Siemens SIMATIC ET 200PA SMART+ 6DL1162-6BL00-0PH1 DQ 32x24VDC
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Product Overview
- Key Functions
- Official Specifications
- Frequently Asked Questions
- Compatibility & Ordering Notes
- Hot Selling Models
- Recommended Products
Overview
Siemens · SIMATIC ET 200PA SMART+
6DL1162-6BL00-0PH1 DQ 32x24VDC/0.5A PA Digital Output Module
Siemens 6DL1162-6BL00-0PH1 is the SIMATIC ET 200PA SMART+ DQ 32x24VDC/0.5A PA digital output module with 32 parameterizable current-sourcing channels, electronic short-circuit protection and channel diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6DL1162-6BL00-0PH1 |
| Product Type | Parameterizable current-sourcing digital output module |
| Core Function | Controls industrial DC actuators with protected electronic outputs |
| Application or Compatible Series | SIMATIC ET 200PA SMART+ distributed I/O stations |
Channel Mapping
Record all 32 output assignments and their group wiring before removing the installed module.
Load Verification
Check actuator current, inrush demand and switching frequency against the selected channel limits.
Diagnostic Setup
Transfer the parameterized substitute-value, supply-monitoring and short-circuit diagnostic settings.
Product Overview
Siemens 6DL1162-6BL00-0PH1 is the SIMATIC ET 200PA SMART+ DQ 32x24VDC/0.5A PA digital output module with 32 parameterizable current-sourcing channels, electronic short-circuit protection and channel diagnostics.
Thirty-two current-sourcing channels provide compact control of 24 V DC field actuators. Clocked short-circuit protection and overload handling protect individual output circuits. Supply monitoring, channel-level short-circuit detection and diagnostic alarms support maintenance.
Key Functions
Dense Digital Output
Thirty-two current-sourcing channels provide compact control of 24 V DC field actuators.
Electronic Protection
Clocked short-circuit protection and overload handling protect individual output circuits.
Channel Diagnostics
Supply monitoring, channel-level short-circuit detection and diagnostic alarms support maintenance.
Official Specifications
| Output Process Data | 4 bytes |
|---|---|
| Number of Digital Outputs | 32 |
| Output Switching Principle | Current-sourcing |
| Short-Circuit Response Threshold | 2 A typical |
| Inductive Shutdown Voltage Limitation | L+ minus 53 V typical |
| Maximum Resistive Load Current | 0.5 A |
| Maximum Lamp Load | 5 W |
| Permitted Load Resistance | 48 Ω to 4 kΩ |
| Rated Current at Signal 1 | 0.5 A |
| Maximum Residual Current at Signal 0 | 0.1 mA |
| Typical Turn-On Delay with Resistive Load | 54 µs |
| Typical Turn-Off Delay with Resistive Load | 48 µs |
| Maximum Resistive-Load Switching Frequency | 100 Hz |
| Maximum Inductive-Load Switching Frequency | 2 Hz |
| Maximum Lamp-Load Switching Frequency | 10 Hz |
| Maximum Total Module Output Current | 10 A |
| Maximum Shielded Cable Length | 1,000 m |
| Maximum Unshielded Cable Length | 600 m |
| Redundant Load Control | Two outputs from the same group |
| Maximum Horizontal-Mount Current at 70 °C | 10 A |
Frequently Asked Questions
How should I transfer the field wiring to 6DL1162-6BL00-0PH1?
Move each current-sourcing output and its reference conductor according to the recorded channel and group assignment.
Which loads are suitable for 6DL1162-6BL00-0PH1?
Use 24-volt DC actuators whose steady-state, surge and switching demands remain within the specified output limits.
Can 6DL1162-6BL00-0PH1 drive a redundant load from two channels?
Yes, two outputs in the same group may be used for redundant load control.
What causes an electronic short-circuit response on 6DL1162-6BL00-0PH1?
An overload or short circuit that reaches the typical two-ampere threshold activates the channel protection.
How should substitute values be configured on 6DL1162-6BL00-0PH1?
Set the required safe output state for each channel in the station parameters before commissioning.
What cable-length limit applies to 6DL1162-6BL00-0PH1?
Keep shielded runs within one thousand metres and unshielded runs within six hundred metres.
What should I check if 6DL1162-6BL00-0PH1 reports a supply fault?
Check the module supply, reference wiring, polarity, terminal condition and parameterized diagnostic response.
Compatibility & Ordering Notes
Compatibility Checklist
- Confirm the station configuration contains the exact DQ 32x24VDC/0.5A PA module entry.
- Preserve channel groups, load reference wiring, diagnostic settings and substitute values.
- Calculate channel and total-module current for the actual mounting position and ambient temperature.