For SIEMENS

Home >  Products >  For SIEMENS

Siemens SIMATIC ET 200iSP 6ES7135-7TD00-0AB0 4 AO HART

Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months

  • Overview
  • Product Overview
  • Key Functions
  • Official Specifications
  • Frequently Asked Questions
  • Compatibility & Ordering Notes
  • Hot Selling Models
  • Recommended Products
Overview

Siemens · SIMATIC ET 200iSP

6ES7135-7TD00-0AB0 4 AO HART Analog Output Module

Siemens 6ES7135-7TD00-0AB0 is a four-channel SIMATIC ET 200iSP analog output electronic module for 4–20 mA process signals with HART protocol communication and channel diagnostics.

At a Glance

Brand Siemens
Model 6ES7135-7TD00-0AB0
Product Type Four-channel HART analog output module
Core Function Outputs four 4–20 mA process signals with HART communication
Application or Compatible Series SIMATIC ET 200iSP distributed I/O systems

Loop Compatibility

Match every two-wire current loop to the supported load, cable length and HART device requirements.

Power and Base Unit

Verify the ET 200iSP station arrangement, 24 V supply and matching terminal assignment before installation.

Hazardous-Area Check

Confirm the project-specific intrinsic-safety parameters and installation approvals for the field circuit.

Product Overview

Siemens 6ES7135-7TD00-0AB0 is a four-channel SIMATIC ET 200iSP analog output electronic module for 4–20 mA process signals with HART protocol communication and channel diagnostics.

Four independent channels provide standard process current signals with HART communication. Diagnostic alarms cover wire break, short circuit and module faults with status indication. The module is designed for distributed process I/O stations, including approved hazardous-area applications.

Ordering focus: verify the ET 200iSP station position, four output-loop assignments, HART device configuration, load limits, terminal wiring and project-specific intrinsic-safety values.
Key Functions

Four HART Current Outputs

Four independent channels provide standard process current signals with HART communication.

Integrated Channel Diagnostics

Diagnostic alarms cover wire break, short circuit and module faults with status indication.

ET 200iSP Integration

The module is designed for distributed process I/O stations, including approved hazardous-area applications.

Official Specifications
Hardware Function Status 17
Firmware Version V3.0.4
Rated Supply Voltage 24 V DC
Permitted Supply Range 20.4 to 28.8 V DC
Current Consumption 295 mA typical
Maximum Load-Bus Current 330 mA
Power Loss 2.7 W typical
Analog Outputs 4
Maximum Cycle Time for All Channels 3.6 ms
Current Ranges 0 to 20 mA and 4 to 20 mA
Output Connection Two-wire connection
Maximum Output Load 750 ohms
Maximum Shielded Cable Length 500 m
Output Resolution 14 bit
Resistive-Load Settling Time 4 ms
Capacitive-Load Settling Time 40 ms
Inductive-Load Settling Time 40 ms
Basic Error Limit 0.1 percent
Operational Error Limit 0.15 percent
Degree of Protection IP30
Frequently Asked Questions

How many HART loops can 6ES7135-7TD00-0AB0 operate?

It provides four independent analog output channels for compatible current loops with HART communication.

Which current ranges are available on 6ES7135-7TD00-0AB0?

The channels support zero to twenty milliamps and four to twenty milliamps.

What loop load is permitted for 6ES7135-7TD00-0AB0?

The connected output loop must not exceed seven hundred fifty ohms.

Can 6ES7135-7TD00-0AB0 detect field-wiring faults?

Yes, channel diagnostics can report wire-break and short-circuit conditions.

What cable length can be used with 6ES7135-7TD00-0AB0?

A shielded output cable may be up to five hundred metres when the installation conditions are satisfied.

What must be checked for hazardous-area use of 6ES7135-7TD00-0AB0?

Verify the field-circuit intrinsic-safety values, station configuration and applicable installation approvals.

What should be recorded before replacing 6ES7135-7TD00-0AB0?

Record channel parameters, HART device assignments, terminal wiring and diagnostic settings before exchange.

Compatibility & Ordering Notes
Before ordering 6ES7135-7TD00-0AB0: verify the ET 200iSP station position, four output-loop assignments, HART device configuration, load limits, terminal wiring and project-specific intrinsic-safety values.

Compatibility Checklist

  • Confirm that the module position and terminal arrangement match the installed SIMATIC ET 200iSP station.
  • Check every connected loop against the supported current range, 750-ohm load limit and shielded-cable length.
  • Validate HART assignments and hazardous-area circuit parameters before commissioning.
Hot Selling Models
9043/001
PS43F
6ES7193-4CC20-0AA0
7000-40341-2341000
TL-W1R5MB1
3SU1102-6AA20-1AA0
ZB4BK1313 089070
EP61 C6 C65110122S3
3VU1300-1NH00
VIP-2/SC/FLK50/PLC
CA4-9C-01
3RU1126-1GB0
Allen-Bradley 140M-C2T-B16
33918.000 QCB-NH1
12MN 08 PS-B3

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.