Siemens SIMATIC HMI SMART 1000 IE V3 6AV6648-0AF11-3AX0
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Product Overview
- Key Functions
- Official Specifications
- Frequently Asked Questions
- Compatibility & Ordering Notes
- Hot Selling Models
- Recommended Products
Overview
Siemens · SIMATIC HMI SMART Line V3
6AV6648-0AF11-3AX0 SIMATIC HMI SMART 1000 IE V3 Touch Panel
The Siemens SIMATIC HMI SMART 1000 IE V3 is a 10.1-inch widescreen touch panel with Ethernet, isolated RS422/485 and USB connectivity.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6AV6648-0AF11-3AX0 |
| Product Type | 10.1-inch widescreen resistive-touch HMI panel |
| Core Function | Provides machine visualization, alarm handling, recipes and operator control through Ethernet and serial PLC communication |
| Application or Compatible Series | SMART Line V3 projects connected to S7-200, S7-200 SMART, LOGO! and supported serial PLC systems |
Exact Identification
Match the complete article number and SMART 1000 IE V3 hardware generation.
Project Compatibility
Preserve the WinCC flexible SMART project, device settings, recipes and communication drivers.
Installation Check
Confirm the mounting opening, 24 V supply, Ethernet addressing and serial-port pinout.
Product Overview
The Siemens SIMATIC HMI SMART 1000 IE V3 is a 10.1-inch widescreen touch panel with Ethernet, isolated RS422/485 and USB connectivity.
The TFT display provides 1024 × 600 resolution and 65,536 colors for machine visualization. An isolated RS422/485 interface and a 10/100 Mbps Industrial Ethernet port support the specified PLC connections. The analog resistive touchscreen, USB host and buffered real-time clock support practical machine-level operation.
Key Functions
10.1-Inch Widescreen HMI
The TFT display provides 1024 × 600 resolution and 65,536 colors for machine visualization.
Flexible PLC Connectivity
An isolated RS422/485 interface and a 10/100 Mbps Industrial Ethernet port support the specified PLC connections.
Touch-Based Operation
The analog resistive touchscreen, USB host and buffered real-time clock support practical machine-level operation.
Official Specifications
| Unpacked Weight | Approximately 1200 g |
|---|---|
| Display Technology | LCD TFT |
| Active Display Area | 222.7 × 125.3 mm; 10.1 in |
| Display Resolution | 1024 × 600 pixels |
| Color Depth | 16 bit; 65,536 colors |
| Backlight | LED; approximately 15,000 h to half brightness |
| Touch Input | Analog resistive touchscreen |
| Data Memory | 128 MB |
| Program Memory | 256 MB |
| Serial Interface | 1 × RS422/485; up to 187.5 Kb/s |
| Industrial Ethernet Interface | 1 × RJ45; 10/100 Mb/s with auto crossover |
| USB Interface | 1 × USB 2.0 host; maximum 500 mA |
| Rated Supply Voltage | 24 V DC |
| Permissible Supply Range | 19.2 to 28.8 V DC |
| Maximum Transient Voltage | 35 V for 500 ms |
| Typical Current Consumption | Approximately 230 mA |
| Maximum Continuous Current | Approximately 370 mA |
| Real-Time Clock | Buffered and synchronizable; typical backup time 6 weeks |
| Front / Rear Protection | IP65 / IP20 |
| Operating Temperature | 0 to 50 °C upright; 0 to 40 °C at up to 35° inclination |
Frequently Asked Questions
Which engineering project is required for 6AV6648-0AF11-3AX0?
Use the matching WinCC flexible SMART project created for the SMART 1000 IE V3 hardware generation.
Which PLC connections can be used with 6AV6648-0AF11-3AX0?
The panel can communicate through its Ethernet port or isolated RS422/485 interface with the specified supported controllers.
What should be backed up before replacing 6AV6648-0AF11-3AX0?
Save the HMI project, recipes, communication parameters, Ethernet addressing and runtime settings.
What power source is required for 6AV6648-0AF11-3AX0?
Provide a 24 V DC supply that remains within the permitted 19.2 to 28.8 V range.
Can a USB device be connected to 6AV6648-0AF11-3AX0?
The USB 2.0 host port can supply a connected device up to the specified 500 mA limit.
What environmental check matters when mounting 6AV6648-0AF11-3AX0?
Verify the panel orientation, inclination, temperature, sealing and rear ventilation conditions.
What should be tested after restoring 6AV6648-0AF11-3AX0?
Check touch calibration, every PLC connection, alarms, recipes, time settings and project screens.
Compatibility & Ordering Notes
Compatibility Checklist
- Confirm the project targets the SMART 1000 IE V3 hardware generation and matching runtime environment.
- Match the Ethernet or RS422/485 driver and wiring to the installed PLC connection.
- Restore the project, communication parameters, recipes, clock settings and touch calibration before production use.