Siemens SIMATIC S7-400 CP 441-2 6ES7441-2AA03-0AE0 Communication Processor
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Record the plug-in interface module fitted to each CP channel.
- Archive the STEP 7 project and any loadable protocol driver before replacement.
- Check cable type, length, termination and character-frame settings for both communication partners.
SIEMENS SIMATIC S7-400
Siemens SIMATIC S7-400 CP 441-2 6ES7441-2AA03-0AE0 Communication Processor
Two-channel CP 441-2 communication processor for serial point-to-point links using plug-in RS 232C, TTY or RS 422/485 interface modules.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7441-2AA03-0AE0 |
| Product Type | Communication processor |
| Core Function | Executes point-to-point data exchange |
| Application | SIMATIC S7-400 automation systems |
Interface Modules
Confirm the two installed physical-interface modules before replacement.
Protocol Selection
Match the configured ASCII, 3964(R), RK512, printer or loadable Modbus driver.
Project Restore
Preserve the STEP 7 hardware configuration, parameters and communication blocks.
Product Overview
The CP 441-2 adds two independent serial point-to-point channels to a SIMATIC S7-400 station.
Physical communication is selected with plug-in TTY, RS 232C or RS 422/485 interface modules, while standard and loadable protocol drivers handle the connected device.
Key Functions
Dual Serial Channels
Provides two configurable point-to-point communication channels in one S7-400 module.
Selectable Electrical Interface
Accepts plug-in TTY, RS 232C or RS 422/485 interface modules for the connected equipment.
Protocol Processing
Supports ASCII, 3964(R), RK512 and printer drivers plus loadable Modbus RTU master or slave operation.
Official Specifications
| Communication Channels | 2 |
|---|---|
| Plug-In Interface Positions | 2 |
| Supported Physical Interfaces | 20 mA TTY, RS 232C, or RS 422/485 |
| Standard Protocol Drivers | ASCII, 3964(R), RK512 and printer |
| Loadable Modbus Roles | RTU master or RTU slave |
| Transmission Rate Range | 300 bit/s to 115.2 kbit/s |
| Maximum TTY Transmission Rate | 19.2 kbit/s |
| RS 232C Cable Length | Up to 10 m |
| RS 422/485 Cable Length | Up to 1,200 m |
| 20 mA TTY Cable Length | Up to 1,000 m |
| Maximum ASCII or 3964 Message Length | 4,096 bytes |
| Maximum RK512 Send Length | 4,096 bytes |
| Maximum RK512 Fetch Length | 450 bytes |
| Diagnostic Interrupt | Configurable |
| Status Indication | TXD, RXD, FAULT, INTF and EXTF LEDs |
| Module Dimensions | 25 × 290 × 210 mm |
| Packaging Dimensions | 30.1 × 23.3 × 3.7 cm |
| Net Weight | 0.952 kg |
Frequently Asked Questions
Which interface modules can I use with 6ES7441-2AA03-0AE0?
The two channels accept plug-in 20 mA TTY, RS 232C or RS 422/485 interface modules.
Can 6ES7441-2AA03-0AE0 run Modbus RTU?
Yes, loadable drivers provide Modbus RTU master or slave operation when the required software and license are installed.
What is the maximum serial rate for 6ES7441-2AA03-0AE0?
The supported range reaches 115.2 kbit/s, while a TTY interface is limited to 19.2 kbit/s.
How far can I run an RS 422/485 cable from 6ES7441-2AA03-0AE0?
The specified maximum distance is 1,200 m when the interface and cable installation meet the stated requirements.
Which project data should I save before replacing 6ES7441-2AA03-0AE0?
Save the STEP 7 hardware configuration, channel parameters, driver selection and the user blocks used for communication.
How do I identify channel faults on 6ES7441-2AA03-0AE0?
Use the TXD, RXD and FAULT indications together with the internal and external fault LEDs and diagnostic information.
What must match on both ports of 6ES7441-2AA03-0AE0?
Each channel must match its interface module, pinout, baud rate, character frame and protocol partner.