |
| Product Type | Counter and measuring electronics module |
| Core Function | Evaluating incremental encoder pulses |
| Application | ET 200S counting and measurement stations |
Evaluate incremental position signals
One 32-bit counting channel accepts differential A/notA, B/notB and N/notN encoder signals.
Measure signal dynamics
Frequency, cycle duration and speed can be measured over their respective configured ranges.
Coordinate external events
The digital input supports gate control, synchronization and latch functions, while two outputs provide local switching signals.
Product Overview
6ES7138-4DE02-0AB0 processes a symmetrical incremental-encoder signal in an ET 200S station. The module supports counting and measurement with clock synchronization and evaluates quadrature A/B signals together with the zero mark.
A separate digital control input handles gating, synchronization or latching, and two digital outputs provide local switching. Measurement functions cover frequency, cycle duration and speed, with dedicated direction and synchronization indicators.
Key Functions
Evaluate incremental position signals
One 32-bit counting channel accepts differential A/notA, B/notB and N/notN encoder signals.
Measure signal dynamics
Frequency, cycle duration and speed can be measured over their respective configured ranges.
Coordinate external events
The digital input supports gate control, synchronization and latch functions, while two outputs provide local switching signals.
Official Specifications
| Counting resource | 1 counter channel, 32 bits |
|---|---|
| Module supply range | 24 V DC nominal; 20.4–28.8 V DC |
| Maximum supply currents | 45 mA from L+ without load; 10 mA from the 3.3 V backplane |
| Typical power loss | 2 W |
| Encoder signal format | RS422 differential A/notA, B/notB and N/notN; A/B shifted by 90° |
| Minimum differential input voltage | 1 V |
| Encoder input termination | 330 Ω |
| Maximum encoder input frequency | 650 kHz |
| Shielded encoder cable length | 50 m; limited to 30 m above 500 kHz |
| Frequency measurement range | 0.1 Hz–500 kHz |
| Cycle-duration measurement range | 10 µs–120 s |
| Speed measurement range | 1–25,000 rpm |
| Control input | 1 digital input, IEC 61131 type 2 |
| Control-input thresholds | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Control-input timing | Maximum 2.5 µs rising-edge delay; shielded cable up to 50 m |
| Digital outputs | 2 outputs, rated 2 A each; electronically short-circuit protected |
| Maximum output switching rates | 100 Hz resistive; 2 Hz inductive; 10 Hz lamp load |
| Maximum output-cable lengths | 1,000 m shielded; 600 m unshielded |
| Counter isolation | Isolated from the backplane bus; not isolated from load voltage L+ |
| Dimensions and approximate mass | 30 × 81 × 52 mm; 65 g |
Frequently Asked Questions
Which encoder signal type should I use with 6ES7138-4DE02-0AB0?
Use a symmetrical RS422 incremental encoder with differential A, B and zero-mark signals.
Can I run a 50 m encoder cable above 500 kHz with 6ES7138-4DE02-0AB0?
Above 500 kHz the shielded encoder cable is limited to 30 m.
Does the 650 kHz input limit of 6ES7138-4DE02-0AB0 also define its frequency-measurement range?
The encoder input accepts up to 650 kHz, while frequency measurement is limited to 500 kHz.
Can an external event latch the count on 6ES7138-4DE02-0AB0?
The digital control input can be assigned a latch function.
Which pulse-period range can 6ES7138-4DE02-0AB0 measure?
Cycle-duration measurement covers 10 µs to 120 seconds.
Can 6ES7138-4DE02-0AB0 measure rotational speed?
The speed-measurement function covers 1 to 25,000 rpm.
How can I distinguish count direction locally on 6ES7138-4DE02-0AB0?
Separate green forward-counting and backward-counting indicators show the count direction.