Overview
SIEMENS SIMATIC S7-1500

6EP1332-4BA00 SIMATIC PM 1507 24 V DC 3 A Power Supply

A 72 W PM 1507 load supply with automatic AC range selection, fixed 24 V DC output and S7-1500-rail mounting.

At a Glance

Brand Siemens
Model 6EP1332-4BA00
Product Type Load power-supply module
Core Function Converts mains power to regulated DC
Application S7-1500 control and field-load power circuits

AC input selection

Automatically selects the 120 V or 230 V mains range.

Regulated DC output

Provides fixed 24 V DC at up to 3 A.

Panel integration

Mounts on the S7-1500 rail with removable terminals.

Product Overview

6EP1332-4BA00 is a stabilized PM 1507 load power supply for SIMATIC S7-1500 applications.

Its isolated output supplies 24 V DC loads, with electronic short-circuit shutdown, automatic restart and separate indicators for normal operation, error and standby.

Ordering focus: Match the mains range, DC load budget and S7-1500 rail, and provide the mounting clearance and feeder protection required for the installation.
Key Functions

Automatic mains-range handling

The input automatically selects between 85–132 V AC and 170–264 V AC.

Protected load supply

Electronic shutdown with automatic restart handles output short circuits, while an additional control loop limits overvoltage.

Load and status management

The fixed 24 V output supplies up to 3 A, and green, red and yellow indicators identify its operating state.

Official Specifications
AC input ranges 85–132 V AC or 170–264 V AC; automatic range selection
Input frequency 45–65 Hz
Rated input current 1.4 A at 120 V; 0.8 A at 230 V
Maximum inrush current 23 A at 25 °C
Output voltage 24 V DC, fixed
Output-current range 0–3 A
Rated output power 72 W
Overall voltage tolerance 1%
Maximum residual ripple 50 mV
Maximum voltage peaks 150 mV
Minimum mains buffering 20 ms at rated output current and 93/187 V AC input
Typical efficiency 87%
Typical rated-load power loss 11 W
Current limiting 3.15–3.6 A; 3.4 A typical
Output short-circuit response Electronic shutdown with automatic restart
Overvoltage limitation Below 28.8 V by an additional control loop
Operating temperature 0–60 °C horizontal; 0–40 °C vertical mounting
Storage and transport temperature −40 to +85 °C
Protection and isolation IP20, Class I; isolated SELV output
Dimensions and weight 50 × 147 × 129 mm (W × H × D); 0.45 kg
Frequently Asked Questions

Do I need a manual mains-voltage selector for 6EP1332-4BA00?

The supply automatically selects its 120 V or 230 V AC input range.

Can I adjust the output voltage of 6EP1332-4BA00?

The regulated output is fixed at 24 V DC and is not adjustable.

Can two units of 6EP1332-4BA00 increase the available power?

Two supplies may be connected in parallel for increased power under the specified installation arrangement.

What happens after a short circuit at the output of 6EP1332-4BA00?

The supply shuts down electronically and restarts automatically.

Can I mount 6EP1332-4BA00 on a standard 35 mm DIN rail?

The module mounts on the S7-1500 rail rather than a standard DIN rail or wall.

How much free space should I leave around 6EP1332-4BA00?

Leave at least 40 mm above and below the supply, with no required spacing at either side.

Which feeder breaker is recommended for 6EP1332-4BA00?

Use a 10 A type-B or 6 A type-C miniature circuit breaker as the recommended feeder protection.

Compatibility & Ordering Notes
Before ordering 6EP1332-4BA00: Select this non-Ex PM 1507 for the S7-1500 rail and the intended load power, retaining the specified feeder protection, terminal sizing and cooling clearance.

Compatibility Checklist for 6EP1332-4BA00

  • Calculate the total load against the 3 A output rating.
  • Use S7-1500-rail mounting.
  • Leave 40 mm clearance above and below.
  • Observe the lower 40 °C operating limit for vertical mounting.
  • Use 0.5–2.5 mm² conductors at the removable input and output terminals.
  • This article has no hazardous-area Ex approval.
Hot Selling Models
4-TWIN-PE 3031416
3RN2011-1BA30
1816705000000200 A7233
25142/11 G-CUSN12
ZD04H059MSS0005H11
VW3A58732
N-ID8
N-OD8
AZ40
7PR4140-6PM00
CDM420-0001 2028933 + CMC400-101 + CMF400-DPS
2731128
RSDQB32F20DK
31364000
9475/12-04-21

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.