Siemens 6ES7134-4NB51-0AB0 SIMATIC ET 200S 2AI RTD High Feature Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Parameterize the exact RTD characteristic or resistance range for each channel.
- Match the two-, three- or four-wire terminal arrangement to the selected sensor connection.
- Include compensation and diagnostic conversion times when calculating the measurement update rate.
- Use shielded cable within the 200 m limit and select the appropriate 50/60 Hz suppression setting.
6ES7134-4NB51-0AB0 SIMATIC ET 200S 2AI RTD High Feature Module
Two-channel RTD input with 2-, 3- or 4-wire sensor connections, line resistance compensation and configurable digital smoothing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7134-4NB51-0AB0 |
| Product Type | Resistance temperature input module |
| Core Function | Acquisition of RTD and resistance measurements |
| Application | Temperature monitoring in distributed ET 200S stations |
Multiple resistance sensors
The module supports Pt, Ni and Cu RTDs plus 150, 300, 600 and 3,000 Ω resistance ranges.
Lead resistance handling
Two-, three- and four-wire connections are supported, with internal line resistance compensation for the three-wire method.
Measurement quality and diagnostics
50/60 Hz suppression, four smoothing settings and wire-break or range diagnostics support stable temperature acquisition.
Product Overview
6ES7134-4NB51-0AB0 acquires two RTD or resistance signals in an ET 200S station using integrating Sigma-Delta conversion.
Supported Pt, Ni and Cu sensors can use two-, three- or four-wire connections, with line resistance compensation for three-wire measurements and channel diagnostics for maintenance.
Key Functions
Multiple resistance sensors
The module supports Pt, Ni and Cu RTDs plus 150, 300, 600 and 3,000 Ω resistance ranges.
Lead resistance handling
Two-, three- and four-wire connections are supported, with internal line resistance compensation for the three-wire method.
Measurement quality and diagnostics
50/60 Hz suppression, four smoothing settings and wire-break or range diagnostics support stable temperature acquisition.
Official Specifications
| Analog input channels | 2 |
|---|---|
| Sensor connections | 2-, 3- or 4-wire; 3-wire line compensation |
| RTD characteristics | Pt100/200/500/1000, Ni100/120/200/500/1000 and Cu10 |
| Resistance ranges | 0–150, 0–300, 0–600 and 0–3,000 Ω |
| RTD resolution | 15 bits plus sign |
| Measurement method | Integrating Sigma-Delta |
| Typical measurement current | 1.25 mA |
| Integration time | 16.7 or 20 ms |
| Interference suppression | 50 or 60 Hz |
| Basic conversion time per channel | 50 or 60 ms |
| Additional wire-break test time | 5 ms per channel |
| Additional 3-wire compensation time | 50 or 60 ms per channel |
| Smoothing factors | 1, 4, 32 or 64 × cycle time |
| Address space | 4 bytes |
| Load supply | 24 V DC from power module; maximum 30 mA without load |
| Typical power loss | 0.6 W |
| Maximum shielded cable length | 200 m |
| Diagnostics | Wire break, group fault and overflow/underflow; SF LED |
| Dimensions (W × H × D) | 15 × 81 × 52 mm |
| Weight | Approximately 40 g |
Frequently Asked Questions
Can 6ES7134-4NB51-0AB0 accept a Pt1000 sensor?
Pt1000 is supported together with the listed Pt, Ni and Cu resistance thermometer characteristics.
Which wiring method gives line resistance compensation on 6ES7134-4NB51-0AB0?
The three-wire connection provides internal compensation of the line resistances.
Can 6ES7134-4NB51-0AB0 measure a 0–3,000 Ω resistance signal?
A 0 to 3,000 Ω input range is available in addition to the lower resistance ranges.
Why does enabling wire-break diagnostics lengthen the cycle on 6ES7134-4NB51-0AB0?
The wire-break test adds 5 ms to the conversion time for each active channel.
How can I reduce 50 Hz interference on 6ES7134-4NB51-0AB0?
Select the 50 Hz suppression setting and use the appropriate shielded sensor cable arrangement.
Why does strong smoothing make 6ES7134-4NB51-0AB0 respond more slowly?
The high smoothing setting uses 64 times the cycle time, increasing the time needed for a changed measurement to settle.
Are the two measurement channels on 6ES7134-4NB51-0AB0 isolated from each other?
The channels are not isolated from one another, although they are isolated from the backplane and load supply.