Overview
- Select backup duration against the real load current rather than the maximum headline time.
- Include connected-power-supply restrictions when calculating the available buffer time.
- Use correctly sized conductors and observe the 24–28.8 V input range.
- Maintain the top and bottom clearances for natural-convection cooling.
6EP1961-3BA01 SITOP PSE201U 24 V Buffer Module
A buffer module with load-dependent backup time, rated for 40 A and designed for 24 V DC power systems.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1961-3BA01 |
| Product Type | DC buffer module |
| Core Function | Bridging short supply interruptions |
| Application | 24 V SITOP control-power systems |
Load-dependent energy buffering
Backup time increases as the connected load current decreases.
Supply-status indication
A green indicator identifies supply voltage above the stated threshold.
Rail-mounted power integration
Screw terminals and a DIN-rail housing integrate the module with the control-power installation.
Product Overview
6EP1961-3BA01 bridges brief supply interruptions in a 24 V control-power system.
The available backup time depends on load current and the connected supply, while the narrow rail-mounted enclosure provides a supply-status indicator.
Key Functions
Load-dependent energy buffering
Backup time increases as the connected load current decreases.
Supply-status indication
A green indicator identifies supply voltage above the stated threshold.
Rail-mounted power integration
Screw terminals and a DIN-rail housing integrate the module with the control-power installation.
Official Specifications
| Nominal input | 24 V DC |
|---|---|
| Permitted input range | 24–28.8 V DC |
| Rated output current | 40 A |
| Output-voltage relationship | Input voltage minus approximately 1 V |
| Backup time by load | 200 ms at 40 A; 400 ms at 20 A; 800 ms at 10 A; 1.6 s at 5 A |
| Normal-operation indication | Green LED for supply voltage above 20.5 V |
| PC interface and communication | None |
| Protection classification | Class III; IP20 |
| Operating ambient | −25 to +70 °C with natural convection |
| Storage and transport ambient | −40 to +85 °C |
| Environmental category | Climate class 3K3; 5–95% RH without condensation |
| Power-terminal conductors | Screw terminals for 0.5–10 mm² |
| Mounting and required clearance | 35 mm DIN rail; 50 mm top and bottom; 0 mm lateral spacing |
| Dimensions and net mass | 70 × 125 × 121 mm (W × H × D); 1.2 kg |
Frequently Asked Questions
How long can 6EP1961-3BA01 support a 20 A load during a power interruption?
The stated backup time at a 20 A load is 400 ms.
Does the supply model affect the backup time of 6EP1961-3BA01?
The maximum backup time is 100 ms when combined with 6EP1336-2BA10 at a 20 A load.
What does the green LED on 6EP1961-3BA01 indicate?
The green LED indicates that the supply voltage is above 20.5 V.
Will the output voltage of 6EP1961-3BA01 equal the incoming supply voltage?
The output is approximately 1 V below the input voltage.
Can I read operating data from 6EP1961-3BA01 through a PC connection?
The module has no PC interface or communication function.
What clearance must be allowed for natural convection around 6EP1961-3BA01?
Provide 50 mm above and below the module.
Can 6EP1961-3BA01 be fixed directly to a wall without a rail?
The specified fastening method is 35 mm DIN-rail mounting, with direct wall mounting unsupported.