Siemens Siemens Process Automation 6DL3100-8AC05 Legacy Automation Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Product Overview
- Key Functions
- Official Specifications
- Frequently Asked Questions
- Compatibility & Ordering Notes
- Hot Selling Models
- Recommended Products
Overview
SIEMENS ADDFEM · POCO PLUS FRONT-END MODULE
6DL3100-8AC05 AddFEM PoCo Plus
Front-end module for fast position-control signal preparation with channel-selective redundancy in SPPA-T3000 automation systems.
At a Glance
| Manufacturer | Siemens |
| Article Number | 6DL3100-8AC05 |
| Product Type | AddFEM PoCo Plus front-end module |
| Core Function | Fast position-control signal preparation with channel-selective redundancy |
| Application / Compatible Series | SPPA-T3000 with S7-400 PROFIBUS DP |
PoCo Plus Processing
Executes fast position-control functions and extends PoCo with channel-selective redundancy.
Redundant Communication
Supports redundant DPV1 channels A and B with PrmCommand changeover and redundancy diagnostics.
Installation Options
Suitable for double DIN-rail mounting or direct wall mounting on steel brackets.
Product Overview
6DL3100-8AC05 is the Siemens AddFEM PoCo Plus front-end module for SPPA-T3000 automation systems. It performs fast position-control signal preparation close to the process I/O, reducing the transfer-cycle burden on the master automation processor.
PoCo Plus extends the AddFEM PoCo function with channel-selective redundancy. The module also supports DPV1 services, redundant PROFIBUS channels, diagnostic alarms, and redundancy-status data.
Key Functions
PoCo Plus Signal Processing
Executes fast position-control functions in the front-end module and supports channel-selective redundancy.
Redundant DPV1 Communication
Uses two PROFIBUS DP interfaces, PrmCommand changeover between channels A and B, and redundancy-state diagnostics.
Mixed Process I/O
Combines analog, digital, and count-pulse channels for fast acquisition and control-output tasks.
Official Specifications
| Dimensions (H × W × D) | 295 × 75 × 209 mm |
| Weight | 2.8 kg |
| Rated Input Voltage | 24 V DC |
| Permissible Input Range | Static: 19.2 to 30 V DC; dynamic: 18.5 to 30.2 V |
| Rated Module Supply Current | 0.8 A |
| Rated Load Supply Current | 8 A |
| Power-Failure Buffering | At least 10 ms |
| PROFIBUS DP Interfaces | 2 |
| PROFIBUS DP Transmission Rate | 9.6 kbps to 12 Mbps |
| Analog Inputs | 12 total: 6 current inputs and 6 current/voltage inputs |
| Analog Input Impedance | 41.8 Ω for current measurement; 100 kΩ for voltage measurement |
| Analog Outputs | 8 |
| Analog Output Transfer Time | 1 ms |
| Fixed Digital Inputs | 12, channels 5 to 16 |
| Digital Semiconductor Outputs | 16; may also operate as digital inputs |
| Count Pulse Inputs | 3 |
| Count Input Frequency | 0 to 20 kHz |
| Counter Resolution | 32 bit |
| Operating Temperature | 0 to 50 °C at rated load |
| Storage Temperature | -40 to +70 °C |
Frequently Asked Questions
Which SPPA-T3000 configuration supports 6DL3100-8AC05?
It integrates with an S7-400 PROFIBUS interface, either onboard or through a CP443-5 EXT module, using the AddFEM/SPPA-T3000 GSD model.
What position-control task is 6DL3100-8AC05 designed to execute?
PoCo Plus performs fast position-control signal preparation and extends PoCo with channel-selective redundancy.
How does 6DL3100-8AC05 handle redundant PROFIBUS communication?
Redundant DPV1 channels A and B change over through PrmCommand, while the redundancy state is supplied as diagnostic data.
What power supply range is required for 6DL3100-8AC05?
The rated module supply is 24 V DC, with a permissible static range of 19.2 to 30 V DC.
Which mounting arrangements are available for 6DL3100-8AC05?
The enclosure can be mounted on a double DIN rail or directly on a wall using steel brackets.
What process I/O is available on 6DL3100-8AC05?
The module provides 12 analog inputs, 8 analog outputs, 12 fixed digital inputs, 16 semiconductor outputs that can also operate as inputs, and 3 count-pulse inputs.
What sequence should technicians follow before removing 6DL3100-8AC05 from a redundant pair?
Move the target module from RUN to STOP so the partner assumes the master function, then remove the redundancy fiber, disconnect power, and disconnect the process-signal cables.
Compatibility & Ordering Notes
Compatibility Checklist for 6DL3100-8AC05
- Use the AddFEM/SPPA-T3000 GSD model with an onboard S7-400 PROFIBUS interface or CP443-5 EXT.
- Provide a 24 V DC module supply within the static 19.2 to 30 V DC operating range.
- For a redundant pair, use two 1.6 m fiber-optic cables, Siemens order number 6DL9901-8AA.
- Use one AddFEM connector set, Siemens order number 6DL9900-8AA, for process cables and module power.