Siemens TELEPERM M 6DS1222-8BA N-AT Local-Bus Interface Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use only with the documented OS 525 and CS 275 local-bus architecture.
- Keep the local-bus device count and ground-potential difference within the specified limits.
- Restore both redundant bus paths and verify half-duplex communication after replacement.
19:05:33Siemens · TELEPERM M / OS 525
6DS1222-8BA N-AT Local-Bus Interface Module
Siemens 6DS1222-8BA is the N-AT local-bus interface used to connect an OS 525 operator station to the redundant, isolated 20 m local bus of the TELEPERM M CS 275 system.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6DS1222-8BA |
| Product Type | Operator-station local-bus interface module |
| Core Function | Connects an OS 525 station to the CS 275 20 m local bus |
| Application or Compatible Series | TELEPERM M OS 525 and CS 275 local-bus systems |
Host Interface
Confirm the OS 525 computer and its short-AT slot arrangement.
Bus Segment
Preserve the redundant 20 m local-bus cabling and station topology.
Signal Integrity
Check grounding, isolation and permitted device count before startup.
Product Overview
Siemens 6DS1222-8BA is the N-AT local-bus interface used to connect an OS 525 operator station to the redundant, isolated 20 m local bus of the TELEPERM M CS 275 system.
Provides the operator station with a hardware interface to the CS 275 local bus. Supports input and output paths with wired-OR, asymmetric and isolated signaling. Uses the documented local-bus data rate, parity protection and half-duplex operation.
Key Functions
OS 525 Local-Bus Access
Provides the operator station with a hardware interface to the CS 275 local bus.
Redundant Bus Signaling
Supports input and output paths with wired-OR, asymmetric and isolated signaling.
Deterministic Legacy Communication
Uses the documented local-bus data rate, parity protection and half-duplex operation.
Official Specifications
| Interface Designation | N-AT module |
|---|---|
| Host Expansion Format | Short AT |
| Local-Bus Length | 20 m |
| Bus Arrangement | Redundant input/output with wired-OR coupling |
| Electrical Isolation | Isolated local-bus interface |
| High Input Level | At least 2.0 V |
| Low Input Level | No more than 0.8 V |
| High Output Level | At least 2.7 V |
| Low Output Level | No more than 0.7 V |
| Self-Contained Bus Data Rate | 40 kbit/s |
| Remote Interface Data Rate | 250 kbit/s through the inductive converter |
| Maximum Local-Bus Devices | 9 |
| Permitted Ground Difference | Up to 2 V |
| Data Integrity | Block parity with distance 4 |
| Transmission Mode | Half duplex |
| Supply Voltage | 5 V DC |
Frequently Asked Questions
Which operator station uses 6DS1222-8BA?
The interface is intended for the documented TELEPERM M OS 525 hardware arrangement.
What bus does 6DS1222-8BA connect to?
It connects the operator station to the redundant CS 275 20 m local bus.
How many devices may share the local bus with 6DS1222-8BA?
The documented 20 m local-bus segment permits up to nine devices.
What data rate does 6DS1222-8BA use on the direct local bus?
The self-contained local-bus interface operates at 40 kbit/s.
Does 6DS1222-8BA provide electrical isolation?
The N-AT interface provides isolated signaling for the local-bus path.
What should I record before replacing 6DS1222-8BA?
Record the short-AT slot, bus connectors, redundant path and station addressing.
What must I check after installing 6DS1222-8BA?
Verify bus levels, parity diagnostics, device count and communication with the OS 525 station.