- Select an AC input arrangement with the correct 115–230 V field voltage and isolated group wiring.
- Fit the front-connector enable bridge and observe the defined signal thresholds.
- Apply the unventilated simultaneity limit at 230 V AC when sizing the active input load.
- Keep field wiring within the shielded or unshielded cable-length limit and follow the rack installation arrangement.
6ES5436-4UA12 SIMATIC S5 16-Channel AC Digital Input Module
A sixteen-channel AC input module with two isolated groups of eight, defined switching thresholds and front-connector enable wiring.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES5436-4UA12 |
| Product Type | AC digital input module |
| Core Function | Acquiring 115–230 V AC switching signals |
| Application | SIMATIC S5 U peripheral racks |
AC signal detection
Defined high and low voltage bands distinguish field switching states.
Grouped electrical isolation
Two groups of eight inputs isolate the field circuits from one another.
Long field wiring
The input circuit permits extended shielded or unshielded sensor cable runs within the stated limits.
Product Overview
6ES5436-4UA12 connects AC field switching signals to the S5 peripheral bus.
The sixteen channels are divided into two isolated groups, with rated operation from 115 to 230 V AC and different positive- and negative-edge input delays.
Key Functions
AC signal detection
Defined high and low voltage bands distinguish field switching states.
Grouped electrical isolation
Two groups of eight inputs isolate the field circuits from one another.
Long field wiring
The input circuit permits extended shielded or unshielded sensor cable runs within the stated limits.
Official Specifications
| Rated input supply | 115–230 V AC at 47–63 Hz |
|---|---|
| Input allocation | 16 channels in two isolated groups of eight |
| Low-state voltage | 0–60 V AC |
| High-state voltage | 90–264 V AC |
| Typical input current | 15 mA at 115 V AC; 25 mA at 230 V AC |
| Maximum input pulse frequency | 20 Hz |
| Positive-edge delay | Typically 5 ms; range 2–15 ms |
| Negative-edge delay | Typically 20 ms; range 10–25 ms |
| Typical input resistance | 10 kΩ |
| Simultaneity with ventilation | 100% |
| Simultaneity without ventilation | 75% at 230 V AC; 100% up to 35 °C or at 115 V AC |
| Maximum sensor cable length | 600 m unshielded; 1,000 m shielded |
| Logic-bus demand | 5 V DC; typically 100 mA |
| Rated operating dissipation | 3.5 W at 115 V AC; 17 W at 230 V AC |
| Enable input | F+/F− bridge in the front connector |
| Isolation test voltage | 2,000 V AC group-to-group; 1,500 V AC group-to-earth |
| Dimensions | 40 × 255 × 195 mm (W × H × D) |
| Approximate mass | 0.55 kg |
Frequently Asked Questions
Can I use 24 V DC field signals directly with 6ES5436-4UA12?
The input channels are rated for 115–230 V AC rather than 24 V DC.
What voltage is required for a high input state on 6ES5436-4UA12?
A high state requires an input voltage within the specified 90–264 V AC band.
How are the sixteen inputs on 6ES5436-4UA12 electrically grouped?
The channels form two isolated groups with eight inputs in each group.
Can a two-wire BERO sensor drive an input on 6ES5436-4UA12?
The input circuit permits a two-wire BERO connection.
Can I use 6ES5436-4UA12 to count a 50 Hz pulse train?
The specified maximum input pulse frequency is 20 Hz.
Must I reduce the active-channel load when using 6ES5436-4UA12 without ventilation?
At 230 V AC without ventilation the simultaneity factor is 75%, increasing to 100% up to 35 °C.
Which enable connection is required at the front connector of 6ES5436-4UA12?
Fit the specified bridge for the F+/F− enable input in the front connector.