Siemens 6ES7134-6HD00-0BA1 ET 200SP AI 4xU/I 2-wire ST Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use BU type A0 or A1 and apply the CC03 terminal identification.
- Connect current sensors as two-wire transmitters within the 650 Ω burden limit.
- Allocate the extra quality-information byte when using QI data.
- Select filtering and interference suppression to match the required process response.
6ES7134-6HD00-0BA1 ET 200SP AI 4xU/I 2-wire ST Module
Four differential analog inputs for voltage or two-wire current measurement, with up to 16-bit resolution and module diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-6HD00-0BA1 |
| Product Type | Standard analog input module |
| Core Function | Acquisition of voltage and two-wire current signals |
| Application | ET 200SP process instrumentation |
Voltage and two-wire current acquisition
Use 0–10 V, 1–5 V, ±10 V, ±5 V, 0–20 mA or 4–20 mA measuring ranges.
Configurable signal processing
Select 16.6, 50 or 60 Hz interference suppression and one of four smoothing levels.
Process diagnostics
Monitor supply voltage, wire break, short circuit and range overflow or underflow through diagnostic alarms.
Product Overview
6ES7134-6HD00-0BA1 integrates four differential analog inputs in an ET 200SP station for voltage signals and two-wire current transmitters.
BU types A0 and A1 provide the matching connection base, and CC03 identifies the module-specific terminal color code; diagnostic functions include wire break at 4–20 mA and configured short-circuit detection.
Key Functions
Voltage and two-wire current acquisition
Use 0–10 V, 1–5 V, ±10 V, ±5 V, 0–20 mA or 4–20 mA measuring ranges.
Configurable signal processing
Select 16.6, 50 or 60 Hz interference suppression and one of four smoothing levels.
Process diagnostics
Monitor supply voltage, wire break, short circuit and range overflow or underflow through diagnostic alarms.
Official Specifications
| Supply Voltage | 24 V DC; permissible range 19.2–28.8 V |
|---|---|
| Maximum Current Consumption | 37 mA without sensor supply |
| Sensor Supply Output | 20 mA maximum per channel; up to 50 mA for less than 10 s |
| Typical Power Loss | 0.85 W without sensor supply |
| Input Address Space | 8 bytes plus 1 byte of quality information |
| Voltage Measuring Ranges | 0–10 V, 1–5 V, ±10 V and ±5 V |
| Current Measuring Ranges | 0–20 mA and 4–20 mA |
| Maximum Resolution | 16 bits including sign |
| Voltage Input Resistance | 120 kΩ |
| Current Input Resistance | 100 Ω plus approximately 0.7 V diode forward drop |
| Maximum Two-Wire Transmitter Burden | 650 Ω |
| Per-Channel Conversion Time | 180, 60 or 50 ms |
| Interference Suppression Frequencies | 16.6, 50 or 60 Hz |
| Digital Smoothing | None, 4, 8 or 16 times |
| Voltage and Current Error Limits | ±0.3% at 25 °C; ±0.5% across the operating temperature range |
| Maximum Shielded Cable | 1,000 m for current; 200 m for voltage |
| Isolation Test Voltage | 707 V DC, type test |
| Dimensions and Approximate Weight | 15 × 73 × 58 mm; 31 g |
Frequently Asked Questions
Which BaseUnits fit 6ES7134-6HD00-0BA1?
The module is suitable for BU types A0 and A1 and uses the CC03 terminal color code.
Can I connect four-wire current transmitters to 6ES7134-6HD00-0BA1?
The current inputs are intended for two-wire transmitters, while four-wire current-transmitter connection is not supported.
How much quality information should I allocate for 6ES7134-6HD00-0BA1?
The module uses up to eight input bytes plus one byte for quality information.
Will 6ES7134-6HD00-0BA1 detect an open 4–20 mA loop?
Wire-break diagnostics are available in the 4–20 mA range.
Can I reparameterize 6ES7134-6HD00-0BA1 while the station is running?
Reparameterization is possible in RUN, while calibration in RUN is not supported.
How long can voltage signal cables run to 6ES7134-6HD00-0BA1?
Shielded cables for voltage measurement can be up to 200 m long.
Which STEP 7 versions can configure 6ES7134-6HD00-0BA1?
Configuration is available from TIA Portal V11 SP2 and STEP 7 V5.5 SP3, with TIA integration from V13.