- Keep the combined output current at or below 4 A.
- Use compatible terminal modules such as TM-E15S24-A1, TM-E15S24-01, TM-E15S23-01 or TM-E15S26-A1.
- Account for the brief output pulse possible when the power-module supply is applied through a mechanical contact.
- If evaluating the listed successor 6ES7132-4BD32-0AA0, check the installed configuration and terminal arrangement separately.
6ES7132-4BD30-0AA0 SIMATIC ET 200S Four-Channel 2A Digital Output Module
A four-channel output module for 24 V DC loads, including solenoid valves, DC contactors and indicator lamps.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-4BD30-0AA0 |
| Product Type | Standard digital output module |
| Core Function | Switch discrete DC actuators |
| Application | ET 200S remote I/O stations |
Four actuator channels
Each channel has a 2 A rated current with a 4 A total limit for the module.
Channel indication
A green LED shows the state of each output.
Permanent field wiring
The electronic module plugs into its matching ET 200S terminal module.
Product Overview
6ES7132-4BD30-0AA0 switches four 24 V DC output channels in an ET 200S station, with a rated current of 2 A per channel.
The Standard electronic module includes per-channel short-circuit protection and green status indication. The four outputs share a 4 A total module current limit and have no channel-to-channel isolation.
Key Functions
Operate common DC actuators
The output stage is suitable for solenoid valves, DC contactors and indicator lamps, with a lamp-load limit of 10 W.
Respond to an output fault
Each channel has short-circuit protection with a typical response threshold from 2.8 to 7.2 A.
Respect load-dependent switching
The maximum switching rate is 100 Hz for resistive loads, 2 Hz for 0.5 H inductive loads and 10 Hz for lamps.
Official Specifications
| Digital Outputs | 4 |
|---|---|
| Rated Load Voltage | 24 V DC from the power module |
| Rated Output Current | 2 A per channel |
| Permitted On-State Current | 7 mA to 2.4 A per channel |
| Total Output Current | 4 A per module |
| Minimum On-State Voltage | L+ − 1 V |
| Maximum Off-State Leakage | 0.5 mA |
| Resistive-Load Output Delay | Turn-on: 200 µs maximum; turn-off: 1.3 ms maximum |
| Maximum Switching Rate | Resistive: 100 Hz; inductive at 0.5 H: 2 Hz; lamp: 10 Hz |
| Maximum Lamp Load | 10 W |
| Load Resistance Range | 12 Ω to 3.4 kΩ |
| Short-Circuit Protection | Per channel; typical threshold 2.8 to 7.2 A |
| Inductive Turn-Off Voltage Limit | Typically L+ − 55 V to L+ − 60 V |
| Output Isolation | No isolation between channels; isolated from the backplane bus |
| Insulation Test Voltage | 500 V DC |
| Maximum Cable Length | 600 m unshielded; 1,000 m shielded |
| No-Load L+ Current | 5 mA maximum per channel |
| Typical Power Dissipation | 1.6 W |
| Channel Status Indication | One green LED per channel |
| Dimensions and Weight | 15 × 81 × 52 mm (W × H × D); approximately 40 g |
Frequently Asked Questions
Can I run four 2 A loads simultaneously from 6ES7132-4BD30-0AA0?
No, the total output current is limited to 4 A per module even though each channel has a 2 A rated current.
May I parallel two outputs of 6ES7132-4BD30-0AA0 to increase load current?
No, parallel connection is permitted for redundant load triggering within one module but not to increase output capacity.
Why can a fast counter detect a pulse when power is applied to 6ES7132-4BD30-0AA0?
Applying the power-module supply through a mechanical contact can produce an approximately 50 µs signal-1 pulse at the digital outputs.
Can 6ES7132-4BD30-0AA0 switch an inductive load as quickly as a resistive load?
No, the switching limit is 2 Hz for a 0.5 H inductive load and 100 Hz for a resistive load.
How can I see which output of 6ES7132-4BD30-0AA0 is active?
Each output has its own green status LED.
Are the output channels on 6ES7132-4BD30-0AA0 electrically isolated from one another?
No, the channels are not mutually isolated, although they are isolated from the backplane bus.
Can I use 6ES7132-4BD30-0AA0 for a 20 W indicator lamp?
No, the permitted lamp load is 10 W.