Overview
- Match the complete article number and hardware version on the installed device.
- Archive the existing project parameters and label all field connections before replacement.
- Verify the system interface, supply and environmental requirements before commissioning.
SIEMENS SIMATIC S7-400
Siemens SIMATIC S7-400 SM 431 6ES7431-1KF00-0AB0 Analog Input Module
Eight-channel isolated SM 431 analog input module with 13-bit resolution for voltage, current and resistance measurement.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7431-1KF00-0AB0 |
| Product Type | Eight-channel isolated analog input module |
| Core Function | Acquires voltage, current and resistance signals |
| Application | SIMATIC S7-400 automation systems |
Exact Identification
Eight-channel isolated analog input module for the specified Siemens system.
Core Application
SIMATIC S7-400 automation systems.
Configuration Focus
Confirm the full article number, input ranges, channel wiring, integration time, front connector and the STEP 7 hardware configuration.
Product Overview
The SM 431 module provides eight isolated analog input channels for SIMATIC S7-400 systems.
The official data covers selectable voltage and current ranges plus resistance measurement on four channels with 13-bit resolution including sign.
Key Functions
Primary Function
Acquires voltage, current and resistance signals.
System Integration
It occupies an S7-400 central or expansion rack slot and uses the configured analog measuring ranges.
Commissioning Focus
Confirm the full article number, input ranges, channel wiring, integration time, front connector and the STEP 7 hardware configuration.
Official Specifications
| Analog Inputs | 8 |
|---|---|
| Resistance Inputs | 4 |
| Maximum Resolution | 13 bit including sign |
| Voltage Ranges | 1 to 5 V, ±1 V, ±10 V |
| Current Ranges | ±20 mA, 4 to 20 mA |
| Resistance Range | 0 to 600 Ω; usable to 500 Ω |
| Voltage Input Resistance | 200 kΩ |
| Current Input Resistance | 80 Ω |
| Constant Measuring Current | 1.67 mA |
| Shielded Cable Length | 200 m maximum |
| Conversion Time | 23 or 25 ms per channel |
| Integration Time | 16.7 or 20 ms |
| Interference Suppression | 50 / 60 Hz |
| Backplane Current | 350 mA maximum |
| Power Loss | 1.8 W |
| Dimensions | 25 x 290 x 210 mm |
| Weight | 500 g |
Frequently Asked Questions
How many field signals can 6ES7431-1KF00-0AB0 acquire?
It provides eight analog input channels, with four channels available for resistance measurement.
Which signal families suit 6ES7431-1KF00-0AB0?
The configured channel can measure supported voltage, current or resistance ranges.
What resolution is available from 6ES7431-1KF00-0AB0?
The maximum stated resolution is 13 bit including sign.
Can 6ES7431-1KF00-0AB0 read a four-wire resistor?
Yes, the module supports two-, three- and four-wire resistance connections.
What cable practice applies to 6ES7431-1KF00-0AB0?
Use shielded analog cabling and keep the run within the specified 200 m maximum.
How is mains-frequency interference handled by 6ES7431-1KF00-0AB0?
Select the matching 50 Hz or 60 Hz integration and suppression setting.
What should be copied before exchanging 6ES7431-1KF00-0AB0?
Record every channel range, connection type, integration setting and rack slot assignment.