Siemens 6ES7131-4BD50-0AA0 SIMATIC ET 200S Four-Channel Source Input Module

Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months

  • Overview
  • Hot Selling Models
  • Recommended Products
Overview
SIEMENS SIMATIC ET 200S

6ES7131-4BD50-0AA0 SIMATIC ET 200S Four-Channel Source Input Module

A four-channel source-input module for 24 V DC switches and proximity sensors in an ET 200S station.

At a Glance

Brand Siemens
Model 6ES7131-4BD50-0AA0
Product Type Standard digital input module
Core Function Acquire discrete field-sensor signals
Application ET 200S remote I/O stations

Source-input design

Input voltage thresholds are referenced to L+ for this SRC variant.

Sensor connections

Compatible terminal modules support two- and three-conductor layouts.

Input filtering

Both signal transitions have a typical 3 ms input delay.

Product Overview

6ES7131-4BD50-0AA0 acquires four discrete signals through the ET 200S 4DI 24 V DC/SRC Standard input stage.

The source-input circuit is intended for switches and proximity switches. Its sensor-supply output is rated at 500 mA, while the input channels share a common potential and are isolated from the backplane bus.

Ordering focus: Select the SRC input circuit to match the sensor switching arrangement and L+-referenced thresholds.
Key Functions

Read source-input signals

The SRC circuit evaluates signal 1 from −15 to −30 V and signal 0 from +30 to −5 V relative to L+.

Filter discrete transitions

Both rising and falling transitions have a typical 3 ms delay, with a 2.0 to 4.5 ms range.

Connect proximity sensors

Two-wire BEROs can be connected when their bias current does not exceed 1.5 mA.

Official Specifications
Digital Inputs 4
Rated Supply and Input Voltage 24 V DC
Signal-1 Voltage Relative to L+ −15 to −30 V
Signal-0 Voltage Relative to L+ +30 to −5 V
Signal-1 Input Current 7 mA typical at 24 V
Input Delay in Either Direction 3 ms typical; 2.0 to 4.5 ms
Input Characteristic IEC 61131, Type 1
Two-Wire Sensor Bias Current 1.5 mA maximum
Sensor-Supply Output Current 500 mA rated; 0 to 500 mA permitted
Loaded Sensor-Supply Voltage M + 0.5 V maximum
Maximum Field Cable Length 600 m unshielded; 1,000 m shielded
Channel Isolation Not isolated from each other; isolated from the backplane bus
Permissible Circuit Potential Difference 75 V DC or 60 V AC
Insulation Test Voltage 500 V DC
Supply Reverse-Polarity Protection Provided
Typical Power Dissipation 0.7 W
Input Status Indication One green LED per channel
Diagnostic Functions Not provided
Dimensions (W × H × D) 15 × 81 × 52 mm
Approximate Weight 35 g
Frequently Asked Questions

What should I check before replacing another 4DI module with 6ES7131-4BD50-0AA0?

Match the source-input SRC circuit and its L+-referenced voltage thresholds to the installed sensor wiring.

Can a two-wire proximity switch operate with 6ES7131-4BD50-0AA0?

Yes, a two-wire BERO can be used when its bias current is no more than 1.5 mA.

Will 6ES7131-4BD50-0AA0 capture a very short pulse without delay?

No, both input transitions have a typical 3 ms delay with a 2.0 to 4.5 ms range.

Which reference potential applies to the thresholds of 6ES7131-4BD50-0AA0?

The signal thresholds are referenced to L+ rather than to M.

Can the sensor-supply output of 6ES7131-4BD50-0AA0 deliver 800 mA?

No, the sensor-supply output is rated at 500 mA.

Does 6ES7131-4BD50-0AA0 provide channel diagnostic messages?

No, it provides green channel status LEDs but no diagnostic functions.

What field-cable lengths can I plan with 6ES7131-4BD50-0AA0?

The maximum cable length is 600 m for unshielded cable and 1,000 m for shielded cable.

Compatibility & Ordering Notes
Before ordering 6ES7131-4BD50-0AA0: Preserve the source-input SRC version and select the terminal layout for the actual sensor conductor count.

Compatibility Checklist for 6ES7131-4BD50-0AA0

  • Match sensor operation to the L+-referenced input thresholds.
  • Choose a compatible terminal module such as TM-E15S24-A1, TM-E15S24-01, TM-E15S23-01 or TM-E15S26-A1.
  • Keep two-wire sensor bias current within 1.5 mA and sensor-supply output current within 500 mA.
  • Include the 2.0 to 4.5 ms input delay in the signal timing assessment.
Hot Selling Models
AW20-N02-CRZ-8
3RV1011-1GA10 3RV1901-1E 3RV1915-5A 3RV1915-1AB
3RV2011-0JA20
3-22E
E3S-LS20X84
54203 16246
0821200005
CCB-84901-0101-02 849010101 185-0247R
CG6D7Y78600EV
DILM150-XHI20
CG6.D-7Y78-600.EV AT18F28085/500
ADN-20-10-IPA
WIDENT-40fq50n50-11Se1A
KMAi-E08
VS-PPC-J-4X-1227

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.