Siemens SIMATIC S7-300T 6ES7315-6TH13-0AB0 CPU 315T-2 DP
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Match the TH13 technology CPU rather than a standard S7-300 CPU.
- Use the supported STEP 7 and S7 Technology versions.
- Preserve CPU firmware and integrated technology version compatibility.
- Provide 24 V DC within 20.4 to 28.8 V.
- Use a supported MMC and restore the validated project.
- Back up both PROFIBUS networks, addresses and device assignments.
- Restore all motion technology objects, axes and drive relationships.
Siemens · SIMATIC S7-300T
6ES7315-6TH13-0AB0 CPU 315T-2 DP Technology CPU
Siemens 6ES7315-6TH13-0AB0 is the SIMATIC S7-300T CPU 315T-2 DP technology CPU with 256 KB work memory. It combines standard PLC processing with integrated technology functions and two PROFIBUS interfaces for DP and DP Drive applications.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7315-6TH13-0AB0 |
| Product Type | SIMATIC S7-300T Technology CPU |
| Core Function | Executes PLC logic and integrated motion-control technology functions |
| Application or Compatible Series | SIMATIC S7-300T automation systems with PROFIBUS DP and DP Drive |
Technology CPU Identity
Match the complete TH13 article number, hardware revision, CPU firmware and integrated technology version.
Engineering Baseline
Use the supported STEP 7 and S7 Technology releases and preserve the complete motion and PLC project.
Dual DP Configuration
Record every DP and DP Drive address, device assignment, network parameter and axis relationship.
Product Overview
Siemens 6ES7315-6TH13-0AB0 is the SIMATIC S7-300T CPU 315T-2 DP technology CPU with 256 KB work memory. It combines standard PLC processing with integrated technology functions and two PROFIBUS interfaces for DP and DP Drive applications.
Combines cyclic controller logic with integrated technology and motion functions. Provides one DP interface and one DP Drive interface for automation and drive communication. Uses an MMC for load memory and long-term retention of the configured program.
Key Functions
PLC and Motion Integration
Combines cyclic controller logic with integrated technology and motion functions.
Dual PROFIBUS Interfaces
Provides one DP interface and one DP Drive interface for automation and drive communication.
Memory Card Project Storage
Uses an MMC for load memory and long-term retention of the configured program.
Official Specifications
| Hardware Functional Status | 01 |
|---|---|
| CPU Firmware | V2.7 |
| Integrated Technology Version | V4.1.5 |
| Engineering Requirement | STEP 7 V5.4 SP5 or later and S7 Technology V4.2 |
| Rated Supply Voltage | 24 V DC |
| Permissible Supply Range | 20.4 to 28.8 V DC |
| Recommended External Fuse | At least 2 A |
| Quiescent Current | 250 mA |
| Inrush Current | 2.5 A |
| Typical Power Loss | 6 W |
| Integrated Work Memory | 256 KB |
| Work Memory Expansion | No |
| Maximum MMC Load Memory | 8 MB |
| Data Retention | At least 10 years on the MMC |
| Input Address Area | 1024 bytes |
| Output Address Area | 1024 bytes |
| Local Expansion | One rack with up to 8 signal modules |
| Integrated DP Interfaces | 2, consisting of DP and DP Drive |
| Dimensions | 160 x 125 x 130 mm |
| Approximate Weight | 750 g |
Frequently Asked Questions
Which engineering software is required for 6ES7315-6TH13-0AB0?
Use STEP 7 V5.4 SP5 or later together with S7 Technology V4.2 for the specified firmware generation.
How much work memory does 6ES7315-6TH13-0AB0 provide?
The CPU includes 256 KB of integrated work memory and it cannot be expanded.
Which memory card can store the project for 6ES7315-6TH13-0AB0?
Use a supported SIMATIC MMC with up to 8 MB load memory and restore the validated project backup.
How many PROFIBUS interfaces are integrated in 6ES7315-6TH13-0AB0?
The CPU provides two interfaces configured for DP and DP Drive use.
What supply should I provide for 6ES7315-6TH13-0AB0?
Provide 24 V DC within 20.4 to 28.8 V and fit the required external protection.
Can I replace 6ES7315-6TH13-0AB0 without the original motion project?
No, preserve the PLC program, technology objects, axis data, drive assignments and both PROFIBUS configurations.
What must I compare before changing 6ES7315-6TH13-0AB0 firmware?
Verify the hardware revision, CPU firmware, technology version, STEP 7 release and compatibility of every configured axis and drive.