Siemens SIMATIC ET 200SP HA 6DL1131-6BL00-0PH1 DI 32x24VDC
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Confirm the station is SIMATIC ET 200SP HA and the engineering system is PCS 7 V9.0 or later.
- Order an H1 or P0 terminal block and retain the CC00 color coding.
- Keep the field supply within 19.2 to 28.8 V DC and verify two-wire sensor leakage.
- Reserve four process-data bytes plus four bytes for quality information.
- Configure wire-break, edge-evaluation and alarm parameters for the installed channels.
Siemens · SIMATIC ET 200SP HA
6DL1131-6BL00-0PH1 DI 32x24VDC HA Digital Input Module
Siemens 6DL1131-6BL00-0PH1 is the SIMATIC ET 200SP HA DI 32x24VDC HA digital input module with thirty-two parameterizable P-reading channels, channel diagnostics and fast process acquisition.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6DL1131-6BL00-0PH1 |
| Product Type | Digital Input Module |
| Core Function | Connects discrete field sensors to a high-availability distributed I/O station |
| Application or Compatible Series | SIMATIC ET 200SP HA and SIMATIC PCS 7 systems |
Terminal-Block Match
Use an H1 or P0 terminal block and order the selected terminal block separately.
Channel Configuration
Plan thirty-two P-reading inputs with the required edge evaluation and channel diagnostics.
Engineering Baseline
Integrate and parameterize the module with SIMATIC PCS 7 V9.0 or later.
Product Overview
Siemens 6DL1131-6BL00-0PH1 is the SIMATIC ET 200SP HA DI 32x24VDC HA digital input module with thirty-two parameterizable P-reading channels, channel diagnostics and fast process acquisition.
Thirty-two inputs acquire industrial 24 V DC sensor and contact states in one module. Hardware alarms, diagnostic alarms and optional wire-break monitoring support detailed fault location. A 250 microsecond module cycle supports operation from −40 °C in high-availability installations.
Key Functions
Dense Digital Acquisition
Thirty-two inputs acquire industrial 24 V DC sensor and contact states in one module.
Channel-Level Diagnostics
Hardware alarms, diagnostic alarms and optional wire-break monitoring support detailed fault location.
Fast Extended-Temperature Operation
A 250 microsecond module cycle supports operation from −40 °C in high-availability installations.
Official Specifications
| Firmware Version | V1.0 |
|---|---|
| Usable Terminal Blocks | H1 and P0 |
| Module Color Code | CC00 |
| Identification and Maintenance Data | I&M0 through I&M3 |
| Supply Voltage | 24 V DC; permissible range 19.2 to 28.8 V |
| Module Current Consumption | 11.5 mA rated; 15 mA maximum |
| Address Space | 4 bytes plus 4 bytes for QI information |
| Digital Input Count | 32 |
| Input Characteristic | IEC 61131 Type 1 and Type 3 |
| Input Logic Levels | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Signal-1 Input Current | 2.5 mA typical |
| Input Delay | 0 to 1: 3.2 to 5.3 ms; 1 to 0: 2.9 to 4.5 ms |
| Maximum Cable Length | 1,000 m shielded; 600 m unshielded |
| Two-Wire Sensor Quiescent Current | 1.5 mA maximum |
| Wire-Break Contact Protection | Optional 15 to 18 kΩ protective circuit |
| Isolation Test | 1,500 V DC for 1 minute |
| Operating Temperature | −40 to +70 °C horizontal; −40 to +60 °C vertical |
| Dimensions and Weight | 22.5 × 115 × 138 mm; approximately 150 g |
| Module Cycle Time | 250 µs |
Frequently Asked Questions
Which terminal block should I order for 6DL1131-6BL00-0PH1?
Use an H1 or P0 terminal block and order it separately from the I/O module.
Which engineering release can configure 6DL1131-6BL00-0PH1?
Configure and integrate the module with PCS 7 V9.0 or later.
What field-supply range should I provide for 6DL1131-6BL00-0PH1?
Provide 24 V DC within the permitted 19.2 to 28.8 V range.
How far can I run sensor cables to 6DL1131-6BL00-0PH1?
Cable runs may reach 1,000 m when shielded or 600 m when unshielded.
Can I connect two-wire sensors to 6DL1131-6BL00-0PH1?
Yes, provided their permissible quiescent current does not exceed 1.5 mA.
How can I use wire-break monitoring with simple contacts on 6DL1131-6BL00-0PH1?
Enable channel diagnostics and fit the optional 15 to 18 kΩ protective circuit where simple contacts require it.
Does installation orientation change the temperature limit for 6DL1131-6BL00-0PH1?
Yes, the maximum is +70 °C horizontally and +60 °C vertically, with a −40 °C lower limit in either position.