- Use the electronic module in an approved SIMATIC ET 200S station.
- Match the terminal module and field wiring to the selected voltage ranges.
- Restore the original channel parameters and validate both analog values before operation.
SIEMENS · SIMATIC ET 200S
6ES7134-4FB52-0AB0 2 AI High-Speed Voltage Electronic Module
The 6ES7134-4FB52-0AB0 electronic module provides two high-speed voltage inputs for SIMATIC ET 200S and supports four parameterizable bipolar and unipolar measuring ranges.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-4FB52-0AB0 |
| Product Type | Two-channel high-speed analog voltage input module |
| Core Function | Digitizes two voltage signals with a 0.1 ms module cycle for fast distributed measurement |
| Application or Compatible Series | SIMATIC ET 200S stations using 15 mm electronic modules |
Exact Identification
Match 6ES7134-4FB52-0AB0 character by character before replacement.
Interface Check
Confirm the installed supply, terminals, network and field wiring.
Project Backup
Preserve the validated configuration and application data before exchange.
Product Overview
The 6ES7134-4FB52-0AB0 electronic module provides two high-speed voltage inputs for SIMATIC ET 200S and supports four parameterizable bipolar and unipolar measuring ranges.
The 0.1 ms module cycle supports rapidly changing voltage measurements in compact distributed I/O stations. Each installation can be engineered for 1 to 5 V, ±2.5 V, ±5 V or ±10 V signals. The 15 mm electronic module reports group faults through its SF indicator and occupies four input bytes.
Key Functions
Fast Analog Acquisition
The 0.1 ms module cycle supports rapidly changing voltage measurements in compact distributed I/O stations.
Selectable Voltage Ranges
Each installation can be engineered for 1 to 5 V, ±2.5 V, ±5 V or ±10 V signals.
Compact ET 200S Integration
The 15 mm electronic module reports group faults through its SF indicator and occupies four input bytes.
Official Specifications
| Analog Input Channels | 2 |
|---|---|
| Supported Voltage Ranges | 1 to 5 V, ±2.5 V, ±5 V and ±10 V |
| Module Cycle Time | 0.1 ms |
| Conversion Time per Channel | 15 µs |
| Maximum Address Space | 4 input bytes |
| Resolution at 1 to 5 V | 15 bits including sign |
| Resolution at ±2.5 V | 15 bits including sign |
| Resolution at ±5 V | 16 bits including sign |
| Resolution at ±10 V | 16 bits including sign |
| Input Resistance | 120 kΩ |
| Permanent Destruction Limit | 35 V |
| Maximum Shielded Cable Length | 200 m |
| Current from L+ | 130 mA maximum |
| Current from 3.3 V Backplane Bus | 10 mA maximum |
| Typical Power Loss | 2 W |
| Module Width | 15 mm |
Frequently Asked Questions
Which signal ranges can be configured for 6ES7134-4FB52-0AB0?
Choose among 1 to 5 V, ±2.5 V, ±5 V and ±10 V according to the transmitter output.
How quickly does 6ES7134-4FB52-0AB0 update both channels?
The module cycle is 0.1 ms, with a 15 µs conversion time for each channel.
What cable practice is appropriate for 6ES7134-4FB52-0AB0?
Use shielded analog wiring and keep the run within the documented 200 m maximum.
How much input address space does 6ES7134-4FB52-0AB0 require?
Reserve four input bytes in the ET 200S station configuration.
What should be checked before installing 6ES7134-4FB52-0AB0?
Verify the 15 mm terminal arrangement, measuring range, channel wiring and station parameter set.
How is a group fault indicated on 6ES7134-4FB52-0AB0?
The red SF indicator reports the module group-fault condition.
What must be retained when replacing 6ES7134-4FB52-0AB0?
Keep the channel ranges, filtering, scaling and terminal assignments identical to the validated project.