- Use a controlled DC input between 22 and 30 V with sufficient current for the four branches.
- Set the channel thresholds individually and do not parallel outputs.
- Keep 50 mm of ventilation clearance above and below the DIN-rail-mounted module.
- Do not combine this module with the specified 40 A DC UPS types 6EP1931-2FC21 or 6EP1931-2FC42.
6EP1961-2BA00 SITOP select Four-Channel Selectivity Module
A four-channel 24 V DC module with adjustable 2–10 A thresholds and local branch-status indication.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1961-2BA00 |
| Product Type | DC selectivity and diagnosis module |
| Core Function | Separating overloaded DC load branches |
| Application | Protected 24 V control-power distribution |
Protect four load branches
Each output is rated for up to 10 A and has an adjustable current response threshold from 2 to 10 A.
Sequence output connection
All outputs can connect together or sequentially with a programmed 24 ms or 100 ms delay.
Locate an overloaded branch
Green/red LEDs show the channel state and a common NO signal contact supports remote status indication.
Product Overview
6EP1961-2BA00 distributes a controlled 24 V DC supply to four monitored load branches.
Adjustable trip thresholds, a common signaling contact and selectable sequential connection support load coordination and fault diagnosis.
Key Functions
Protect four load branches
Each output is rated for up to 10 A and has an adjustable current response threshold from 2 to 10 A.
Sequence output connection
All outputs can connect together or sequentially with a programmed 24 ms or 100 ms delay.
Locate an overloaded branch
Green/red LEDs show the channel state and a common NO signal contact supports remote status indication.
Official Specifications
| Nominal Input Voltage | 24 V DC |
|---|---|
| Permitted Input Range | 22–30 V DC |
| Rated Input Current | 40 A |
| Output Arrangement | 4 outputs rated up to 10 A each at 60 °C |
| Trip-Threshold Adjustment | 2–10 A per channel, by potentiometer |
| Output Voltage | Input voltage minus approximately 0.3 V |
| Overload Trip | Approximately 5 s at 1.0–1.3 times the set current |
| High-Overcurrent Trip | Approximately 50–100 ms at 1.3 times the set current |
| Fast Trip Condition | Approximately 0.5 ms when current exceeds its setting and input voltage falls below 20 V |
| Sequential Connection Delay | 24 ms or 100 ms; simultaneous connection also selectable |
| Typical Off-State Residual Current | 20 mA |
| Efficiency and Power Loss | 97% efficiency; 30 W typical at rated load |
| Common Signal Contact | Normally open, rated 0.5 A at 24 V DC |
| Included Output Fuses | Four 15 A blade-type fuses |
| Operating Temperature | 0 to +60 °C with natural convection |
| Protection | IP20; Class III |
| Output and Signal Terminals | Screw terminals for 0.22–4 mm² conductors |
| Ventilation Clearance | 50 mm above and below; 0 mm at sides |
| Dimensions (W × H × D) | 72 × 90 × 90 mm |
| Net Weight | 0.4 kg |
Frequently Asked Questions
Can I parallel the outputs of 6EP1961-2BA00 to supply a larger branch?
Parallel connection of the outputs is not supported.
Can 6EP1961-2BA00 start its load branches one after another?
Sequential connection can be configured with a 24 ms or 100 ms delay.
How do I change the trip level of a branch on 6EP1961-2BA00?
Use the channel potentiometer to set a current response threshold between 2 and 10 A.
Does a switched-off output of 6EP1961-2BA00 provide galvanic isolation?
The input and output are not electrically separated when a channel is switched off.
How can a PLC read the collective status of 6EP1961-2BA00?
A common normally open signaling contact is rated for 0.5 A at 24 V DC.
Can 6EP1961-2BA00 operate with the 40 A SITOP DC UPS modules 6EP1931-2FC21 or 6EP1931-2FC42?
This selectivity module is not designed for operation with those 40 A DC UPS modules.
How do I reset a tripped channel on 6EP1961-2BA00?
Reset the channel using the keys on the module.