Siemens 6ES7131-6BF01-0BA0 ET 200SP DI 8x24VDC ST Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use an A0 BaseUnit and the CC01 module color assignment.
- For three-wire wiring, provide AUX terminals or a potential distributor module.
- For four-wire wiring, add the specified potential distributor module.
- Use TIA Portal V14 or later; the 2019 module manual specifies HSP 0222 for that version.
6ES7131-6BF01-0BA0 ET 200SP DI 8x24VDC ST Input Module
Eight type-3 inputs with individually selectable filtering, a protected sensor supply and module-level wire-break and supply diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7131-6BF01-0BA0 |
| Product Type | Standard digital input module |
| Core Function | Acquisition of PNP field signals |
| Application | ET 200SP distributed input stations |
Adjustable input filtering
Select input delays from 0.05 to 20 ms for the individual channels.
Sensor supply budget
The eight sensor-supply outputs share a maximum module current of 700 mA.
Value status
The input address occupies one byte, with one additional byte for quality information.
Product Overview
6ES7131-6BF01-0BA0 acquires eight field signals through P-reading inputs with an IEC 61131 type-3 characteristic. Channel filtering can be selected individually, while module diagnostics monitor the supply, sensor-supply short circuits and wire breaks.
The 15 mm-wide module uses an A0 BaseUnit and the CC01 color assignment. A common sensor-supply current limit applies across the module, so the individual terminal ratings must not be added together when budgeting connected sensors.
Key Functions
Filter field-contact transitions
Each channel permits a filter setting between 0.05 and 20 ms, with an additional line-dependent delay of 30–500 µs.
Monitor the input installation
Module diagnostics cover wire break, short circuits and supply-voltage monitoring, supported by PWR, channel-state and DIAG indicators.
Integrate input quality
The module provides one byte of input data and an additional byte for quality information.
Official Specifications
| Digital inputs | 8 P-reading inputs; IEC 61131 type 3 |
|---|---|
| DC supply | 24 V rated; permissible range 19.2–28.8 V |
| Input logic thresholds | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Typical signal-1 input current | 2.5 mA |
| Selectable input delays | 0.05, 0.1, 0.4, 0.8, 1.6, 3.2, 12.8 or 20 ms, plus 30–500 µs line-dependent delay |
| Maximum module current consumption | 50 mA when all channels use the sensor supply |
| Sensor-supply outputs | 8 outputs; minimum output voltage 19.2 V |
| Sensor-supply current limit | 700 mA maximum per module and per channel |
| Sensor-supply protection | Short-circuit protection at module level |
| Maximum two-wire sensor quiescent current | 1.5 mA |
| Maximum field-cable length | 1,000 m shielded; 600 m unshielded |
| Input address allocation | 1 input byte plus 1 byte for quality information |
| Local indicators | Green PWR and channel LEDs; green/red DIAG LED |
| Electrical isolation | No channel-to-channel isolation; isolation between channels and backplane |
| Insulation test voltage | 707 V DC, type test |
| Typical power loss | 1 W at 24 V with all eight inputs supplied via the sensor supply |
| Operating temperature | Horizontal: −30 to +60 °C; vertical: −30 to +50 °C; operation below 0 °C from FS02 |
| Dimensions and approximate weight | 15 × 73 × 58 mm (W × H × D); 28 g |
Frequently Asked Questions
Which BaseUnit should I pair with 6ES7131-6BF01-0BA0?
Use an A0 BaseUnit with the CC01 color assignment and select the terminal arrangement for the sensor wiring.
Can I feed 700 mA from every sensor terminal on 6ES7131-6BF01-0BA0 simultaneously?
The maximum current is 700 mA for the entire module as well as for an individual channel.
How much input address space should I reserve for 6ES7131-6BF01-0BA0 with quality information?
Reserve one byte for the input values and one additional byte for quality information.
Can I adjust the filtering independently for noisy contacts on 6ES7131-6BF01-0BA0?
The input delay is selectable for each channel from 0.05 to 20 ms.
Will 6ES7131-6BF01-0BA0 distinguish a broken sensor wire from a normal channel indication?
Wire-break diagnostics operate at module level, while the green channel LEDs indicate the individual input states.
What leakage-current limit applies to a two-wire sensor connected to 6ES7131-6BF01-0BA0?
The maximum permissible quiescent current is 1.5 mA.
Can 6ES7131-6BF01-0BA0 operate below freezing in a horizontal rack?
Hardware from FS02 supports horizontal operation down to −30 °C.