Siemens SITOP PSU100M 6EP1337-3BA00 24 V DC 40 A Power Supply
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Set the line-voltage jumper for the installed network before energizing the supply.
- Coordinate the upstream protective device with the documented input current and inrush-energy values.
- Use an EN 60715 35 × 15 mm DIN rail and maintain 50 mm clear space above and below the enclosure.
- Apply the specified output derating when the ambient temperature exceeds 60 °C.
- Select SITOP buffer or signaling accessories only when their electrical function matches the required control-power architecture.
- Use matched wiring and protection when operating up to two supplies in parallel for increased output power.
6EP1337-3BA00 24 V DC 40 A Power Supply
A stabilized industrial power supply with selectable 120/230 V AC input and an adjustable 24 to 28.8 V DC output.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6EP1337-3BA00 |
| Product Type | SITOP PSU100M stabilized power supply |
| Core Function | Stabilized and isolated DC power conversion for industrial control circuits |
| Application | Industrial 24 V DC control-power systems |
Exact Identification
Match the complete article number 6EP1337-3BA00 and the SITOP PSU100M 40 A designation.
Input Selection
Set the wire jumper for the installed 120 V or 230 V AC network before startup.
Protection Planning
Coordinate the branch protection, cabinet ventilation and selectable short-circuit behavior with the control system.
Product Overview
6EP1337-3BA00 is a Siemens SITOP PSU100M stabilized power supply for converting a selectable 120 V or 230 V AC input into an isolated industrial DC control supply.
The output can be adjusted from 24 to 28.8 V DC and supplies 40 A continuously, with short-term power boost and selectable short-circuit behavior for demanding startup and fault conditions.
Natural-convection cooling, DIN-rail mounting, visual status indication and compatibility with SITOP buffer and signaling modules support integration into control cabinets.
Key Functions
High-Current Stabilized Output
The supply delivers a regulated 40 A output with an adjustable voltage range from 24 to 28.8 V DC.
Power Boost and Fault Response
A 120 A boost is available for 25 ms, and the short-circuit response can use an approximately 46 A constant-current characteristic or latching shutdown.
Control-Cabinet Integration
The 240 mm-wide enclosure snaps onto an EN 60715 rail and provides LED indication for normal output, overload and latching shutdown.
Official Specifications
| Input Network | Single-phase AC |
|---|---|
| Rated Input Voltage | 120 V or 230 V AC, selected by a wire jumper |
| Permitted Input Ranges | 85 to 132 V AC or 176 to 264 V AC |
| Line Frequency Range | 47 to 63 Hz |
| Input Current at Rated Voltage | 15 A at 120 V AC; 8 A at 230 V AC |
| Inrush Limitation | 125 A maximum at 25 °C; I²t maximum 26 A²s |
| Power-Failure Buffering | 20 ms minimum at 230 V AC and rated output current |
| Adjustable Output Voltage | 24 to 28.8 V DC |
| Rated Output Current | 40 A |
| Supplied Active Power | 960 W typical |
| Short-Term Overload | 120 A for 25 ms during operation |
| Short-Circuit Characteristic | Approximately 46 A constant current or latching shutdown, selectable |
| Efficiency | 88% typical |
| Power Loss at Rated Load | 131 W typical |
| Output Voltage Quality | 60 mV typical residual ripple, 100 mV maximum ripple and 200 mV maximum voltage peak |
| Dynamic Response | 2 ms for 50-to-100% and 100-to-50% load steps; 5 ms maximum setting time |
| Overvoltage Protection | Output limited below 35 V |
| Electrical Protection | Galvanically isolated SELV/ES1 output, protection class I and IP20 enclosure |
| Ambient Operation | 0 to 70 °C with natural convection; output derating 2.5% per K from 60 to 70 °C |
| Mechanical Installation | 240 × 125 × 125 mm enclosure, 2.9 kg, DIN rail EN 60715 35 × 15 mm, 50 mm clearance above and below |
Frequently Asked Questions
How do I select the input range on 6EP1337-3BA00?
Set the device wire jumper for the available 120 V or 230 V AC supply before energizing the unit.
Can 6EP1337-3BA00 ride through a brief mains interruption?
The power supply provides at least 20 ms of buffering at a 230 V AC input while delivering the rated output current.
What overload capability is available from 6EP1337-3BA00?
The unit can deliver 120 A for 25 ms and can sustain an approximately 46 A short-circuit current under its selectable protection characteristic.
Can I connect two 6EP1337-3BA00 units in parallel?
Up to two power supplies may be connected in parallel when additional output power is required and the installation follows the documented parallel-operation arrangement.
Which mounting space should I reserve for 6EP1337-3BA00?
Install the unit on a 35 × 15 mm DIN rail and keep 50 mm of free space above and below for natural convection.
How can I read the operating state of 6EP1337-3BA00?
A green LED indicates the 24 V output is present, while yellow and red indications identify overload and latching shutdown conditions.
When does temperature derating begin for 6EP1337-3BA00?
Full rated output is available up to 60 °C, after which the current is reduced by 2.5% per kelvin through 70 °C.