Overview
- Use one of the permitted TM-E15 terminal modules for the relay electronics.
- Keep both relay channels within the same extra-low-voltage system when either channel is SELV or PELV.
- Do not parallel channels for increased output current.
- Provide external 6 A output fuses.
- Apply the 4 A channel limit at 60 °C and the 8 mA minimum load.
6ES7132-4HB12-0AA0 SIMATIC ET 200S Two-Channel Relay Output Module
A two-channel changeover-relay module with 15 mm width, selectable substitute-output behavior and separate channel status indicators.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-4HB12-0AA0 |
| Product Type | Relay output electronics module |
| Core Function | Switching isolated changeover-contact load circuits |
| Application | ET 200S distributed I/O stations |
Two changeover channels
Each output provides common, normally open and normally closed terminals.
Temperature-dependent current
Per-channel current is limited to 5 A up to 50 °C and 4 A up to 60 °C.
External output protection
Relay circuits require external 6 A fuses.
Product Overview
6ES7132-4HB12-0AA0 provides two relay-output channels for an ET 200S station, using isolated changeover contacts to switch suitable AC or DC loads.
Channel status LEDs show the output states, and the configured reaction to CPU or master STOP can substitute a selected output value or retain the last output value.
Key Functions
Switch normally open or normally closed paths
Each relay channel provides a common terminal and separate normally open and normally closed contacts.
Define the STOP reaction
The module can substitute a configured value or keep the last value on CPU or master STOP, with a channel-specific substitute value.
Show output status
A green LED for each channel indicates whether that output is activated.
Official Specifications
| Relay Output Channels | 2 |
|---|---|
| Module Width and Approximate Weight | 15 mm; 50 g |
| Rated Electronics Supply | 24 V DC from the power module |
| Maximum Channel Current | 5 A up to 50 °C; 4 A up to 60 °C |
| Minimum Load Current | 8 mA |
| Maximum Load Cable Length | 600 m unshielded; 1000 m shielded |
| Parameter Length | 3 bytes |
| Address Space | 1 byte; 2 bits in packed addressing |
| Maximum Current Consumption | 30 mA from L+; 10 mA from the backplane bus |
| Typical Power Dissipation | 0.6 W |
| Maximum Switching Frequency | 2 Hz resistive or lamp loads; 0.5 Hz inductive loads |
| External Output Fuse | 6 A |
| Channel Indication | One green output-status LED per channel |
| Isolation Test Voltages | 500 V DC supply-to-backplane; 2500 V DC channels-to-backplane and channels-to-supply |
| CPU/Master STOP Behavior | Substitute value or keep last value; default substitute value 0 |
Frequently Asked Questions
Can I choose either normally open or normally closed wiring with 6ES7132-4HB12-0AA0?
Each channel provides both contact paths from its common terminal.
Can 6ES7132-4HB12-0AA0 carry 5 A per channel at 60 °C?
The channel limit at 60 °C is 4 A.
Which fuse protection is needed for the outputs of 6ES7132-4HB12-0AA0?
The relay outputs must be protected externally with 6 A fuses.
Can one channel of 6ES7132-4HB12-0AA0 use SELV while the other switches mains voltage?
If one channel uses an extra-low-voltage SELV or PELV system, the other channel must also use an extra-low-voltage system.
Can I parallel both channels of 6ES7132-4HB12-0AA0 to obtain more current?
Paralleling outputs to increase capacity is not permitted.
What happens to 6ES7132-4HB12-0AA0 on CPU or master STOP?
The configured reaction substitutes a value or retains the last output value.
Will 6ES7132-4HB12-0AA0 retain a substitute output when its interface module loses power?
No, loss of interface-module or COMPACT-module power sets the output value to zero.