Siemens 6ES7134-6HD00-0BA1 ET 200SP AI 4xU/I 2-wire ST Module
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Usus BU typi A0 aut A1 et applicatio identificationis terminalis CC03.
- Conecte sensores currentis ut transmittentes duo-filares intra limitem oneris 650 Ω.
- Allocare byte informationis qualitatis additivae ubi data QI utuntur.
- Elige filtrationem et suppressionem interference ad responsionem processus requisitam accommodandam.
6ES7134-6HD00-0BA1 ET 200SP AI 4xU/I 2-wire ST Module
Quattuor ingressus analogici differentiales pro mensura tensionis aut currentis bi-filari, cum resolutione usque ad 16 bit et diagnosticis moduli.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7134-6HD00-0BA1 |
| Typus Producti | Modulus analogicus introductorius normalis |
| Functio principalis | Acquisitio signorum tensionis et currentis bi-filari |
| Applicatio | Instrumentatio processualis ET 200SP |
Acquisitio tensionis et currentis bi-filari
Utere limites mensurae 0–10 V, 1–5 V, ±10 V, ±5 V, 0–20 mA aut 4–20 mA.
Elaboratio signali configurabilis
Elige suppressionem interference 16.6, 50 aut 60 Hz et unum ex quattuor niveis lenitionis.
Diagnostica processus
Monitora tensionem alimentationis, interruptionem fili, cortocircuitum et excessum aut defectum limitis per alarmas diagnosticas.
Product Overview
6ES7134-6HD00-0BA1 integrat quattuor differentiales analogicas intradas in statione ET 200SP pro signis tensionis et transmitteribus currentis bi-filariis.
Typi BU A0 et A1 praebent basim connexionis congruentem, et CC03 identificat codicem coloris terminalis specificum moduli; functiones diagnosticas includunt interruptionem fili ad 4–20 mA et detectionem cortocircuitus configuratam.
Key Functions
Acquisitio tensionis et currentis bi-filari
Utere limites mensurae 0–10 V, 1–5 V, ±10 V, ±5 V, 0–20 mA aut 4–20 mA.
Elaboratio signali configurabilis
Elige suppressionem interference 16.6, 50 aut 60 Hz et unum ex quattuor niveis lenitionis.
Diagnostica processus
Monitora tensionem alimentationis, interruptionem fili, cortocircuitum et excessum aut defectum limitis per alarmas diagnosticas.
Official Specifications
| Supple voltage | 24 V CC; intervallo ammesso 19,2–28,8 V |
|---|---|
| Maxima Consumptio Electrica | 37 mA sine suppeditatione sensoris |
| Sensoris alimentatio productio | 20 mA maximum per canallem; usque ad 50 mA per minus quam 10 secunda |
| Perditio potentiæ typica | 0.85 W sine suppeditatione sensoris |
| Spatium Adressarum Input | 8 octeta plus 1 octetum informationis de qualitate |
| Intervala Mensurae Tensionis | 0–10 V, 1–5 V, ±10 V et ±5 V |
| Intervala Mensurae Currentis | 0–20 mA et 4–20 mA |
| Maxima Resolutio | 16 bita, signum inclusum |
| Résistance d'entrée en tension | 120 kΩ |
| Résistance d'entrée en courant | 100 Ω plus approximative 0.7 V cadere directum diodi |
| Onus Maximum Transmittentis Duo-filaris | 650 Ω |
| Tempus conversionis per canalem | 180, 60 aut 50 ms |
| Frequencias pro suppressione interference | 16.6, 50 aut 60 Hz |
| Lissage numérique | Nullus, 4, 8 aut 16 vicibus |
| Limites erroris tensionis et currentis | ±0.3% ad 25 °C; ±0.5% in toto intervallo temperaturarum operationis |
| Maximus Cabelus Scutatus | 1 000 m pro currente; 200 m pro tensione |
| Tensio Probae Isolationis | 707 V DC, type test |
| Dimensiones et pondus approximatum | 15 × 73 × 58 mm; 31 g |
Quaestiones Frequenter Rogatae
Quae BaseUnits conveniunt ad 6ES7134-6HD00-0BA1?
Hoc modulum aptum est ad typum BU A0 et A1 et codicem coloris terminalis CC03 utitur.
Possumne coniungere transmittentes currentis quattuor-filares ad 6ES7134-6HD00-0BA1?
Ingressus currentis destinati sunt ad transmittentes bi-filares; coniunctio transmittentis currentis quattuor-filarem non suffragatur.
Quam multum informationis de qualitate debeo assignare ad 6ES7134-6HD00-0BA1?
Modulus usque ad octo octetos ingressus consumit, plus unum octetum pro informatione de qualitate.
Num 6ES7134-6HD00-0BA1 detegit circuitum apertum 4–20 mA?
Diagnostica interruptae connexionis disponibilia sunt in intervallo 4–20 mA.
Num possum reparametrizare 6ES7134-6HD00-0BA1 dum statio operatur?
Reparametrizatio possibilis est in statu RUN; tamen calibratio in statu RUN non suffragatur.
Quam longae esse possunt catenae signali voltatici ad 6ES7134-6HD00-0BA1?
Catenae scutatae pro mensura voltationis usque ad 200 m longae esse possunt.
Quae versiones STEP 7 configurare possunt 6ES7134-6HD00-0BA1?
Configuratio disponibilis est ab TIA Portal V11 SP2 et STEP 7 V5.5 SP3, cum integratione TIA ab V13.