Siemens 6ES7134-4JB51-0AB0 ET 200S RTD Analog Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Configure Pt100 or Ni100 standard or climatic characteristics to match the installed sensors.
- Allocate two channels for three- or four-wire sensor circuits.
- Allow for additional conversion time when wire-break diagnostics are active.
- Keep shielded sensor runs within 200 m and use the selected power-module supply.
6ES7134-4JB51-0AB0 ET 200S RTD Analog Input Module
Compact RTD input module supporting four two-wire channels or two three-/four-wire channels for Pt100, Ni100 and resistance measurement.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-4JB51-0AB0 |
| Product Type | 2/4 AI RTD Standard electronics module |
| Core Function | Temperature and resistance measurement |
| Application | Pt100 and Ni100 sensor acquisition in ET 200S |
Flexible RTD wiring
Connect four sensors in two-wire form or two sensors using three- or four-wire measurement.
Resistance ranges
Measure resistance over the 0–150 Ω, 0–300 Ω or 0–600 Ω ranges.
Measurement diagnostics
Wire-break and range diagnostics, together with the SF LED, help identify sensor-circuit faults.
Product Overview
6ES7134-4JB51-0AB0 brings resistance-temperature and resistance signals into an ET 200S station in a 15 mm-wide electronics module.
Pt100 and Ni100 standard and climatic characteristics are selectable, and configurable digital filtering helps adapt the readings to the process response.
Key Functions
Flexible RTD wiring
Connect four sensors in two-wire form or two sensors using three- or four-wire measurement.
Resistance ranges
Measure resistance over the 0–150 Ω, 0–300 Ω or 0–600 Ω ranges.
Measurement diagnostics
Wire-break and range diagnostics, together with the SF LED, help identify sensor-circuit faults.
Official Specifications
| Load Supply | 24 V DC from the power module |
|---|---|
| Maximum Supply Consumption | 30 mA from L+; 10 mA from the 3.3 V backplane |
| Typical Power Loss | 0.6 W |
| Input Address Space | 8 bytes maximum |
| Input Wiring Capacity | 4 channels in 2-wire form; 2 channels in 3- or 4-wire form |
| Resistance Ranges | 0–150 Ω, 0–300 Ω and 0–600 Ω |
| Measurement Current | 1.67 mA typical |
| Input Resistance | 2,000 kΩ |
| Resolution Including Sign | 16 bits for Pt100/Ni100; 14 bits at 150 Ω; 15 bits at 300/600 Ω |
| Integration Time | 16.7 or 20 ms |
| Per-Channel Conversion Time | 66 or 80 ms, with additional time for wire-break testing |
| Interference Rejection Frequencies | 50 or 60 Hz |
| Digital Smoothing | None, low, medium and high; 1, 4, 32 and 64 cycle-time factors |
| RTD Error Limits | ±0.4% at 25 °C; ±0.6% across the operating temperature range |
| Maximum Shielded Sensor Cable | 200 m |
| Isolation Test Voltage | 500 V DC |
| Dimensions and Approximate Weight | 15 × 81 × 52 mm; 40 g |
Frequently Asked Questions
Can 6ES7134-4JB51-0AB0 measure four three-wire Pt100 sensors?
Three- or four-wire wiring provides two input channels, while four channels are available with two-wire connections.
Can I select a climatic Pt100 characteristic on 6ES7134-4JB51-0AB0?
Pt100 and Ni100 characteristics are selectable in both standard and climatic ranges.
Which resistance ranges can I configure on 6ES7134-4JB51-0AB0?
The available resistance ranges are 0–150 Ω, 0–300 Ω and 0–600 Ω.
How can I smooth a fluctuating reading on 6ES7134-4JB51-0AB0?
The digital filter offers none, low, medium and high smoothing with factors of 1, 4, 32 and 64 times the cycle time.
Can 6ES7134-4JB51-0AB0 identify a broken sensor lead?
Wire-break diagnostics are available along with group-error and overflow or underflow diagnostics.
How far can shielded RTD cables run to 6ES7134-4JB51-0AB0?
Shielded sensor cables can be up to 200 m long.
Are the sensor channels of 6ES7134-4JB51-0AB0 isolated from each other?
The channels share a potential group, while isolation is provided from the backplane bus and the L+ load supply.