WEINVIEW TK8071iP 7-inch Ethernet Touchscreen HMI
Manufacturer: WEINVIEW
Condition: Brand New
Lead Time: In Stock
Origin: China
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the original TK8071iP project target rather than a later TK8071iP1 hardware target.
- Assign RS-232 wiring to COM1 and RS-485 wiring to COM2.
- Prepare a 192 × 138 mm cutout and allow space behind the 34 mm-deep housing for wiring.
- For the S7-300 MPI driver, use the supported baud rate and matching PLC station address rather than 19.2 kbit/s.
TK8071iP 7-inch Ethernet Touchscreen HMI
A 7-inch operator panel combining an ARM RISC processor with Ethernet, RS-232 and RS-485 communication.
At a Glance
| Brand | WEINVIEW |
|---|---|
| Model | TK8071iP |
| Product Type | Touchscreen operator panel |
| Core Function | Machine visualization and operator commands |
| Application | EasyBuilder Pro HMI projects |
Ethernet-connected visualization
One 10/100 Base-T port supports an Ethernet connection alongside the panel’s serial communication channels.
Separate serial channels
COM1 provides RS-232 and COM2 provides RS-485 two-wire or four-wire communication for the configured PLC driver.
Compact cabinet integration
The 200.4 × 146.5 × 34 mm enclosure fits a 192 × 138 mm opening with front-panel protection for the operator interface.
Product Overview
TK8071iP provides local machine visualization with serial and Ethernet communication in the TK panel family.
An ARM RISC processor runs the operator application, while the compact panel housing fits a 192 × 138 mm cabinet opening and provides a NEMA 4/IP65-compliant front panel.
Key Functions
Ethernet-connected visualization
One 10/100 Base-T port supports an Ethernet connection alongside the panel’s serial communication channels.
Separate serial channels
COM1 provides RS-232 and COM2 provides RS-485 two-wire or four-wire communication for the configured PLC driver.
Compact cabinet integration
The 200.4 × 146.5 × 34 mm enclosure fits a 192 × 138 mm opening with front-panel protection for the operator interface.
Official Specifications
| Screen size | 7 inches |
|---|---|
| Display colors | 16 million |
| Processor | ARM RISC, 528 MHz |
| Ethernet interface | 1 × 10/100 Base-T |
| Serial interfaces | COM1: RS-232; COM2: RS-485 two-wire or four-wire |
| Supply voltage | 10.5–28 V DC |
| Current consumption | 550 mA at 12 V DC; 300 mA at 24 V DC |
| Overall dimensions | 200.4 × 146.5 × 34 mm |
| Panel cutout | 192 × 138 mm |
| Front-panel protection | NEMA 4 / IP65 compliant |
Frequently Asked Questions
Which engineering software should I use for TK8071iP?
Use EasyBuilder Pro with the matching panel target, starting from the V5.07.02 version identified for this hardware.
Can TK8071iP connect to a PLC through Ethernet?
The panel includes one 10/100 Base-T Ethernet connection for a supported configured PLC driver.
How do I allocate serial wiring on TK8071iP?
Use COM1 for RS-232 communication and COM2 for RS-485 two-wire or four-wire communication.
Will TK8071iP fit a 192 × 138 mm panel opening?
The specified cabinet cutout is 192 × 138 mm.
Can I supply TK8071iP from either 12 V or 24 V DC?
Both nominal supplies fall within the permitted 10.5–28 V DC input range.
Should I configure 19.2 kbit/s MPI communication for TK8071iP?
The Siemens S7-300 MPI driver does not support 19.2 kbit/s on this panel, so use a supported setting such as 187.5 kbit/s.
Does the IP65 protection of TK8071iP cover its rear connectors?
The NEMA 4/IP65 compliance applies to the front panel.