Siemens RWD44U Universal Staged HVAC and Refrigeration Controller
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a 24 V AC SELV supply and the specified safety-isolating transformer arrangement.
- Disconnect controlled outputs before changing the application selection.
- Allow at least 8 mm clearance between terminals and the panel or enclosure.
- Provide the selected DIN-rail, wall or ARG62.21 enclosure mounting arrangement.
RWD44U Universal Staged HVAC and Refrigeration Controller
A standalone controller with universal sensor inputs and four relay outputs for heating, cooling and one-, two- or three-stage compressor applications.
At a Glance
| Brand | Siemens |
|---|---|
| Model | RWD44U |
| Product Type | Standalone temperature controller |
| Core Function | Staged heating and cooling regulation |
| Application | HVAC, refrigeration and heat-pump installations |
Universal sensor inputs
X1 and X2 accept Siemens Ni 1000, Pt 1000 or active 0–10 V DC sensor signals.
Four relay outputs
Q1 to Q4 provide two-position control for the selected application.
Compressor staging
Preconfigured applications support up to three compressor stages and a reversing valve.
Product Overview
RWD44U regulates heating, cooling and refrigeration equipment through four on/off relay outputs. Its preconfigured applications cover two heating and two cooling stages or up to three compressor stages with a reversing valve for heat-pump operation.
The X1 input provides the main temperature measurement, while X2 can provide auxiliary sensing, remote setpoint, averaging or other selected functions. A separate D1 input supports functions such as day/night changeover, standby and alarm handling.
Key Functions
Configure staged equipment control
Applications 10–19 provide heating and cooling stages, while applications 20–39 configure compressor stages and a reversing valve.
Adapt sensing and auxiliary functions
The universal inputs support Ni 1000, Pt 1000 and active 0–10 V DC signals, with X2 also supporting a remote resistance setting.
Coordinate switching delays
Adjustable minimum on/off times and interstage or heating/cooling delays range from 0 to 4,096 seconds.
Official Specifications
| Controller supply | 24 V AC, SELV |
|---|---|
| Universal input channels | 2, designated X1 and X2 |
| Supported sensor signals | Siemens Ni 1000, Pt 1000 and 0–10 V DC |
| Ni 1000 sensing range | −50 to +150 °C |
| Pt 1000 sensing range | −20 to +180 °C |
| Active-input scaling limits | −100 to 2,400 for the 0–10 V DC input range |
| Remote-setpoint input at X2 | 0–10 V DC or 0–1,000 Ω |
| Digital input | 1, designated D1 |
| Control outputs | 4 two-position relay outputs, Q1–Q4 |
| Relay switching voltage | 24–240 V AC |
| Relay contact ratings | 5 A resistive; 5 FLA; 30 LRA; 1/2 HP |
| Switching differential range | 0.1–50 K |
| Switching timing ranges | 0–4,096 s for minimum on/off, interstage and heating/cooling changeover delays |
| Sensor calibration offset | −5 to +5 K for Ni and Pt sensor inputs |
| PC tool connection | 9-pin TOOL communication connector |
| Controller dimensions | 130 × 106 × 56.5 mm (W × H × D) |
Frequently Asked Questions
Can I connect the supply terminals of RWD44U directly to 230 V AC?
The controller supply requires 24 V AC SELV rather than mains voltage.
Can RWD44U control a heat pump with three compressor stages?
Its preconfigured heat-pump applications support up to three compressor stages and a reversing valve.
Which passive temperature sensors can I connect to RWD44U?
The universal inputs support Siemens Ni 1000 and Pt 1000 temperature sensors.
Can I rescale the Ni 1000 sensing range on RWD44U like an active input?
The Ni 1000 range is fixed at −50 to +150 °C, while active 0–10 V DC inputs permit user-defined scaling.
Can RWD44U average two temperature measurements?
The auxiliary-function selection includes averaging of the X1 and X2 sensor inputs.
Is a PC required for the initial setup of RWD44U?
The controller supports local parameter setup, while the PC software tool is optional.
How can I keep RWD44U from switching a compressor on and off too quickly?
Set the required minimum on and minimum off times within their 0–4,096 second adjustment ranges.