- Overview
- Specifications
- Description
- Environment and certification
- Applications
- Features and benefits
- FAQ
- Recommended Products
Overview
Place of Origin: |
Sweden |
Brand Name: |
ABB |
Model Number: |
PM860AK01 3BSE066495R1 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Model |
PM860AK01 3BSE066495R1 |
|
Dimensions |
12 x 19 x 13.5 cm |
|
Weight |
0.92 kg |
|
Redundancy |
No |
|
High Integrity |
No |
|
Clock Frequency |
48 MHz |
|
Performance (1000 boolean operations) |
0.23 ms |
|
Performance |
0.23 ms |
|
Memory |
16 MB (from 800xA 5.1 FP4) |
|
RAM available for application |
10.346 MB (from 800xA 5.1 FP4) |
|
Flash memory for storage |
Yes |
|
Processor type |
MPC860 |
|
Switch over time in redundant configuration |
NA |
|
Applications per controller |
32 |
|
Programs per application |
64 |
|
Diagrams per application |
128 |
|
Tasks per controller |
32 |
|
Number of cycle times |
32 |
|
Cycle time per application program |
Down to 1 ms |
|
Firmware storage (Flash PROM) |
2 MB |
|
Power supply |
24 V DC (19.2–30 V DC) |
|
Power consumption (typ/max) |
180 / 300 mA |
|
Power dissipation |
4.32 W (7.2 W max) |
|
Redundant power supply status input |
Yes |
|
Built-in backup battery |
Lithium, 3.6 V |
|
Clock synchronization |
1 ms (CNCP protocol between AC 800M controllers) |
|
Event queue per OPC client |
Up to 3000 events |
|
Transmission speed to OPC server |
36–86 events/sec, 113–143 data messages/sec |
|
CEX bus communication modules |
12 single CEX bus modules |
|
CEX bus supply current |
Max 2.4 A |
|
I/O clusters (non-redundant CPU) |
1 electrical + 7 optical |
|
I/O clusters (redundant CPU) |
NA |
|
I/O capacity (Modulebus) |
Max 96 I/O modules |
|
Modulebus scan rate |
0–100 ms |
|
Electrical Modulebus supply current (24 V) |
Max 1.0 A |
|
Electrical Modulebus supply current (5 V) |
Max 1.5 A |
|
Ethernet channels |
2 |
|
Ethernet interface |
Ethernet IEEE 802.3, 10 Mbit/s, RJ-45 |
|
Control Network protocol |
MMS / IAC |
|
Recommended Control Network backbone |
100 Mbit/s switched Ethernet |
|
Real-time clock stability |
100 ppm (~1 hour/year) |
|
RS-232C interfaces |
2 (COM3 service / COM4 general) |
|
COM3 (RS-232C) |
75–19200 baud, RJ-45, non-isolated, RTS-CTS supported |
|
COM4 (RS-232C) |
9600 baud, RJ-45, opto-isolated, no RTS-CTS |
Description
PM860AK01 3BSE066495R1 is a controller, featuring CPU board with microprocessor, RAM, real-time clock, LED indicators, INIT button and CompactFlash interface. Base plate includes dual RJ45 Ethernet (CN1/CN2) and COM3/COM4 serial ports, DIN rail slide-lock mounting, and unique Ethernet hardware ID on TP830.
Environment and certification
|
Parameter |
Value |
|
Operating Temperature |
0 to +55 °C (+32 to +131 °F) |
|
Storage Temperature |
-40 to +70 °C (-40 to +158 °F) |
|
Temperature Change Rate |
3 °C/min (IEC/EN 61131-2) |
|
Pollution Degree |
Degree 2 (IEC/EN 61131-2) |
|
Corrosion Protection |
G3 (ISA 71.04 compliant) |
|
Relative Humidity |
5 to 95%, non-condensing |
|
Noise Emission |
< 55 dB(A) |
|
Vibration (10–50 Hz) |
0.0375 mm amplitude |
|
Vibration (50–150 Hz) |
0.5 g acceleration |
|
Vibration (5–500 Hz) |
0.2 g acceleration |
|
Rated Isolation Voltage |
500 V AC |
|
Dielectric Test Voltage |
50 V |
|
Protection Class |
IP20 (EN 60529, IEC 529) |
|
Altitude Rating |
Up to 2000 m (IEC/EN 61131-2) |
|
EMC Emission & Immunity |
EN 61000-6-4 / EN 61000-6-2 |
|
Environmental Classification |
Industrial |
|
CE Mark |
Yes |
|
Electrical Safety Standards |
EN 50178, IEC 61131-2, UL 61010-1, UL 61010-2-201 |
|
Hazardous Location Approval |
cULus Class 1, Zone 2; AEx nA IIC T4; Ex nA IIC T4 Gc X |
|
Marine Certifications |
ABS, BV, DNV-GL, LR |
|
TÜV Approval |
No |
|
RoHS Compliance |
EU RoHS, UAE RoHS, CN RoHS |
|
WEEE Compliance |
Directive 2012/19/EU |
Applications
Precision pulp mills: Logic and timing control for the pulping process.
Medium-sized chemical plants: Monitoring the temperature and pressure of reactors to ensure production safety.
Waste-to-energy plants: Automated control of incinerators and flue gas treatment systems.
Water treatment plants: Variable frequency drive scheduling of pump sets and aggregation of water quality monitoring data.
Ore processing plants: Distributed control of conveyor systems and mineral processing procedures.
Features and benefits
Reliability and simple fault diagnosis procedures
Modularity, allowing for step-by-step expansion
IP20 Class protection without the requirement for enclosures
The controller can be configured with 800xA control builder
The controller has full EMC certification
Hardware based on standards for optimum communication connectivity (Ethernet, PROFIBUS DP, etc.)
FAQ
Q: What is the PM860AK01 3BSE066495R1?
A: It is a controller.
Q: What exactly does the PM860AK01 3BSE066495R1 "kit" include?
A: It includes the PM860A processor module, the TP830 baseboard, and necessary wiring terminals, forming a complete installation unit.
Q: How many signals can 8 MB of memory handle in the PM860AK01 3BSE066495R1?
A: It is generally recommended to handle 500 to 1000 I/O points, depending on the complexity of the program logic.
Q: If the PM860AK01 3BSE066495R1 controller fails, is rewiring required when replacing the module?
A: No. The wiring is fixed on the TP830 baseboard. Simply remove the old processor and insert the new module; the program can be synchronized from the redundant terminal or the Flash card.
Q: Does the PM860AK01 3BSE066495R1 support the Modbus protocol?
A: Yes. The processor's built-in serial port can be used directly for Modbus RTU communication; if Modbus TCP is required, it can be achieved through the built-in Ethernet port.