Siemens 6ES7322-1FH00-0AA0 SIMATIC S7-300 SM 322 AC Digital Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the AC output wiring and provide the correct 120/230 V load source.
- Budget channel and group currents for both cabinet temperature and mounting direction.
- Use the specified group fuses and coordinate the circuit with the minimum 40 A fuse-clearing current and maximum 300 ms response time.
- Keep any redundant output connection within one group and do not parallel outputs to increase current capacity.
6ES7322-1FH00-0AA0 SIMATIC S7-300 SM 322 AC Digital Output Module
Sixteen 120/230 V AC outputs with 1 A channel rating, eight-channel isolation groups and group fuse protection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7322-1FH00-0AA0 |
| Product Type | AC digital output module |
| Core Function | Switching of AC field loads from the PLC output image |
| Application | AC solenoid, contactor and indication circuits in S7-300 systems |
AC load switching
The output stage supports nominal 120/230 V AC loads with a rated channel current of 1 A up to 40 °C.
Eight-channel protection groups
Each group of eight outputs has galvanic isolation and an 8 A fuse, requiring a group current budget below the sum of all individual channel ratings.
Local fault and signal indication
Output status and fuse/group-fault indicators support cabinet service, while diagnostic interrupts are not provided.
Product Overview
6ES7322-1FH00-0AA0 provides sixteen AC digital outputs for SIMATIC S7-300 control systems, with outputs isolated and fused in groups of eight.
The output circuits switch AC solenoids, actuators, motor starters and signal lamps, subject to the channel current, group current and temperature limits.
Key Functions
AC load switching
The output stage supports nominal 120/230 V AC loads with a rated channel current of 1 A up to 40 °C.
Eight-channel protection groups
Each group of eight outputs has galvanic isolation and an 8 A fuse, requiring a group current budget below the sum of all individual channel ratings.
Local fault and signal indication
Output status and fuse/group-fault indicators support cabinet service, while diagnostic interrupts are not provided.
Official Specifications
| Digital outputs | 16 |
|---|---|
| Nominal load voltage | 120/230 V AC |
| Permissible load voltage | 79–264 V AC |
| Channel current at 0–40 °C | Maximum 1 A |
| Channel current at 40–60 °C | Maximum 0.5 A |
| Maximum current per group | 4 A up to 40 °C horizontal; 2 A up to 60 °C horizontal or 40 °C vertical |
| Minimum load current | 10 mA |
| Maximum off-state residual current | 2 mA |
| Maximum lamp load | 50 W |
| Group fuse | 8 A, 250 V, quick-acting |
| Maximum resistive-load switching | 10 Hz |
| Maximum inductive-load switching | 0.5 Hz |
| Output isolation | Groups of 8; optocoupler isolation from backplane |
| Maximum backplane current | 200 mA at 5 V DC |
| Typical power loss | 8.6 W |
| Maximum field cable length | 1,000 m shielded; 600 m unshielded |
| Field wiring connection | 20-pin front connector |
| Dimensions (W × H × D) | 40 × 125 × 120 mm |
| Weight | Approximately 275 g |
| Isolation test voltage | 4,000 V DC |
Frequently Asked Questions
Can every output on 6ES7322-1FH00-0AA0 carry 1 A at the same time?
Each eight-channel group is limited to 4 A up to 40 °C horizontally and 2 A up to 60 °C horizontally or 40 °C vertically.
Can a channel on 6ES7322-1FH00-0AA0 continue switching 1 A at 55 °C?
Above 40 °C the permissible channel current is reduced to a maximum of 0.5 A.
Can two outputs on 6ES7322-1FH00-0AA0 be wired for redundant switching of one load?
Redundant load control is permitted only between outputs in the same group and does not allow increasing the load current rating.
Which spare fuse should I stock for 6ES7322-1FH00-0AA0?
Use an 8 A, 250 V quick-acting fuse for the output group.
Will a very small AC load switch correctly on 6ES7322-1FH00-0AA0?
Allow for the 10 mA minimum load current and up to 2 mA of residual current when the output is off.
Does 6ES7322-1FH00-0AA0 raise a diagnostic interrupt when a group fuse blows?
The module provides fuse-related diagnostics and local indication but does not generate a diagnostic alarm.
Which front connector is required for 6ES7322-1FH00-0AA0?
The field wiring uses a 20-pin S7-300 front connector.