Siemens 6ES7132-6BF00-0BA0 SIMATIC ET 200SP DQ 8x24VDC/0.5A ST Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a type A0 BaseUnit and the CC02 identification arrangement.
- For functional status up to 002, keep the station within 32 I/O modules.
- For firmware V1.1.0, use TIA Portal V13 Update 3 or the specified STEP 7 V5.5 SP3 HSP0230 V4.0 support.
- Keep channel loading within 0.5 A and module loading within 4 A.
- Do not parallel outputs to increase current capacity.
- Account for the off-state residual current when selecting LED loads and wire-break diagnostics.
6ES7132-6BF00-0BA0 SIMATIC ET 200SP DQ 8x24VDC/0.5A ST Module
An eight-channel sourcing output module with 0.5 A per output, a 4 A module limit, configurable diagnostics and output quality information.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-6BF00-0BA0 |
| Product Type | Standard digital output electronics module |
| Core Function | Driving binary field loads from the distributed I/O station |
| Application | ET 200SP stations with a compatible interface and A0 BaseUnit |
Eight sourcing outputs
The 24 V DC output bank supplies up to 0.5 A per channel and 4 A in total.
Channel diagnostics
Configurable diagnostics cover wire break and short circuits, with local status and DIAG indication.
A0 BaseUnit interface
The 15 mm-wide electronics module uses an A0 BaseUnit and CC02 identification.
Product Overview
6ES7132-6BF00-0BA0 adds eight sourcing digital outputs to an ET 200SP station, combining field-load switching with configurable diagnostic functions.
The output area occupies one byte, with a further byte when quality information is used; wire-break diagnostics can produce a small residual current in the off state.
Key Functions
Drive discrete DC loads
Eight sourcing outputs operate from a nominal 24 V DC supply, with a 0.5 A channel rating and a 4 A module total.
Track output and supply faults
The module supports diagnostics for supply voltage, wire break and short circuits, with channel-status LEDs and a green/red DIAG LED.
Set the output response in the project
Output substitute values and quality information support the configured controller response, while parameter record 128 permits parameter changes during RUN.
Official Specifications
| Output Bank | 8 sourcing digital outputs |
|---|---|
| Supply Voltage | 24 V DC nominal; permissible range 19.2–28.8 V DC |
| Maximum No-Load Current Consumption | 35 mA |
| Typical Power Dissipation | 1 W |
| Output Address Space | 1 byte, plus 1 byte for quality information |
| Rated Channel Current | 0.5 A |
| Maximum Module Current | 4 A |
| Typical Short-Circuit Response Threshold | 0.7–1.3 A |
| Maximum Signal-0 Residual Current | 0.1 mA |
| Load-Resistance Range | 48 Ω–12 kΩ |
| Maximum Resistive-Load Output Delay | 50 µs OFF-to-ON; 100 µs ON-to-OFF at rated load |
| Maximum Switching Frequency | 100 Hz resistive; 2 Hz inductive; 10 Hz lamp load |
| Maximum Lamp Load | 5 W per output |
| Maximum Field-Cable Length | 1000 m shielded; 600 m unshielded |
| Isolation Test Voltage | 707 V DC, type test |
| Permitted Potential Difference | 75 V DC or 60 V AC between different circuits, basic insulation |
| Operating Ambient Temperature | 0–60 °C horizontal; 0–50 °C vertical |
| Module Width | 15 mm |
| Approximate Weight | 28 g |
Frequently Asked Questions
Why might an LED load flicker with an output on 6ES7132-6BF00-0BA0 switched off?
Wire-break diagnostics produce a small off-state residual current whose level depends on the diagnostic setting.
Can I parallel two outputs on 6ES7132-6BF00-0BA0 to increase load capacity?
Parallel connection for increased output performance is not permitted.
Which BaseUnit type should I select for 6ES7132-6BF00-0BA0?
The electronics module uses a type A0 BaseUnit with CC02 identification.
How much output address space should I reserve for 6ES7132-6BF00-0BA0 when using quality information?
Reserve one output byte and one additional byte for quality information.
Can I change parameters on 6ES7132-6BF00-0BA0 while the CPU is in RUN?
WRREC can transfer parameter data record 128 during RUN, while a restart restores the parameters held in the STEP 7 project.
What station-size restriction applies to early hardware versions of 6ES7132-6BF00-0BA0?
Modules up to functional status 002 do not support station configurations with more than 32 I/O modules.
Can all eight outputs on 6ES7132-6BF00-0BA0 carry their rated current together?
The module permits a total of 4 A up to 60 °C horizontally or 50 °C vertically.