Siemens 6EP3333-3SA00-0AY0 SITOP PSU2200 24 V DC 5 A Power Supply
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Provide a single-phase 100–240 V nominal AC supply.
- Keep the load within the temperature-derated current rating.
- Connect protective earth at PE and use the recommended feeder protection.
- Set the potentiometer only within the voltage range accepted by the connected loads.
6EP3333-3SA00-0AY0 SITOP PSU2200 24 V DC 5 A Power Supply
A slim 120 W power supply with a single-phase wide-range AC input, adjustable 24 V DC output and automatic short-circuit recovery.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP3333-3SA00-0AY0 |
| Product Type | Regulated AC/DC power supply |
| Core Function | Supplying a stabilized DC control circuit |
| Application | Industrial control-cabinet power distribution |
Wide AC input
The nominal supply range is 100–240 V AC.
Adjustable output
A potentiometer sets the output between 21.6 and 26.4 V DC.
Slim enclosure
The enclosure is 30 mm wide and uses natural convection.
Product Overview
6EP3333-3SA00-0AY0 provides a stabilized 24 V DC supply at a nominal 5 A output. The PSU2200 accepts a single-phase wide-range AC source and separates the DC output electrically from the input.
Its green 24 V OK LED indicates normal output operation. The protection arrangement combines current limiting with a hiccup characteristic at low output voltage and automatic restart after the fault is removed.
Key Functions
Regulate the control supply
The potentiometer-adjustable output covers 21.6–26.4 V DC around the nominal 24 V setting.
Bridge short mains interruptions
At 230 V AC input, minimum mains buffering is 45 ms at rated output current.
Recover from an output fault
The short-circuit arrangement automatically restarts after the fault is removed.
Official Specifications
| Nominal AC input | 1-phase, 100–240 V AC |
|---|---|
| Permitted AC input range | 90–264 V |
| Input frequency range | 47–63 Hz |
| Rated output | 24 V DC, 5 A |
| Output adjustment range | 21.6–26.4 V DC |
| Typical output power | 120 W |
| Overall voltage tolerance | 1% |
| Output ripple and peaks | 150 mV typical; 450 mV maximum |
| Minimum mains buffering | 45 ms at 230 V AC and rated output current |
| Typical efficiency | 88.5% |
| Typical power loss at rated output | 16 W |
| Maximum inrush current | 35 A at 25 °C |
| Overvoltage protection | Below 33.6 V; latch mode |
| Current-limit characteristic | 105–150% of rated load current with output above 80%; automatic recovery |
| Short-circuit characteristic | Constant current; hiccup below 80% output voltage; automatic restart |
| Output safety classification | SELV, ES1 and DVC As |
| Ingress and equipment protection | IP20; Class I |
| Ambient operating temperature | −30 to +70 °C; natural convection |
| Output-current derating | 1.67%/K above 40 °C at 115 V AC; 2.5%/K above 50 °C at 230 V AC |
| Enclosure dimensions | 30 × 124 × 117.2 mm (W × H × D) |
Frequently Asked Questions
Can I adjust 6EP3333-3SA00-0AY0 above its nominal 24 V output?
The front potentiometer permits adjustment from 21.6 to 26.4 V DC.
How should I derate 6EP3333-3SA00-0AY0 at a high cabinet temperature?
Reduce output current by 1.67% per kelvin above 40 °C at 115 V AC or by 2.5% per kelvin above 50 °C at 230 V AC.
What happens if the output of 6EP3333-3SA00-0AY0 is short-circuited?
Current limiting changes to hiccup operation below 80% output voltage and automatically restarts after the fault is removed.
How much mains hold-up is available from 6EP3333-3SA00-0AY0 at rated load?
At 230 V AC input the minimum mains-buffering time is 45 ms.
Which incoming circuit-breaker characteristic is recommended for 6EP3333-3SA00-0AY0?
A 16 A miniature circuit breaker with characteristic B is recommended in the feeder.
Does 6EP3333-3SA00-0AY0 need a protective-earth conductor?
The Class I supply has L, N and PE input terminals and requires the protective-earth connection.
Which local indication shows normal output operation on 6EP3333-3SA00-0AY0?
A green 24 V OK LED indicates normal output operation.