siemens 6ep1331 1sl11 sitop power 2 24 v 2 a power supply-0

For SIEMENS

Home >  Products >  For SIEMENS

Siemens 6EP1331-1SL11 SITOP Power 2 24 V 2 A Power Supply

Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months

  • Overview
  • Hot Selling Models
  • Recommended Products
Overview
SITOP Power Basic Line

6EP1331-1SL11 SITOP Power 2 24 V 2 A Power Supply

A 24 V DC, 2 A SITOP supply with selectable 120/230 V AC input, natural-convection cooling and short-circuit automatic restart.

At a Glance

Brand Siemens
Model 6EP1331-1SL11
Product Type Rail-mounted power supply
Core Function Stabilized DC control power
Application Industrial control cabinets

Selectable mains input

The voltage selector chooses the 85–132 V or 170–264 V AC operating window.

Protected DC output

The output is short-circuit-proof and open-circuit-proof, with automatic restart after an output short circuit.

Convection-cooled installation

Vertical DIN-rail installation with terminals at the bottom and clear ventilation space supports natural cooling.

Product Overview

6EP1331-1SL11 provides a floating, stabilized 24 V DC output from a single-phase AC supply.

The input selector matches the 120 V or 230 V range, while current limitation and automatic restart after an output short circuit define the supply’s overload behavior.

Ordering focus: Set the AC input selector correctly, keep the output demand within 2 A and provide at least 40 mm of ventilation space above and below.
Key Functions

Selectable mains input

The voltage selector chooses the 85–132 V or 170–264 V AC operating window.

Protected DC output

The output is short-circuit-proof and open-circuit-proof, with automatic restart after an output short circuit.

Convection-cooled installation

Vertical DIN-rail installation with terminals at the bottom and clear ventilation space supports natural cooling.

Official Specifications
Nominal input 120/230 V AC, single phase, 50/60 Hz
Input voltage windows 85–132 V AC or 170–264 V AC
Input current 0.9 A at 120 V; 0.6 A at 230 V
Power consumption 58 W
DC output voltage 24 V ±3%
Output current range 0–2 A
Maximum ripple Less than 150 mV peak-to-peak
Maximum switching spikes Less than 240 mV peak-to-peak
Full-load efficiency Above 82% at 230 V AC
Inrush characteristic Less than 20 A at 25 °C and 230 V AC; I²t of 1 A²s
Recommended upstream breaker 3 A, characteristic C
Current limitation Typically 1.1–1.3 times rated current
Mains buffering More than 20 ms at 93/187 V input and full load
Protection IP20; protection class I; SELV output
Operating temperature 0 to +60 °C
Storage and transport temperature −40 to +85 °C
Cooling Natural air convection
Mounting rail DIN EN 50022, 35 × 15 mm
Terminal wiring 0.5–2.5 mm²; recommended screw torque 0.4–0.6 Nm
Weight 0.42 kg
Frequently Asked Questions

How should I set the mains selector on 6EP1331-1SL11?

Use the 120 V position for 85–132 V AC and the 230 V position for 170–264 V AC.

Can I parallel two 6EP1331-1SL11 supplies to obtain more output current?

Parallel connection to increase output power is not permitted.

Can two identical 6EP1331-1SL11 supplies be connected in series?

Two units of the same type may be connected in series to increase the output voltage.

What clearance does 6EP1331-1SL11 need for cooling?

Leave at least 40 mm of free space above and below the vertically installed supply.

What happens after an output short circuit on 6EP1331-1SL11?

The supply uses current limitation and restarts automatically after the short-circuit condition clears.

Where should the wiring terminals face when mounting 6EP1331-1SL11?

Install the supply vertically with both input and output terminals at the bottom.

What tightening torque should I use on the terminals of 6EP1331-1SL11?

The recommended terminal-screw torque is 0.4–0.6 Nm.

Compatibility & Ordering Notes
Before ordering 6EP1331-1SL11: Set the AC input selector correctly, keep the output demand within 2 A and provide at least 40 mm of ventilation space above and below.

Before installation

  • Set the input-voltage selector before energizing the supply.
  • Install vertically with terminals downward and at least 40 mm clearance above and below.
  • Use the specified conductor range and recommended screw torque.
  • Do not parallel units for higher current; use only the permitted same-type series arrangement when a higher voltage is required.
Hot Selling Models
ZK2030-1200-0100
MM2-4TX1
ADN-12-70-IPAQ-S2-5K8
KSA-3-20 031000073 7-409-00-016-0
6FC9344-3QA
MA-1.1s
6ED1055-1CB10-0BA2
Allen-Bradley 800T-QB24
UHV 150
IL9151.12 0049135
2668710000 AITB 6BB2CBL
3RV1 421-1HA10
0801 V4 332-020-04
T4000-DNA25C
NXD32/25

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop