Siemens 7UF7000-1AB00-0 SIMOCODE pro C Motor Management Basic Unit
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the 24 V DC supply variant within its permitted operating range.
- Select a compatible current measuring module for current-based motor protection.
- Choose the 9-pin bus socket for rates above 1.5 Mbit/s.
- Use the thermistor input for the corresponding sensor circuit, rather than an analog temperature sensor.
- Select direct or reversing starting as required; the pro C arrangement does not provide star-delta control.
- Allow the stated cabinet clearances and apply the terminal torque and cable-length limits.
7UF7000-1AB00-0 SIMOCODE pro C Motor Management Basic Unit
A 24 V DC SIMOCODE pro C basic-unit arrangement with configurable digital I/O, monostable relay outputs, a thermistor input and PROFIBUS DP communication up to 12 Mbit/s.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 7UF7000-1AB00-0 |
| Product Type | Motor management and control basic unit |
| Core Function | Coordinating motor protection, control and diagnostics |
| Application | Compatible PROFIBUS motor-feeder assemblies |
Configurable control I/O
Four digital inputs and three monostable relay outputs serve the motor control circuit.
PROFIBUS connection
The RS-485 interface provides a 9-pin socket and a separate screw-terminal connection with different speed limits.
Thermistor evaluation
The dedicated sensor input evaluates the motor thermistor circuit.
Product Overview
7UF7000-1AB00-0 provides the control and communication functions of a SIMOCODE pro C motor-feeder assembly.
A separately selected current measuring module supports current-based protection and monitoring, while the basic unit supplies the configurable control I/O, thermistor evaluation and PROFIBUS diagnostics.
Key Functions
Coordinate motor-feeder control
The control functions include direct starting, reversing starting, circuit-breaker control and configurable overload-relay operation.
Evaluate motor and field signals
The unit combines four configurable digital inputs with thermistor evaluation, and the appropriate current module enables current-based overload, asymmetry and phase-failure functions.
Exchange commands and diagnostics
PROFIBUS DP provides bus communication and diagnostic data, using the selected RS-485 connection and its corresponding transmission-rate limit.
Official Specifications
| Control Supply | 24 V DC nominal; permissible operating factor 0.8–1.2 × rated voltage |
|---|---|
| Consumed Active Power | 2.3 W |
| Supply Inrush | 14 A peak for 0.8 ms at 24 V |
| Power-Failure Buffering Time | 0.05 s |
| Digital Input Bank | 4 inputs with common reference potential; 24 V DC; Type 1 according to EN 61131-2 |
| Output Bank | 3 configurable monostable relay outputs |
| Relay AC-15 Switching Current | 6 A at 24 V or 120 V AC; 3 A at 230 V AC |
| Relay DC-13 Switching Current | 2 A at 24 V DC; 0.55 A at 60 V DC; 0.25 A at 125 V DC |
| Relay Continuous Current | 6 A at 50 °C; 5 A at 60 °C |
| Typical Relay Endurance | 10 million mechanical operations; 100000 electrical operations |
| Thermistor Evaluation Thresholds | Maximum total cold resistance: 1.5 kΩ; response: 3400–3800 Ω; release: 1500–1650 Ω; short-circuit control: 9 Ω |
| PROFIBUS Electrical Connections | 9-pin SUB-D socket up to 12 Mbit/s; screw-terminal connection up to 1.5 Mbit/s |
| Maximum Digital-Signal Cable Length | 300 m |
| Maximum Thermistor Cable Length | 50 m with 0.5 mm² conductors; 150 m with 1.5 mm²; 250 m with 2.5 mm² |
| Control-Terminal Connection | Removable screw terminals; tightening torque 0.8–1.2 Nm |
| Control Conductor Cross-Sections | Solid: 1 × 0.5–4 mm² or 2 × 0.5–2.5 mm²; finely stranded with end processing: 1 × 0.5–2.5 mm² or 2 × 0.5–1.5 mm² |
| Dimensions | 45 × 111 × 95 mm (W × H × D) |
| Ambient Temperature | Operation: −25 to +60 °C; storage and transport: −40 to +80 °C |
| Required Clearances | 40 mm above and below; 0 mm to either side |
| Net Weight | 281.5 g |
Frequently Asked Questions
Does 7UF7000-1AB00-0 measure motor current through the basic unit itself?
The basic unit uses a compatible separate current measuring module for current-based functions.
Can I connect an analog temperature sensor to 7UF7000-1AB00-0?
The basic unit provides a thermistor input but does not accept analog temperature sensors.
Can 7UF7000-1AB00-0 join a PROFINET IO network directly?
This arrangement communicates over PROFIBUS DP and does not provide a PROFINET IO interface.
Which PROFIBUS connection on 7UF7000-1AB00-0 should I use for 12 Mbit/s?
Use the 9-pin SUB-D socket because the screw-terminal bus connection is limited to 1.5 Mbit/s.
Can the control supply of 7UF7000-1AB00-0 be connected to 230 V AC?
This supply variant requires 24 V DC with an operating range of 0.8 to 1.2 times the rated voltage.
Can I select a star-delta starter function on 7UF7000-1AB00-0?
The pro C control functions include direct and reversing starting but do not include a star-delta circuit.
How much free space should I leave around 7UF7000-1AB00-0 in the cabinet?
Allow 40 mm above and below the unit, while no additional side clearance is required.