Siemens 6ES7135-4FB00-0AB0 SIMATIC ET 200S 2AO U Analog Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use an ET 200S terminal arrangement that provides the connections required for the chosen two-wire or four-wire circuit.
- Supply the electronics through the ET 200S power module with the required 24 V DC potential group.
- Keep the analog load at or above 1 kΩ and its capacitance at or below 1 µF.
- Configure channel ranges, substitute values and diagnostic behavior before commissioning the connected equipment.
6ES7135-4FB00-0AB0 SIMATIC ET 200S 2AO U Analog Output Module
15 mm voltage output electronics with two channels, ±10 V and 1–5 V ranges, and two-wire or four-wire connection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7135-4FB00-0AB0 |
| Product Type | Two-channel voltage output module |
| Core Function | Analog voltage command generation |
| Application | ET 200S distributed I/O stations |
Bipolar and live-zero output
Two channels generate ±10 V or 1–5 V signals with range-dependent digital resolution.
Four-wire voltage connection
The output can be wired with separate sensing connections or as a two-wire circuit without line compensation.
Output fault indication
Short-circuit detection, a group fault indication and the SF LED support diagnosis of channel wiring and loads.
Product Overview
6ES7135-4FB00-0AB0 provides two analog voltage outputs in an ET 200S station, delivering control signals for equipment such as valve positioners and speed references.
The narrow electronics module offers a bipolar ±10 V range and a 1–5 V range, with four-wire connection available when voltage drop in the output wiring needs compensation.
Key Functions
Bipolar and live-zero output
Two channels generate ±10 V or 1–5 V signals with range-dependent digital resolution.
Four-wire voltage connection
The output can be wired with separate sensing connections or as a two-wire circuit without line compensation.
Output fault indication
Short-circuit detection, a group fault indication and the SF LED support diagnosis of channel wiring and loads.
Official Specifications
| Module supply | 24 V DC from the power module; reverse-polarity protection |
|---|---|
| Supply current without load | 130 mA maximum from L+ |
| Backplane current | 10 mA from the 3.3 V bus |
| Output address space | 4 bytes |
| Bipolar range and resolution | ±10 V; 13 bits plus sign |
| Unipolar range and resolution | 1–5 V; 12 bits |
| Cycle time for all channels | 1.5 ms maximum |
| Output connection | Two-wire without line compensation or four-wire |
| Minimum resistive load | 1 kΩ |
| Maximum capacitive load | 1 µF |
| Short-circuit current | 25 mA maximum |
| Shielded signal cable | 200 m maximum |
| Settling time | 0.1 ms for resistive load; 0.5 ms for capacitive or inductive load |
| Basic and operational error | ±0.2% at 25°C; ±0.4% over the temperature range |
| Electrical separation | Outputs isolated from backplane and L+; no isolation between channels |
| Insulation test voltage | 500 V DC |
| Dimensions and weight | 15 × 81 × 52 mm (W × H × D); approximately 40 g |
Frequently Asked Questions
When should I use four-wire connection with 6ES7135-4FB00-0AB0?
Use the four-wire connection when the load voltage needs compensation for voltage drop along the output wiring.
Can 6ES7135-4FB00-0AB0 supply both bipolar and 1–5 V control signals?
Each voltage output supports the ±10 V and 1–5 V ranges with the corresponding configured resolution.
How low can the load resistance be on 6ES7135-4FB00-0AB0?
The connected voltage load must have a resistance of at least 1 kΩ.
How much process-image space should I reserve for 6ES7135-4FB00-0AB0?
Reserve four bytes of output address space for the two analog channels.
Does 6ES7135-4FB00-0AB0 isolate its two analog outputs from each other?
The channels share their output potential but are electrically isolated from the backplane bus and L+ supply.
What cable length is possible between 6ES7135-4FB00-0AB0 and an analog load?
Shielded output wiring may extend up to 200 m.
How can I identify a shorted output on 6ES7135-4FB00-0AB0?
Use the module short-circuit diagnostics together with the group fault indication and SF LED to locate the output fault.