Siemens 6ES7322-1HF01-0AA0 SIMATIC S7-300 SM 322 Relay Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a compatible S7-300 station position and the required 20-pin front connector.
- Keep switched loads within the 2 A contact rating and 5 mA minimum load.
- Use the applicable inductive, resistive or lamp switching-frequency limit.
- Provide external protection because output short-circuit protection is absent.
- Do not parallel outputs to increase the current rating.
- Account for contact life at the actual load voltage and switching duty.
6ES7322-1HF01-0AA0 SIMATIC S7-300 SM 322 Relay Output Module
An isolated eight-relay output module for 24 V DC or 230 V AC loads, with 2 A rated switching current, a 20-pin front connector and channel-status LEDs.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7322-1HF01-0AA0 |
| Product Type | Relay digital output module |
| Core Function | Switches external field loads |
| Application | Compatible SIMATIC S7-300 stations |
Relay switching
The contacts switch both the specified DC and AC loads.
Grouped isolation
The outputs are isolated in groups of two channels.
External protection planning
Short-circuit protection is not integrated into the module.
Product Overview
6ES7322-1HF01-0AA0 provides eight relay outputs for an S7-300 station requiring isolated field-load switching.
Green output LEDs show the channel states, while the relay contact limits, switching frequency and operating-life figures determine the suitable load duty.
Key Functions
Switch AC or DC loads with relay contacts
The outputs provide the specified 2 A switching capability at 24 V DC or 230 V AC.
Separate the field-load groups
Channels are isolated in groups of two, with optocoupler separation from the backplane bus.
Indicate output states locally
Green LEDs indicate the digital-output states, while diagnostic alarms and dedicated wire-break or short-circuit diagnostics are not provided.
Official Specifications
| Output Channels | 8 relay outputs |
|---|---|
| Rated Switching Capacity | 2 A at 24 V DC or 230 V AC |
| Minimum Load Current | 5 mA |
| Relay Supply Voltage | 24 V DC |
| Maximum Supply Current | 160 mA from L+; 40 mA from the 5 V backplane bus |
| Typical Power Loss | 3.2 W |
| Resistive and Lamp Switching Frequency | 2 Hz maximum |
| Inductive Switching Frequency | 0.5 Hz maximum |
| Maximum Mechanical Switching Frequency | 10 Hz |
| Contact Operating Life at 2 A | 100,000 cycles at 230 V AC; 200,000 at 120 V AC; 300,000 at 24 V DC |
| Maximum Thermal Continuous Current | 3 A |
| Maximum Lamp Load | 50 W |
| Isolation Arrangement | Groups of two channels; optocoupler separation from the backplane |
| Insulation Test Voltage | 1,500 V AC |
| Maximum Cable Length | 1,000 m shielded; 600 m unshielded |
| Front Connector | 20-pin |
| Overall Dimensions | 40 × 125 × 120 mm (W × H × D) |
| Approximate Weight | 190 g |
Frequently Asked Questions
Can I switch both 24 V DC and 230 V AC loads with 6ES7322-1HF01-0AA0?
The relay outputs are rated for 2 A at either 24 V DC or 230 V AC.
Can I parallel two outputs on 6ES7322-1HF01-0AA0 to increase the permissible load current?
Parallel switching for current uprating is not permitted.
Can outputs on 6ES7322-1HF01-0AA0 be paralleled for redundant control of one load?
Parallel switching for redundant control of a load is permitted.
Does 6ES7322-1HF01-0AA0 protect its relay outputs against a load short circuit?
The module has no integrated output short-circuit protection.
Is the 3 A thermal rating of 6ES7322-1HF01-0AA0 the normal switching-current limit?
The rated switching current is 2 A, while 3 A is the separate thermal continuous-current limit.
How often can 6ES7322-1HF01-0AA0 switch an inductive load?
The maximum switching frequency for an inductive load is 0.5 Hz.
Will 6ES7322-1HF01-0AA0 send a diagnostic alarm when a relay load wire breaks?
The module provides neither wire-break diagnostics nor diagnostic alarms.