Siemens 6EP1331-5BA00 SITOP PSU100C 24 V 0.6 A Power Supply
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Calculate the steady and transient load demand for the 0.6 A output and the fixed 24 V setting.
- Connect PE and use the specified 0.5–2.5 mm² conductors and terminal arrangement.
- Mount on a suitable 35 mm DIN rail with 50 mm top/bottom spacing and natural convection.
- Check feeder protection; Siemens recommends a miniature circuit breaker from 16 A characteristic B or 10 A characteristic C.
6EP1331-5BA00 SITOP PSU100C 24 V 0.6 A Power Supply
22.5 mm wide PSU100C with fixed 24 V, 0.6 A output, wide AC/DC input, electronic short-circuit shutdown and automatic restart.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1331-5BA00 |
| Product Type | Stabilized DIN-rail power supply |
| Core Function | Isolated regulated 24 V DC output |
| Application | Compact industrial control and auxiliary power circuits |
Wide AC/DC input
The input accepts 85–264 V AC or 110–300 V DC within the specified supply conditions.
Fixed regulated output
The isolated 24 V DC output supplies up to 0.6 A without an output-voltage adjustment.
Automatic short-circuit recovery
Electronic shutdown and automatic restart handle a short circuit according to the specified protection characteristic.
Product Overview
6EP1331-5BA00 is a compact SITOP PSU100C stabilized power supply rated at 24 V DC and 0.6 A. It accepts a wide single-phase AC or DC input and provides an isolated output for industrial control loads.
The output is fixed at 24 V and is not adjustable. A green LED indicates output voltage OK, while electronic shutdown with automatic restart provides the documented short-circuit response. The narrow housing snaps onto a 35 mm DIN rail.
Key Functions
Wide AC/DC input
The input accepts 85–264 V AC or 110–300 V DC within the specified supply conditions.
Fixed regulated output
The isolated 24 V DC output supplies up to 0.6 A without an output-voltage adjustment.
Automatic short-circuit recovery
Electronic shutdown and automatic restart handle a short circuit according to the specified protection characteristic.
Official Specifications
| Rated AC input | 100–230 V AC; permissible range 85–264 V |
|---|---|
| DC input range | 110–300 V DC |
| Input frequency | 47–63 Hz |
| Rated output | 24 V DC, 0.6 A |
| Output-voltage adjustment | Not adjustable |
| Typical output power | 14 W |
| Input current | 0.28 A at 100 V AC; 0.18 A at 230 V AC |
| Maximum inrush current | 28 A at 25 °C |
| Minimum mains buffering | 20 ms at 230 V input and rated output current |
| Overall voltage tolerance | 3% |
| Maximum ripple / voltage peak | 200 mV / 300 mV |
| Start-up behavior | Approximately 5% output overshoot; maximum delay 1 s |
| Efficiency | 82% |
| Power loss | 2.6 W typical at rated load; 0.75 W maximum at no load |
| Short-circuit protection | Electronic shutdown with automatic restart; typical 0.7 A |
| Parallel operation | Not supported |
| Electrical protection | Class I; isolated SELV output; IP20 |
| Operating / storage temperature | −20 to +70 °C with natural convection / −40 to +85 °C |
| Dimensions and weight | 22.5 × 80 × 100 mm (W × H × D); 0.12 kg |
| Installation clearance | 50 mm above and below; 0 mm on either side |
Frequently Asked Questions
Can the output voltage of 6EP1331-5BA00 be adjusted?
No; the PSU100C variant has a fixed 24 V DC output.
May two units of 6EP1331-5BA00 be paralleled to increase output current?
No; parallel operation is not supported for this power-supply variant.
Does 6EP1331-5BA00 require a protective-earth connection?
Yes; it is a Class I power supply with L, N and PE input terminals.
What power-interruption buffering is specified for 6EP1331-5BA00?
The minimum buffering time is 20 ms at 230 V input and rated output current.
Does 6EP1331-5BA00 start without any output overshoot?
The specified start-up characteristic includes approximately 5% output-voltage overshoot.
How much vertical clearance is needed around 6EP1331-5BA00?
Keep 50 mm above and 50 mm below the housing for the specified installation arrangement.
What is the short-circuit recovery behavior of 6EP1331-5BA00?
The protection uses electronic shutdown with automatic restart.