- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the High Feature module entry and a station configuration supporting the required timing functions.
- Coordinate interference suppression and smoothing with the process response.
- Provide any external transmitter supply separately.
- Configure the voltage ranges, diagnostics and hardware interrupts for the connected signals.
6ES7134-4LB02-0AB0 SIMATIC ET 200S 2AI U High Feature Module
Two voltage inputs with 16-bit maximum resolution, a 0.5 ms unfiltered module cycle and selectable 50/60 Hz suppression.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-4LB02-0AB0 |
| Product Type | High Feature analog input module |
| Core Function | Fast acquisition of voltage signals |
| Application | ET 200S high-performance analog stations |
Fast two-channel acquisition
A 0.5 ms module cycle serves both channels when line-frequency suppression is disabled.
Configurable noise rejection
50 Hz, 60 Hz or no interference suppression can be selected for the measurement task.
High Feature event handling
Isochronous operation, hardware interrupts and range diagnostics support demanding station applications.
Product Overview
6ES7134-4LB02-0AB0 acquires two voltage signals with fast conversion and High Feature station functions.
The module supports isochronous operation, hardware interrupts and configurable interference suppression, with the accuracy and cycle time determined by the selected filter configuration.
Key Functions
Fast two-channel acquisition
A 0.5 ms module cycle serves both channels when line-frequency suppression is disabled.
Configurable noise rejection
50 Hz, 60 Hz or no interference suppression can be selected for the measurement task.
High Feature event handling
Isochronous operation, hardware interrupts and range diagnostics support demanding station applications.
Official Specifications
| Analog input bank | 2 voltage channels |
|---|---|
| Voltage ranges | ±10 V; ±5 V; 1–5 V |
| Bipolar-range resolution | 15 bits plus sign |
| Input resistance | 800 kΩ for the specified voltage ranges |
| Unfiltered module cycle | 0.5 ms for both channels |
| Cycle with interference suppression | 18 or 21 ms per channel |
| Interference suppression choices | 50 Hz, 60 Hz or disabled |
| Smoothing factors | 1, 4, 16 or 32 times the cycle time |
| Operational error | ±0.1% with suppression; ±0.2% without suppression |
| Basic error at 25°C | ±0.05% with suppression; ±0.1% without suppression |
| Nominal supply | 24 V DC; reverse-polarity protection |
| Maximum supply current | 55 mA from L+ without load; 10 mA from the 3.3 V backplane |
| Typical power loss | 0.85 W |
| Input address space | 4 bytes |
| Transmitter supply | No integrated transmitter supply |
| Maximum shielded signal cable | 200 m |
| Input overvoltage limits | 35 V continuous; 75 V for up to 1 ms |
| Diagnostics and events | Hardware interrupt; group fault; overflow/underflow; wire break in the 1–5 V range |
| Isolation | From backplane and L+; no channel-to-channel isolation; 500 V DC test |
| Dimensions and weight | 15 × 81 × 52 mm (W × H × D); approximately 45 g |
Frequently Asked Questions
Can 6ES7134-4LB02-0AB0 sample both channels in a 0.5 ms module cycle?
The 0.5 ms module cycle applies to both channels when interference suppression is disabled.
What accuracy tradeoff should I allow for when disabling the filter on 6ES7134-4LB02-0AB0?
The operational error limit changes from ±0.1% with suppression to ±0.2% without suppression.
Does 6ES7134-4LB02-0AB0 provide a supply for my voltage transmitter?
The module has no integrated transmitter power supply.
Can I configure hardware interrupts on 6ES7134-4LB02-0AB0?
The High Feature module supports hardware interrupts.
Which smoothing factors are available on 6ES7134-4LB02-0AB0?
The selectable smoothing factors are one, four, sixteen or thirty-two times the cycle time.
How heavily does 6ES7134-4LB02-0AB0 load a voltage signal?
The input resistance is 800 kΩ for the specified voltage ranges.
Will enabling interference suppression preserve the unfiltered cycle time of 6ES7134-4LB02-0AB0?
With suppression enabled, the stated cycle becomes eighteen or twenty-one milliseconds per channel.