Overview
Place of Origin: |
Sweden |
Brand Name: |
ABB |
Model Number: |
DO810 3BSE008510R1 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Product Name: |
Digital Output Module |
|
Model: |
DO810 3BSE008510R1 |
|
Dimensions: |
12 x 10.5 x 4.5 cm |
|
Weight: |
0.16 kg |
|
Signal Specification: |
24 V DC (12–32 V DC), 0.5 A |
|
Number of Channels: |
16 |
|
Signal Type: |
Current sourcing, current limiting |
|
HART: |
No |
|
SOE: |
No |
|
Redundancy: |
No |
|
High Integrity: |
No |
|
Intrinsic Safety: |
No |
|
Mechanics: |
S800 |
|
Isolation: |
Groupwise isolated from ground |
|
Output Load: |
< 0.4 Ω |
|
Current Limiting: |
Short-circuit proof current-limited output |
|
Maximum Field Cable Length: |
600 meters (656 yards) |
|
Rated Insulation Voltage: |
50 V |
|
Dielectric Test Voltage: |
500 V AC |
|
Power Dissipation: |
Typ. 2.1 W |
|
Current Consumption +5 V Modulebus: |
80 mA |
Description
This DO810 3BSE008510R1 has 16 digital outputs. The output voltage range is 10 to 30 volt and the maximum continuous output current is 0.5 A. The outputs are protected against short circuits, over voltage and over temperature. The outputs are divided into two individually isolated groups with eight output channels and one voltage supervision input in each group. Each output channel consists of a short circuit and over temperature protected high side driver, EMC protection components, inductive load suppression, output state indication LED and optical isolation barrier.
The process voltage supervision input give channel error signals if the voltage disappears. The error signal can be read through the ModuleBus. The outputs are current limited and protected against over temperature. If the outputs are overloaded the output current will be limited.
Environment and certification
|
CE Mark: |
Yes |
|
Electrical Safety: |
EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201 |
|
Hazardous Location: |
C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
|
Marine Certification: |
ABS, BV, DNV, LR |
|
Operating Temperature: |
0 to +55 °C (+32 to +131 °F), approvals issued for +5 to +55 °C |
|
Storage Temperature: |
-40 to +70 °C (-40 to +158 °F) |
|
Pollution Degree: |
Degree 2, IEC 60664-1 |
|
Corrosion Protection: |
ISA-S71.04: G3 |
|
Relative Humidity: |
5 to 95 %, non-condensing |
|
Max Ambient Temperature: |
55 °C (131 °F), vertical mounting in compact MTU 40 °C (104 °F) |
|
Protection Class: |
IP20 according to IEC 60529 |
|
Mechanical Operating Conditions: |
IEC/EN 61131-2 |
|
EMC: |
EN 61000-6-4, EN 61000-6-2 |
|
Overvoltage Categories: |
IEC/EN 60664-1, EN 50178 |
|
Equipment Class: |
Class I according to IEC 61140 (earth protected) |
|
RoHS Compliance: |
EU RoHS, UAE RoHS, CN RoHS |
|
WEEE Compliance: |
DIRECTIVE/2012/19/EU |
Applications
Fine Chemical and Pharmaceutical Plants:
Used to control hundreds of solenoid valves and mixer contactors. The hot-swappable nature of the S800 I/O ensures replacement of damaged modules without downtime, maintaining the stability of long-cycle chemical production.
Large Food and Beverage Processing Plants:
Drives cylinder switches and inkjet printer trigger signals on high-speed bottling and packaging lines. Its high-density 16-channel design significantly reduces the size of the distributed I/O box.
Water Treatment and Environmental Protection Facilities Plants:
Collects commands distributed across various pump stations to drive pump start/stop and control dosing pump flow. Its stable EMC performance adapts to the electromagnetic environment of frequent starts of high-power equipment.
Paper and Textile Plants:
Controls various pneumatic actuators and nozzles on the production line.
Compatibility
Use with MTU: TU810, TU812, TU814, TU830
Keying code: AA
Diagnostics
Front LED’s: F(ault), R(un), W(arning), O(SP), Channel 1-16 Status
Supervision: Process voltage, 1 per group
Status indication of supervision : Module Error, Module Warning, Channel error
Features and benefits
16 channels for 24 V d.c. current sourcing outputs
2 isolated groups of 8 channels with process voltage supervision
Output status indicators
OSP sets outputs to predetermined state upon error detection
Short-circuit protection to ground and 30 V
Over-voltage and over-temperature protection
FAQ
Q1: Can the DO810 3BSE008510R1 be connected to an AC 220V load?
A: Absolutely not. Connecting to AC power will instantly burn out the internal power transistor. An intermediate relay must be used for conversion.
Q2: What is the difference between DO810 3BSE008510R1 and the DO801?
A: The DO810 is an earlier model, while the DO801 is its optimized replacement. Both are pin-compatible, but in the 800xA system, you need to confirm if the library file version supports it.
Q3: Does DO810 3BSE008510R1 support "Fail-safe" settings?
A: Yes. In the event of a communication interruption, the output can be set to "Hold" or "Reset".
Q4: Why is my DO810 3BSE008510R1 indicator light on, but there is no external voltage?
A: The most common reason is that no external L+ power supply is connected to the socket. The DO810 is only an internal switch and does not have its own power supply.
Q5: What is its maximum total output current about DO810 3BSE008510R1?
A: Due to module heat dissipation limitations, the total current should not exceed 5A-8A when all 16 channels are open.