Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
siemens vxg41 1501 acvatix three port valve dn 15 pn 16-0

For SIEMENS

Home >  Products >  For SIEMENS

Siemens VXG41.1501 Acvatix Three-Port Valve DN 15, PN 16

Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months

  • Overview
  • Hot Selling Models
  • Recommended Products
Overview
SIEMENS Acvatix VXG41

VXG41.1501 Acvatix Three-Port Valve DN 15, PN 16

A DN 15 bronze three-port valve with a 4.0 m³/h nominal flow coefficient, tight bypass and DVGW-tested drinking-water variant construction.

At a Glance

Brand Siemens
Model VXG41.1501
Product Type Externally threaded three-port seat valve
Core Function Modulates mixing or diverting water flow
Application Heating, cooling and drinking-water control circuits

DN 15 flow control

The nominal flow coefficient is 4.0 m³/h.

Tight bypass design

The .01 variant provides a tight bypass with the specified actuator combination.

Actuator selection

Select SAX, SKD or SKB actuation to suit the circuit and leakage requirements.

Product Overview

VXG41.1501 is a DN 15 Acvatix three-port seat valve for modulating water flow in mixing and diverting circuits.

The bronze body uses externally threaded flat-sealing connections, a stainless-steel seat, plug and stem, and a 20 mm nominal stroke; the .01 construction is intended for drinking-water applications within its specified temperature limit.

Ordering focus: Match the DN 15 connection, 4.0 m³/h flow coefficient, mixing or diverting arrangement and actuator force, including the tight-bypass requirement.
Key Functions

Mixing and diverting flow paths

Mixing directs flow from ports A and B to AB, while diverting directs flow from AB to A and B; mixing is the preferred application.

Modulating valve characteristic

The throughport is linear over the first 30% of stroke and equal-percentage over the remaining range, while the bypass characteristic is linear.

Tight-bypass water service

Use an SKD or SKB actuator to meet the specified bypass leakage rate for the .01 variant, and keep DVGW drinking-water service within 90 °C.

Official Specifications
Nominal size DN 15
Nominal pressure class PN 16 to ISO 7268
Nominal flow coefficient kvs 4.0 m³/h
Rangeability Sv Greater than 50
Nominal stroke 20 mm
Throughport flow characteristic Linear at 0–30% stroke; equal-percentage at 30–100%, ngl = 3
Bypass flow characteristic Linear over 0–100% stroke
Throughport leakage 0–0.02% of kvs
Tight-bypass leakage 0–0.02% of kvs with SKD or SKB actuator
Permissible water-medium temperature −25 to +150 °C; subject to actuator and application limits
Maximum DVGW drinking-water application temperature 90 °C
Valve body material Bronze CuSn5Zn5Pb2
Seat, plug and stem material Stainless steel
Stem gland construction Dezincification-free brass with silicon-free EPDM O-rings
External connection thread G 1 B, flat-sealing, to ISO 228-1
Face-to-face length L1 100 mm
Branch offset L2 and L3 50 mm each
Pipe centre to actuator installation edge H1 26 mm
Closed-valve height H2 122.5 mm
Valve weight 1.30 kg
Frequently Asked Questions

Which flow coefficient should be used when sizing VXG41.1501?

The nominal kvs value is 4.0 m³/h for the DN 15 valve.

How are the ports of VXG41.1501 arranged for mixing and diverting?

Mixing combines A and B into AB, while diverting splits flow from AB toward A and B.

Which actuator families maintain the tight bypass of VXG41.1501?

Use an SKD or SKB actuator to meet the specified tight-bypass leakage rate.

What temperature limit applies to VXG41.1501 in DVGW drinking-water service?

The maximum medium temperature for the DVGW drinking-water application is 90 °C.

Does VXG41.1501 require a stem heater for sub-zero media?

Media below 0 °C require the ASZ6.6 electric stem heater, rated 24 V AC and 30 W.

Are the actuator and union fittings included with VXG41.1501?

Valves, actuators and accessories are supplied separately, and DVGW-approved union fittings must be obtained separately for the drinking-water installation.

Which replacement stem gland belongs to VXG41.1501?

The replacement stem sealing gland order number is 74 284 0047 0.

Compatibility & Ordering Notes
Before ordering VXG41.1501: Choose the valve, actuator and union fittings as separate items, maintain the intended flow direction and select DVGW-approved fittings where the drinking-water installation requires them.

Compatibility Checklist for VXG41.1501

  • Size the circuit using DN 15 and kvs 4.0 m³/h.
  • Select an SKD or SKB actuator when the tight-bypass leakage specification is required.
  • Keep drinking-water service within 90 °C and observe the pressure-temperature limits.
  • Provide an upstream strainer and avoid cavitation.
  • Use ASZ6.6 stem heating for media below 0 °C.
  • Allow service clearance and use stem gland 74 284 0047 0 for this .01 variant.
Hot Selling Models
6ES7212-1BA00-0XB0
3005073
6SN1118-0DG21-0AA0
TRZ24VDC1CO16A
NHI11-FAZ
AITB6BB2C 2668700000
Murr Electronics 276344
RMG12.2-NN
IC693BEM331E
3RV2011-1GA25 3
SSM-BG43
3RV2011-1HA25
3RT1046-1AP04 3RH1921-1HA22 3RT1936-1CD00
LH-1V
9600H1

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.