- Use the S31 arrangement for throughfeed and the S32 version where an infeed connection is required.
- Match the terminal base to the standard DS1-x direct starter.
- Install PE/N terminal blocks before connecting the starter terminal modules.
- Fit the specified caps to exposed power-bus contacts at the end of the load group.
3RA1903-0AB10 ET 200S TM-DS45-S31 Throughfeed Terminal Module
A TM-DS45-S31 terminal base for a standard direct starter, with screw connections and power-bus throughfeed rather than an infeed connection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RA1903-0AB10 |
| Product Type | Motor-starter terminal module |
| Core Function | Mechanical and electrical integration of direct starters |
| Application | ET 200S standard DS1-x starter stations |
Throughfeed arrangement
The S31 terminal module passes the power bus through the starter station.
Standard direct starter
The TM-DS45 base is assigned to the DS1-x standard direct-starter arrangement.
Prepare field wiring
Screw terminals allow prewiring before the starter electronics are fitted.
Product Overview
3RA1903-0AB10 provides the TM-DS45-S31 throughfeed terminal-base arrangement for an ET 200S standard direct starter. The module supports screw-terminal field wiring and passes the power bus onward without providing the supply-line infeed arrangement of the S32 version.
The power-bus rating and the starter-branch rating describe different current paths. The AUX1 conductor passes through without its own terminals, and the open power-bus contacts at the end of a load group require the specified protective caps.
Key Functions
Continue the power bus
The S31 module provides power-bus throughfeed without the S32 infeed connection.
Support prewired starter positions
Screw terminals permit the field wiring to be prepared before fitting the direct starter.
Integrate protective conductors
The terminal-base arrangement can be expanded with the appropriate PE/N terminal block.
Official Specifications
| Rated power-bus operating voltage | 500 V AC |
|---|---|
| Rated insulation voltage | 690 V |
| Rated impulse withstand | 6 kV |
| Power-bus operating current | 40 A for the TM-DS45 arrangement |
| Power-bus frequency | 50/60 Hz |
| Starter-branch current limit | 12 A for the standard DS1-x arrangement |
| Electrical connection | Screw terminals |
| Front and connection-region protection | IP20 at the front; IP00 at the main power-terminal connection region |
| AUX1 conductor arrangement | Throughfeed without terminals |
| Drawing dimensions | 51.9 × 264 × 119 mm overall (W × H × D); module body width 44.9 mm |
| Net weight | 348 g |
Frequently Asked Questions
Can 3RA1903-0AB10 be used as the power-bus infeed terminal module?
The S31 arrangement provides throughfeed rather than the infeed connection of the S32 version.
Which standard motor starter fits the TM-DS45 arrangement of 3RA1903-0AB10?
The terminal module is assigned to the ET 200S DS1-x standard direct starter.
Can I finish field wiring on 3RA1903-0AB10 before fitting the starter?
The screw-terminal base permits prewiring before the starter electronics are installed.
Does the 40 A power-bus rating of 3RA1903-0AB10 also describe its starter branch?
The throughfeed bus is rated at 40 A, while the standard direct-starter branch has a 12 A limit.
Does 3RA1903-0AB10 provide dedicated terminals for AUX1?
The AUX1 conductor is fed through without terminals.
What protection is needed when 3RA1903-0AB10 is the last terminal module in a load group?
Seal the open power-bus contacts with the specified protective caps before commissioning.
When should I install the PE/N terminal block for 3RA1903-0AB10?
Install the PE/N terminal block before connecting the motor-starter terminal modules.