Siemens SIMATIC ET 200B 6ES7133-0BL00-0XB0 16DI/16DO Electronics Block
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use TB2/DC, TB2-4/DC, TB4/DC or TB4M/DC.
- Keep each eight-output group within its 2 A total-current limit.
- Preserve the station address, baud rate and field wiring during replacement.
6ES7133-0BL00-0XB0 ET 200B-16DI/16DO Electronics Block
Siemens ET 200B electronics block with 16 digital inputs and 16 digital outputs for 24 V DC distributed-I/O applications.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7133-0BL00-0XB0 |
| Product Type | ET 200B-16DI/16DO electronics block |
| Core Function | 16 digital inputs and 16 digital outputs for distributed I/O |
| Compatible Series | SIMATIC ET 200B distributed I/O |
I/O Structure
Sixteen 24 V DC inputs and sixteen transistor outputs in one electronics block.
Output Grouping
Outputs are galvanically isolated in two groups of eight channels.
Terminal Block Match
Designed for the TB2/DC, TB2-4/DC, TB4/DC or TB4M/DC terminal block.
Product Overview
The Siemens 6ES7133-0BL00-0XB0 combines sixteen non-isolated digital inputs with sixteen digital outputs that are isolated in groups of eight. It installs in the ET 200B distributed I/O system and uses a 24 V DC field supply.
Input channels accept mechanical switches and suitable two-wire proximity sensors, while the transistor outputs support resistive, inductive and lamp loads within the specified current and switching limits.
Key Functions
Combined Digital Input and Output
Processes sixteen 24 V DC input signals and controls sixteen 24 V DC output channels from one ET 200B station position.
Grouped Output Isolation
Separates the outputs into two galvanically isolated groups of eight with independent load-voltage monitoring.
Local Status and Diagnostics
LEDs indicate run state, PROFIBUS fault, group diagnostics, load-voltage condition and individual I/O status.
Official Specifications
| PROFIBUS Transmission Rates | 9.6, 19.2, 93.75, 187.5, 500, 1500, 3000, 6000 and 12000 kbaud |
|---|---|
| Maximum Power Dissipation | 5.5 W |
| Combined Block Weight | Approximately 800 g with electronics block and terminal block |
| Overall Dimensions | 235 × 130 × 60 mm with electronics block and terminal block |
| Supply Voltage Range | 24 V DC rated; 18.5–30.2 V permissible; 35 V for less than 0.5 s |
| Internal Logic Current | Typically 85 mA from L5+ |
| Sensor Supply Current | Maximum 1 A from L5+ |
| Inrush Energy Integral | Maximum 0.05 A²s |
| Digital Input Signal Levels | Signal 0: −30 to 5 V; signal 1: 13 to 30 V |
| Digital Input Current | Typically 4 mA at 24 V; minimum 2 mA for signal 1 |
| Input Delay | 3 ms |
| Two-Wire Sensor Quiescent Current | Maximum 1.5 mA |
| Unshielded Sensor Cable Length | Maximum 100 m |
| Output Channel Isolation | Galvanically isolated in two groups of 8 |
| Digital Output Voltage Levels | Signal 0: maximum 2 V idle; signal 1: at least supply voltage minus 3 V |
| Digital Output Current | Signal 0: maximum 1 mA; signal 1: maximum 0.5 A |
| Output Switching Delay | Approximately 20 µs from 0 to 1; maximum 0.5 ms from 1 to 0 |
| Maximum Switching Frequency | 1000 Hz resistive load; 0.5 Hz inductive load; 8 Hz lamp load |
| Maximum Load Current per Group | 2 A |
| Maximum Lamp Load | 5 W |
Frequently Asked Questions
Which terminal blocks can I use with 6ES7133-0BL00-0XB0?
The electronics block accepts TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC terminal blocks.
Can 6ES7133-0BL00-0XB0 connect two-wire proximity sensors?
Two-wire BERO sensors can be connected when their quiescent current does not exceed 1.5 mA.
How much load current can each output of 6ES7133-0BL00-0XB0 switch?
Each active output can carry up to 0.5 A, while the total current in one isolated group must not exceed 2 A.
What should I check before replacing 6ES7133-0BL00-0XB0?
Match the ET 200B terminal block, field wiring, 24 V supplies, PROFIBUS configuration and 235 × 130 × 60 mm assembly space.
Which PROFIBUS rates are available for 6ES7133-0BL00-0XB0?
The module supports 9.6 kbaud through 12 Mbaud, while operation with an IM 308-B is limited to 1.5 Mbaud.
Which indicators help diagnose 6ES7133-0BL00-0XB0?
RUN, BF, DIA, L1+/L2+ and channel-status LEDs indicate supply, bus, group-diagnostic, load-voltage and I/O states.
How long can the field cables be for 6ES7133-0BL00-0XB0?
Unshielded sensor cables and output cables can each be up to 100 m long.